Title: Air Conditioning
1Air Conditioning Charging Procedures Review
2Basic Refrigeration
3Basic Refrigeration
Liquid Line
Liquid Line
Metering Device
Condenser
Low Side
Hi Side
Evaporator
Compressor
4Saturation Temperature
5What is Saturation Temperature?
- Saturation temperature is the actual temperature
of the evaporator and condenser coils. - In saturation conditions, both vapor and liquid
are present
6How do you find Saturation Temperature?
- Refrigeration Gauges
- The Only purpose of owning a set of gauges is to
find the refrigerant saturation temperature.
7Saturated Refrigerant
Liquid Line
Metering Device
Condenser
Evaporator
Discharge Line
Suction Line
Compressor
8System Charging
9First things first
- You must verify that you have proper airflow!and
you must have the proper tools to do the job.
10Air Flow
11Air Flow is Critical
12Air Flow Measurements
- Total Static Pressure
- CFM Measurements
- -Temperature Rise
- -Evaporator Pressure Drop
- -Air Velocity
- -Temperature Drop
13Static Pressure Measurement
- The key to system airflow diagnostics
- A companion to airflow measurement
- It takes less than 5 minutes to measure
- Similar to blood pressure diagnostics
14(No Transcript)
15 Total Static Pressure
16Air Flow Measurement-Temperature Rise Methodto
determine CFM
17Airflow Measurement(Temperature Rise Method)
(Red Book, Pg. 33)
18CFM By Temperature Rise
CFM
1.08 constant number for std air. Its a
combination of a number of values that are in the
complete equation. Std air is 70F, sea level
19CFM By Temperature Rise
- 55,200 BTU output
- 60 X 1.08
850 CFM
64.8
20CFM By Evaporator Pressure Drop
21(No Transcript)
22(No Transcript)
23(No Transcript)
24(No Transcript)
25Velocity
- Velocity FPM
- CFM FPM X Area in Square Feet
- Free Area
26Humid Air
Dry Air
27Fan Speed Taps
- Check Service Facts for proper air speed tap to
use - Match tap to size (BTUH) of unit
28(No Transcript)
29Blower should always be on high speed?
30(No Transcript)
31System Charging
32The Right Stuff
- Basic Tools
- Refrigerant Gauges
- Digital Thermometer (one with Wet Bulb
capabilities)
33SYSTEM CHARGING
- The sub-cooling method is required when charging
TXV systems. - The super-heat method is required when charging
fixed orifice systems. - Charging charts are included in the Service Facts
document that come with the outdoor equipment. - Remember to allow sufficient time for the system
to stabilize before adjusting the refrigerant
charge.
34Beer Can Cold and Sweaty
35SYSTEM CHARGING(SC) Using the Charging Chart-TXV
- Measure temperature and pressure at liquid line.
- Use line length lift to choose which curve to
use. - Plot the intersection of temp. pressure.
- If above the curve, remove refrigerant.
- If below, add refrigerant
- Wait 20 minutes to stabilize.
36Sub-Cooling Calculation
- Low Sub-Cooling indicates LOW charge
- High Sub-Cooling indicates OVER charge ( or
possible liquid line restriction) - Rule of thumb 10 - 15 degrees of sub-cooling
Manufactures usually design to 10 degrees
37(No Transcript)
38(390 PSIG 115ยบ F)
39SYSTEM CHARGING(SH) Using the Charging
Chart-Fixed Orifice
- Measure indoor dry bulb (R/A)
- Measure outdoor dry bulb (at unit)
- Measure suction pressure
- Measure suction temperature, before suction
service valve - Use chart to determine SH
- Above 5 F above, add. If 5 F below, remove.
- If below 5 F limit line, DO NOT ADD.
- If RH gt70 or lt20, use ID wet-bulb
40Superheat Calculation
- Superheat indicates that complete vaporization of
liquid refrigerant in the evaporator coil has
taken place - Low Superheat means liquid refrigerant is present
at or near the outlet of the evaporator -
compressor damage is immanent - High Superheat means liquid is boiling off too
soon and could mean evaporator is starved
41(No Transcript)
42Customer Complaint
- System does not cool like it before when it was
new - What do you do?
Check the Enthalpy of the Evaporator Coil
to verify system capacity
43Use the Formula
- Total Heat Removed
- CFM X 4.5 X Change in Enthalpy (Heat Content)
44Enthalpy
- Same as TOTAL HEAT
- The sum of sensible heat and latent heat
Wheres the 4.5 come from? Its how many BTUs
are in one pound of DRY air (0Rh)
45(No Transcript)
46Total Heat CFM X 4.5 X Enthalpy Change
69 WB33.25 60 WB26.46 Difference 6.79 800 X
4.5 X 6.79 24,444 BTUH !
47(No Transcript)
48(No Transcript)
49(No Transcript)
50(No Transcript)
51(No Transcript)
52(No Transcript)