Check water flow in the system. Minimum water flow system 9liter / min.
4 Freeze up problem
Code
Part Refrigerant liquid sensor
LocationLiquid pipe hydrobox
Activation failure Temperature liquid sensor too low.
Possible action to resolve the problem
Check refrigerant charge of the installation
5 Flow failure
Code 7H
Part Flow failure
Location
Activation failure Flow switch open during operation (no signal)
Possible action to resolve the problem
Check water flow in the system. (Minimum water flow system
20liter / min.)
Check water pressure in the installation. (Minimum 0.3 bar)
Check shutt OFF valves
Is water system purged
Check pressure drop and speed of the waterpump
Check pump operation
6 Outlet water temperture too high
Code 8H
Part Outlet water thermistor
Location Outlet back up heater
Activation failure If outlet water gt 65C
Possible action to resolve the problem
Check if contactor(s) back up heater is not welded
Check if thermistor is not damaged
Check if correct resistor value of thermistor
Procedure Refer to service manual
7 Indoor PCB failure
Code A1
Part Indoor PCB
Location Switchbox
Activation failure
Possible action to resolve the problem
Replace PCB
8 Insufficient cooling or heating
Code A5
Part Liquid sensor hydrobox
Location
Possible action to resolve the problem
Check water flow in the system. (Minimum water flow system
9liter / min.)
Check water pressure in the installation. (Minimum 0.3 bar)
Check shutt OFF valves
Is water system purged
Check pressure drop and speed of the waterpump
Check refrigerant charge
Check thermistor
Procedure refer to service
manual
9 Booster heater thermal protector
Code AA
Part Thermal protector booster heater or back up heater
Location
Possible action to resolve the problem
Check if thermal protection is not damaged.
Check contactor of the electric BUH / BSH
10 Stucked flow switch
Code CO
Part Flow switch failure
Activation failure Flow swith remains closed when pump is not operating
Location
Possible action to resolve the problem
Check for dirt in flow switch
Replace part is required
11 Heat exchanger thermistor failure
Code C4
Part Liquid sensor
Activation failure Sensor broken or out of range
Location
Possible action to resolve the problem
Check connector
Check resistance of the sensor
Procedure refer to servicemanual for procedure
If damaged replace part
12 Outdoor PCB failure
Code E1
Part Outdoor PCB failure
Activation failure
Location
Possible action to resolve the problem
Out of control of CPU
Voltage drop
Power loss
Noise on power supply
Defect outdoor PCB
13 Overload activation of compressor
Code E5
Part Overload protector compressor
Activation failure Failure If overload protector ( gt130C) is activated twice in one hour
Location Outdoor unit
Possible action to resolve the problem
Refrigerant shortage.
Malfunction four way valve.
Outdoor PCB failure.
Electronic expansion valve defective.
14 Compressor start up failure
Code E6
Part Compressor locked
Activation failure Failure, if error occurs 16 times, counter reset if compressor runs normal for 5 minutes
Location Outdoor unit
Possible action to resolve the problem
Replace outdoor PCB
Replace compressor
15 Fan motor failure
Code E7
Part Outdoor fan motor
Activation failure Failure, if error occurs 16 times, counter reset if compressor runs normal for 5 minutes
Location Outdoor unit
Possible action to resolve the problem
Fan motor breakdown
Bad contact between PCB and fan motor
Blockage of the fan blades
16 Overcurrent failure
Code E8
Part Compressor overcurrent
Activation failure Failure, if current (gt30 Amp) occurs 16 times. Counter reset if compressor runs normal for 5 minutes
Location Outdoor unit
Possible action to resolve the problem
Compressor breakdown.
Short-circuit
Defective power transistor.
Defective capacitor on inverter board.
Defective outdoor PCB.
17 Cool / Heating switching failure
Code EA
Part four way valve
Activation failure
Cooling if (room temp liquid temperature) lt -10C
Heating if (
Location
Possible action to resolve the problem
18 Sanitary water too high
Code EC
Part Sanitary tank temperature
Activation failure If temperature sanitary water gt 89C
Location Sensor inside sanitary tank
Possible action to resolve the problem
Check position of sensor in socket
Check if contactor(s) booster heater is not welded
Check if thermistor is not damaged
Check if correct resistor value of thermistor
19 Discharge temperature too high
Code F3
Part Discharge sensor
Activation failure Failure if discharge temperature gt 120C for 6 times
Location Sensor located on the discharge pipe of compressor
Possible action to resolve the problem
Refrigerant shortage.
