Title: Greenhouse Cooling
1Greenhouse Cooling
- Summer Cooling
- Winter Cooling
2Conditions of Un-cooled GH
- 20-30º F warmer than outside
- Detrimental effects
- loss of stem strength
- reduced flower size
- delay in flowering
- bud abortion
- improper water and nutrient uptake
3Cooling methods
- Evaporative cooling
- fan and pad (1954)
- package coolers (swamp coolers)
- Fog (1980)
- General ventilation and de-humidification
4Benefits
- Reduce air temperature below outside temperature
by 25º F. - Improve CO2 uptake
- Improves nutrient and water uptake
- Hardier foliage and stems
- Provide constant air movement
- Control humidity levels
5Terms
- Evaporative cooling
- Wet Bulb Temperature
- Dry Bulb Temperature
- Air Flow
- Psychrometric Chart
- Relative humidity
6Summer Cooling System
- Fan and Pad System
- Rate of air exchange measured in cubic feet of
air per minute (cfm) - Factors affecting air exchange
- elevation
- light
- allowable temperature increase from pad to fan
7Summer Cooling System
- The rate of air flow through a greenhouse is
generally the cubic foot capacity of the
greenhouse with a few corrections factors. - Corrections factors?
8Elevation
- As the elevation increases, fan capacities need
to be increased. - One pound of air at sea level occupies a given
volume. As this pound of air moves up in
elevation, its volume increases. The weight
remains the same. - Buy a bag of potato chips in San Bernardino, then
drive up to Big Bear. What happens to the bag of
chips?
9Light
- As light intensity increases, the heat input from
the sun increases requiring greater air removal
from the greenhouse. - An intensity of 5,000 foot candles is accepted as
a desirable level for crops in general. Can be
achieved with a coating of shading compound on
the outside, or a screen material drawn from eave
to eave.
10Pad to fan temperature rises
- Solar energy warms air as it moves from pad to
fan. - Usually a 7º rise in temperature as air moves
from pad to fan is acceptable. - If a more constant temperature is desired, the
velocity of the fans should be increased.
11Calculation formula
- Standard cfm L x W x 8 x Fhouse
- Correction formula
- Fhouse Felev x Flight x Ftemp
- or
- L x W x 8 x Fvel, where Fvel 10/?D.
- D distance of air travel
- usually used when D is less than 100 ft.
- use larger of the two correction factors.
12Example 1
- GH 70 ft. x 50 ft.
- at 500 ft elevation
- 5000 fc
- 7º F pad to fan increase allowed
- Calculate the cfm requirement for this GH.
13Solution-Ex. 1
- Std cfm 70 x 50 x 8 28,000
- Fhouse 1.0 x 1.0 x 1.0 1.0
- Corrected cfm value 28,000 cfm / min.
- air will be drawn in the 70 ft. direction. Since
it is less than 100 ft., the Fvel formula should
also be used. In this case, it is equal to
10/?70 1.2 - Therefore, 1.2 is used instead of 1.0
- Correct value 28,000 x 1.2 33,600 cfm
14Example 2
- GH 70 x 50
- Elevation 5,000 ft.
- Light 6000 fc
- Allowable Pad to fan T 7º F
- Determine Cooling requirement
15Solution Ex. 2
- 50 x 70 x 8 28,000 cfm
- Fhouse 1.2 x 1.2 x 1.0 1.44
- Corrected cfm 28,000 x 1.44 40,320
- F vel 28,000 x 1.2 33,600 cfm
16Fvel 10/?D
- Use this formula when distances of air travel are
less than 100 ft. - Compare the Fhouse value with this, use the
larger of the two. - When air flow is less than 100 ft., the air feels
like there is no velocity, therefore, the fan
capacity should be increased.
17Determining Fan Capacities
- Fans should not be more than 25 apart from
center to center. - Divide length of wall by 25
- 50 ft. ? 25 ft. 2 fans needed
- 40,320 cfm ? 2 20,160 cfm/fan
18(No Transcript)
19(No Transcript)
20(No Transcript)
21Cool Pad Description
- Material should provide an evaporative surface
with large surface area. - Material should be able to withstand weathering.
22Cool Pad Materials
- Aspen Fiber
- Cross-fluted Cellulose
23Cool Pad Efficiencies
- Aspen 150 cfm/ft2
- Cross-Fluted Cellulose 4 thick 250 cfm/ft2
- Cross- Fluted Cellulose 6 thick 350 cfm/ft2
24Determining amount of Pad Material
- Total corrected cfm required / cooling efficiency
per ft2 of pad. - Example If 40,0000 cfm is required and a 4
cool cell will be used - 40,000/250 160 ft2 required.
25Determining the Height of the Pad
- Identify length of wall on which pad will be
installed. - Divide total cfm required by wall length
- 160 sq. ft./ 50 ft. 3.2 ft. high
26Determining Sump Capacity
- Sump volume 1.5 gal. Per foot of pad length.
27Determining Pump Capacity
- Pump capacity 0.6 gal per min. x length of pad.
- 0.6 gal. Per min. x 50 ft. 30 gal per min.
