Title: DAQMASTER
1DAQMASTER MW100Class I Div 2 Data Acquisition
Systemwith AGA Gas Flow Computer Option
Features and Benefits
- Yokogawa Corporation of America
- Network Solutions Business Unit
Rev. 1
2Basic Features Overview
- DAQMASTER MW100
- Basic Features
- FM Approved Class I Div 2
- Gas Flow Computer with AGA3/AGA8
- Scalable / Distributed Universal I/O
- Secure Redundant Data
- Network Capable
- Easy to Configure
- I/O with High Accuracy, Stability Isolation
- Built in web server
3Scalable / Distributed Universal I/O
- Easily Expandable
- Build 10 to 1000s of point I/O systems
- Start small and expand in the future
- Reduce wiring and installation costs
- Locate I/O in any location
- Add I/O to new or existing DCS or PLC
withoutmoving existing wiring - Cost effective
- Reduce Spare Parts by stocking common universal
I/O modules - Very reliable hardware reduces maintenance costs
- Calibration held in each module
simplifiescalibration procedures
4Secure Redundant Data
- No lost data
- Measured data is storedin a local CF (Compact
Flash)memory card - Data will automatically backfill via FTPafter a
failed network recovers - Low operation cost
- System can run standalone without any
operatorinteraction by FIFOing stored data on
local CF memory card - Large CF card will store data for a long period
without operator intervention
Data via FTP
5Network Capable
- Easy integration to existing systems
- Add I/O to an existing DCS without purchasing
expensive I/O cards and DCS tags - Add modern advanced communication capabilities to
your existing PLC or DCS without complex
engineering and integration costs - Safe guard critical data by storing data locally
- Examples
- A-B SLC500, PLC5
- A-B ControlLogix
- Bailey Infi90
- Westinghouse
- DeltaV
- Yokogawa CS
- Foxboro IA
- Seimens S7 PLC
DCS Field Control Station
6Network Capable
FTP SERVER
FTP CLIENT
WEB CLIENT
MODBUS SERVER
EMAIL SERVER
MODBUS CLIENT
SNTP SERVER
MODBUS MASTER
SNTP CLIENT
PI DATA Historian
MODBUS SLAVE
YOKOGAWA DIAGNOSTIC PORT
7Easy to Configure
- Dedicated PC is NOT required
- Everyone with internet access can view data
without special software - No annual software license costs
- View trend, digital alarm process data and log
historical data in minutes - Eliminate expensive configuration and integration
costs - Build control applications without hiring an
integrator - Control configuration is accomplished with
readable math equations and logic statements
(IF,THEN,ELSE,AND,OR,NOT) - All configuration is handled via the DAQMASTER
built-in webserver
Configure
View Real-time Data
8I/O with High Accuracy, Stability Isolation
- Low operation cost
- One module can handle any application by
measuring any signal from 20/-20mV to 100/-100
V, plus DI contact or Level Inputs - Calibration is held in each module and terminal
blocks can be removed - DAQMASTER will withstand accidental over voltage
situation with 3700 VRMS (for 1 minute) and 600
VRMS/VDC continuous isolation
Remove module without breaking 4-20mA loops. Take
the module to the shop for calibration.
9MW100 FM Approval to Class I Division 2
- DAQMASTER MW100
- FM Approved Class I Div 2
- Factory Mutual Approval
- Class I Division 2
- Groups A,B,C,D
- Hazardous (classified) indoor use
- FM3610
- FM3611
- FM3810
- Differences to standard MW100
- No on/off power switch
- 24 Vdc power supply only
- Some I/O modules have usage restrictions
- See Instruction Manual for details
-
10MW100 FM Approval Certificate
11Gas Flow Terminology
- AGA American Gas Association
- Industry research and marketing body that
promotes standards - Flow Computer
- Receives inputs from sensors and applies AGA
calculations to record corrected flow rates and
energy density - Common flow sensors
- Orifice Plate
- Venturi-tube
- V-Cone
- Turbine meter
- Compressibility
- gas becomes more dense under pressure, requiring
calculation of a compressibility factor (Z) in
order to return it to Standard Temperature and
Pressure (STP) volume.
12MW100 AGA Gas Flow Computer Features
- DAQMASTER MW100
- AGA Gas Flow Computer Features
- Supports AGA 3 and AGA 8 methods
- One MW has (10) gas flow computation sets!
- Currently supports orifice and venturi sensor
types - AGA gas flow comes with Class I Div 2 model (/S8
option) - New software (MW180-2) used for gas flow setup
13Backgroun AGA Reports and Methods
- AGA 3
- Corrected gas flow in conjunction with Orifice
Plates and DP Sensors - Density input is external input or fixed value.
- AGA 7
- corrected gas flow in conjunction with Turbine
Meters, requires external input for density or
fixed value. - NX-19
- Older, less intensive corrected closed-form
(non-iterative) gas flow calculation for natural
gas compositions of up to 15 CO2 and N2.
Supported by many flow computers. - AGA 8
- Complex compressibility and density calculations
- Uses table look-ups and iterative sequences
- Compensates for higher inert composition and
operating conditions. - Accepted as most accurate
14Background Characterization Methods
- All methods need operating P, T, and ACFH to be
able to compute SCFH - Detail Characterization
- Input complete breakdown by Mole of gas
composition - Gross Characterization Method 1
- Input specific gravity, CO2, and Heating Value
(BTU/FT3) - Gross Characterization Method 2
- Input Specific Gravity, CO2 , and N2
- MW100 Supports all three characterization types
15Background NX-19 vs. AGA 8
www,.omniflow.com
16How Gas Flow Computation is done in MW100
- Use MVTool offline software to setup gas flow
parameters - Download gas flow configuration to MW100 (this is
a new step) - Use standard webserver configuration tools to
program MW100 - Add new math statements to access gas flow
computation results
MW100
Main module
MATH calculation
Output modules
Flow rate
Differential pressure
Input module
Flow calculation
Recording
Static pressure
Temperature
MW100 MVTool
Web browser
Flow standard Primary device configuration Input
configuration Fluid component configuration
MW100 configuration Measurement Monitoring
17Flow Standard
18Fluid Standard
19MW100 Flow Calculation Function
20MW100 Flow Calculation Function
- New math statement in MW for gas flow
A001 FXFL.OUT(1)
Uses results of virtual flow meter 1
A002 FXFL.OUT(3)
Uses results of virtual flow meter 2
21MW100 Flow Calculation Function
- Model code
- MW100 main module MW100-E-3W/M1/S8
- /M1 has to be specified
- /C2 or /C3 can be specified
- Configuration software MVTool (MW180-2)
required - Specification and functions
- Primary devices and standard
- Orifice (AGA Report 3)
- Venturi tube, Venturi nozzle (ASME MFC-3M,
ISO5167-1, ISO5167-4) - Fluid type and standard
- Natural gas (AGA Report 8)
- Coefficient files
- 10 coefficient files
- Virtual flow meters
- 10 virtual flow meters (10 flow groups)
- 100msec per virtual flow meter
- Flow type Mass flow, Volume flow,
Normal-standard volume flow - MW100 Math functions