Malfunction four way valve.
Defective discharge sensor.
Defective EEV driver.
20 Too high condensing pressure
Code F6
PartSensor outdoor heat exchanger
Activation failure Failure if temperature heat exchanger gt 60C
Possible action to resolve the problem
Faulty outdoor fan
Faulty EEV
Dirty heat exchanger
Faulty thermistor
21 Too high condensing pressure
Code FA
Part
Activation failure
Possible action to resolve the problem
22 Voltage and current sensor failure
Code H0
Part Voltage / Current sensor
Activation failure
No measurement of current during compressor operation.
Possible action to resolve the problem
Reactor disconnected
Compressor disconnection
Outdoor PCB failure
Compressor defective
23 Compressor start up failure
Code H6
Part Compressor / Outdoor PCB
Activation failure Failure when compressor fails to start 8 times.
Possible action to resolve the problem
Compressor cable disconnected
Compressor
Outdoor PCB
Supply voltage out of voltage specifications
24 CT failure
Code H8
Part Current transformer on outdoor PCB
Activation failure Failure if compressor running freq lt 55Hz and CT input lt then 0.1V for 4 times
Possible action to resolve the problem
Power transistor defective
Bad or poor electrical contact
Reactor defective
Outdoor PCB
25 Outdoor ambient thermistor
Code H9
Part Thermistor
Location
Activation failure Resistance value out of range
Possible action to resolve the problem
Check connector
Check resistance value
Replace thermistor.
Outdoor PCB
26 Discharge pipe thermistor
Code J3
Part Discharge pipe thermistor
Location
Activation failure Resistance value out of range
Possible action to resolve the problem
Check connector
Check resistance value
Replace thermistor.
Outdoor PCB
27 Outdoor heat exchanger
Code J6
Part Thermistor
Location
Activation failure Resistance value out of range
Possible action to resolve the problem
Check connector
Check resistance value
Replace thermistor.
Outdoor PCB
28 Fin thermistor switchbox
Code P4
Part resitance located on the outdoor PCB
Location
Activation failure Resistance value out of range
Possible action to resolve the problem
Outdoor PCB
29 Electrical box temperature rise
Code L3
Part Radiation fin thermistor
Location Outdoor PCB
Activation failure failure if temperature gt 85C and compressor OFF
Possible action to resolve the problem
Defective outdoor fan
Defective Fin thermistor
Defective Outdoor PCB
Heat conductive paste
30 Radiation fin temperature rise
Code L4
Part Radiation fin temperature rise
Location Outdoor PCB
Activation failure failure if temperature gt 105C and compressor ON for 4 times
Possible action to resolve the problem
Defective outdoor fan
Defective Fin thermistor
Defective Outdoor PCB
Heat conductive paste
31 Output overcurrent detection
Code L5
Part
Location Outdoor PCB
Activation failure failure if running current is gt then preset value
Possible action to resolve the problem
Defective power transistor
Defective outdoor PCB
Defective compressor
Poor installation condition
32 Insufficient gas
Code U0
Part
Location Outdoor
Activation failure see next slide
Possible action to resolve the problem
Refrigerant shortage
Poor performance of the compressor
Defective electronic expansion valve
33 Insufficient gas When discharge pipe temperature is 45C higher than target value and the electronic expansion value opening is 480 pulse (max.), the adjustment is made for insufficient gas. When an output frequency is exceeds 40 Hz and the input current is less than specified value, the adjustment is made for insufficient gas. 34 Low or High volttage detection
Code U2
Part DC detection circuit
Location Outdoor PCB
Activation failure Low / Over voltage. Failure when low or overvoltage occurs 16 times
Possible action to resolve the problem
Supply voltage not within the specifications
Detection circuit defect
PAM control defective
35 Signal transmission error on outdoor PCB
Code U7
Part CPU PM1
Location Outdoor PCB
Activation failure Failure when communication error between outdoor PCB and power module
PowerShow.com is a leading presentation sharing website. It has millions of presentations already uploaded and available with 1,000s more being uploaded by its users every day. Whatever your area of interest, here you’ll be able to find and view presentations you’ll love and possibly download. And, best of all, it is completely free and easy to use.
You might even have a presentation you’d like to share with others. If so, just upload it to PowerShow.com. We’ll convert it to an HTML5 slideshow that includes all the media types you’ve already added: audio, video, music, pictures, animations and transition effects. Then you can share it with your target audience as well as PowerShow.com’s millions of monthly visitors. And, again, it’s all free.