28(No Transcript)
29GH Cooling
- Pad Location
- Water Treatment
- Sump Bleeding
- Salt Maintenance
- Fan Belt Tension
- Fan Motor Alignment
- Thermostat Calibration
30GH Cooling
- Fan Baffles
- Air Baffles throughout GH
- Air Circulation Fans
- Louver Maintenance
- Shade cloth interior/exterior
- Shading Compound
31Winter Cooling
- System Description
- Pressurizing Fan
- Plenum Chamber
- Convection Tube
- Motorized Inlet Shutter
32Winter Cooling
- System Tied to Summer Cooling system
- Uses some of the exhaust fans either at full of
low speeds. - Air being exhausted in this mode should not
exceed the incoming air volume. - Process can be referred to as minimum
ventilation. - Process can also be used for dehumidification.
33Winter Cooling Calculation
34Winter Cooling Calculation
- Formula L x W x 2 x Fjet
- Where F jet Felev x Flight x Fwinter
- Fwinter factor taken from tables.
35Winter Cooling Example
- GH 70 x 50
- Elevation 5,000 ft.
- Light 6000 fc
- Allowable Pad to fan T 7º F
- GH temp above outdoor temp 13 F
- Determine Winter Cooling requirement
36Example (contd)
- From previous example, we needed 40,320 cfm for
maximum cooling. - Total cfm required 50 x 70 x 2 x Fjet
- Fwinter 1.15
- ?Fjet 1.2 x 1.2 x 1.15 1.66
- Corrected cfm 50 x 70 x 2 x 1.66 11,620
37Example (contd)
- In the winter cooling mode, air will be entering
the GH at a rate of 11,620 cfm. - One of the exhaust fans should be running at a
rate not to exceed 11,620 cfm. - We called for 2 fans, each with a capacity of
20,160 cfm. - If one fan runs at ½ speed, the capacity will be
less than 11,620 cfm
38Example (contd)
- Another option is to divide 40,320 by 4 and use 4
fans, each with a capacity of 10,080 cfm. - During the winter cooling mode, one fan will run
to expel hot humid air. - Any other solutions?
39Dehumidification
- Relative Humidity
- Psychrometric Chart (follow your charts)
- Curved lines RH
- Horizontal line at bottom 0 RH
- Upper most line 100 RH or total saturation
40(No Transcript)
41Example of RH
- At 100 RH, locate the 60 F dry bulb vertical
line. At this condition, 1 lb. Of air contains
77 grains of H2O vapor - Follow the 60 F dry bulb line to 50 RH line. At
this condition there are approximately 38 grains
of water vapor. The air is now only 50 full and
thus has a RH of 50. -
42Relative Humidity
- The amount of water vapor in the air compared to
what it can actually hold at that temperature.
43Example of RH
- We always experience a daily fluctuation in
outdoor relative humidity. - Assume a night temperature of 65 F with 95 RH.
During the day, air arms air to 85 F, the RH
drops to 45. - Also, as air gets colder, the capacity of
holding moisture is reduced.
44Example 1a
- If the greenhouse is at 60 F and air contains 77
grains of moisture and the temperature drops to
40 F, air now contains only 38 grains of
moisture. What happened to the other 39 grains
of moisture?
45Example 1b
- Assume a greenhouse condition of 65 F night
temperature and 75 RH. With poor heat
distribution and random cold air currents, a cold
spot that is at 56 F develops. What would be the
outcome?
46Effect of Temperature on RH
- In a previous example, 1 of air at 60 F DB and
100 RH contained 77 grains of moisture. If air
is warmed 20 F to a temp. of 80 F, the RH is now
50. - Air at 80 F could hold 156 grains of moisture
when saturated but actually contains only 77
grains, therefore is only half full.
47Effect of T on RH (contd)
- If air is warmed another 20 F, to 100 F, the RH
will drop to 25. - This shows that for every 20 F DB rise in T, the
capacity of air to hold water vapor approximately
doubles.
48Reducing the RH in the GH
- If cold air w/ low water vapor content is brought
into the GH and warmed, the capacity to hold
water vapor increases.
49Reducing RH in the GHExample2
- Assume a rainy weather condition, 40 F at 100 RH
outside. - Inside GH, 65 F at 90 RH. Too humid.
- Is it possible to lower the RH to a satisfactory
level even if it is raining outside?
50Reducing RH in GH
- Chart shows
- every of air holds 83 grains inside the GH.
- Every of air holds 37 grains outside.
- Therefore, with each of air removed by an
exhaust fan, 83 grains are carried out (removed)
while 37 grains enter the house with the make-up
air. - This results in a net removal of 46 grains of
moisture.
51Reducing RH in the GH
- A dehumidification system utilizing exhaust fans
running to expel half of the air in the GH will
lower the RH to 65 once the GH is heated back
to 65 F.
52Fog Cooling
- Evaporative Cooling
- Increase Humidity in Propagation
- Reduce Light Levels
53(No Transcript)
54(No Transcript)
55(No Transcript)
56Greenhouse CoolingSystem Description
- Use of series of fog nozzles
- High pressure 400-2000 PSI pumps
- Water treatment and filters
- Ridge Vent
- Thermostat/Humidistat sensing devices
57(No Transcript)
58(No Transcript)
59Fog Cooling Facts
- Fog particle size 10-40 microns
- High pressure
- Surface area 10,000 x greater than same volume
in 1 cup of water - Droplets stay suspended in air, no condensation
- Droplets evaporate 40,000 faster than H20 in a
cup - Air cooled at 100 efficiency
60Advantages
- Uses les electricity
- Even temperature control across greenhouse
- Cooler average temperatures achieved
- Good substitute for mist
- Can be used outdoors in dry climates
61(No Transcript)