Title: ZonePRO Modulating Thermostats
1ZonePRO Modulating Thermostats
- New Product Introduction
- Technical Training
- July 10, 2006
2Models and Features
- Models with 1 output
- TB6980A1007 (Floating)
- TB7980A1006 (Analog 0-10V or 2-10V)
- Models with 3 outputs
- TB6980B1006 (1st output is floating)
- TB7980B1005 (1st output is analog 0-10V or 2-10V)
- 2nd output can be configured for
- Analog 0-10V
- Analog 2-10V
- 24V
- 3rd output is 24V only
- Features for all models
- Automatic changeover (duct sensor required)
- Manual changeover (remote switch or relay
required) - Night setback
- Min and Max temperature setpoint stops
3Applications and Accessories
- Hydronic and pressure dependent VAV with or
without reheat - Non-programmable
- Up to three outputs depending on model
- Can be used for
- Floating or Analog damper/valve actuator control
- Damper/valve actuator with duct reheat and aux
heat (B models) - Hydronic systems (room control, perimeter heating
and cooling) - Compatible accessories
- R841 family of electromechanical relays
- 50014156-002 remote room sensor
- 50014157-001 duct temperature sensor
- 32004800-001 bare thermistor
4Terminal Connections
5Typical Applications
Relay
24 VAC not COM
TB6980B
Damper control with electric reheat and
auxiliary hot-water heating
6Typical Applications
Relay
TB7980B
Relay
Damper control with electric reheat and auxiliary
baseboard heating
7Typical Applications
50014157-001
Relay
TB7980B
Damper control with automatic changeover,
electric reheat and central cooling
8Typical Applications
50014157-001
Relay
TB6980B
Temperature control of fresh air supply
9Typical Applications
TB7980B
TB7980B
TB7980B
Changeover and NSB inputs sharing the same 24-Vac
transformer
10Configuration TB7980B1005
Default configuration
11Configuration TB6980B1006
Default configuration
12Configuration menu TB6980B
Output 1 Activation
output 1 default mode
13Configuration menu TB6980B
Output 1 Modes
14Configuration menu TB6980B
Output 2 Activation
output 1 default mode
Output 1 jumps at 100 if there is an instant
5F difference
15Configuration menu TB6980B
Output 2 Modes
16Configuration menu TB6980B
Output 3 Activation
Output 1 jumps at 100 if there is an instant
5F difference
output 1 default mode
Output 2 jumps at 100 if there is an instant
11F difference
17Configuration menu TB6980B
Output 3 Modes
18Configuration menu TB6980B
Output 3 Activation Contact Mode
output 1 default mode
19Configuration and Operation
- Configuration
- Dip switches
- Temperature display, F or C (SW1)
- Access mode (SW2)
- Output 2 type (SW6)
- This sets output 2 type (analog or triac)
- Operation
- Backlight (on for 12 seconds)
- Temperature setting by 1 increments (2F in
changeover) - Output display (Hold Override for 4 seconds)
20Operation (continued)
- Operation
- Changeover
- Manual changeover (contact)
- Automatic changeover (9F differential between
duct and room) - Night setback
- Override (2 hours)
- Error codes
- E1 (internal sensor defective)
- E2 (internal sensor shorted)
- E3 (external temperature sensor defective or not
connected) - E4 (external temperature sensor shorted)
21System Components
22Literature and Point of Purchase Materials
All ZonePRO sales, technical and PowerPoint
materials can be downloaded at customer.honeywell.
com/buildings
23 www.honeywell.com