Startup Training - PowerPoint PPT Presentation

1 / 12
About This Presentation
Title:

Startup Training

Description:

Startup Training TPS3 15 – PowerPoint PPT presentation

Number of Views:70
Avg rating:3.0/5.0
Slides: 13
Provided by: Kennet173
Category:
Tags: startup | training

less

Transcript and Presenter's Notes

Title: Startup Training


1
Startup Training TPS3 15
2
Topics Covered
  • Visual Inspections
  • Verify environmental requirements are met
  • TPS3 15 Diagnostic Operation
  • Test Procedures
  • Fill out Inspection Sheet

3
Visual Inspections
  • Neutral and ground bond needs to be visually
    inspected.
  • If bond is loose, missing, or old, tighten,
    install, or replace bond. Poor neutral to ground
    bonds account for 99.9 of all surge protection
    failures.
  • Surge protection failure due to poor neutral to
    ground bond integrity will NOT be warranted!
  • Refer to page two of the installation manual.

Ground bond broken off
4
Verify Environmental Requirements
  • This surge protector is designed to operate
    indoors in an ambient temperature range of -40?C
    (-40?F) to 60?C (140?F) with a relative
    humidity of 0 to 95(non-condensing).
  • Verify installed environment meets this
    requirement.
  • Refer to page three of installation manual.
  • Refer to Red Warning Tag that is attached to
    disconnect

5
Startup
  • Before energizing. Surge protection must remain
    off until high-potential insulation testing is
    finished. Refer to page 1 of manual
  • Once all installation procedures are followed,
    surge protector can now be energized.
  • All Siemens TPS surge protectors are designed to
    be virtually maintenance free. Light indicators
    show protection status. The following slides show
    different light conditions and what they mean.

6
Normal Status
  • Normal 100 function suppressor will have three
    green lights. The service light will not
    illuminate nor will the audible alarm sound.

7
Testing Status
  • If the unit is in Normal Mode All green
    lights, pressing the Test button will cause
    the red service light to illuminate, the audible
    alarm to sound, and the dry contacts will change
    state. Also, the green lights remain illuminated
    during the test. Once the Test button is
    released, the service light stops illuminating,
    audible alarm will stop sounding, and the dry
    contacts will reset. The green phase lights stay
    illuminated.

8
Fault Condition
  • If a fault condition occurs, the audible alarm
    will sound, the Red Service LED will illuminate
    and the LED representing the affected phase/s
    will extinguish, indicating that the unit needs
    service. Contact a qualified electrician or
    technician for evaluation.

9
Silence Audible Alarm
  • If an inoperative condition were to occur, the
    built-in audible alarm will sound and the red
    Service LED will illuminate. This indicates that
    the unit needs evaluation by a qualified
    electrician or technician. Until a qualified
    person evaluates the unit, press Alarm Silence to
    silence the alarm. (The LED above Alarm Silence
    illuminates when the alarm is deactivated. Normal
    operation occurs with the Alarm Silence LED
    extinguished.) The red Service LED will remain
    illuminated even though the Audible Alarm has
    been silenced.

10
Abnormal N-G Voltage Indicators
  • This SPD include N-G voltage indicators. If the
    SPD detects excessive N-G voltage, the Red
    Service LED will blink and the Audible Alarm will
    cycle. This condition requires immediate
    attention as the SPD will fail.
  • Immediately TURN OFF the SPD, and contact
    electrician to inspect system grounding.

11
What Causes Abnormal N-G Voltage?
  • Incorrectly bonded distribution systems damage
    SPDs. If the XO or N-G bonding jumper is not
    installed, the electrical system has no reference
    to ground. It becomes an ungrounded system.
    Please see previous section regarding SPDs on
    ungrounded systems. Such systems are known to
    eventually produce abnormally high L-G voltages.
  • SPDs will attempt to chase this system-level
    overvoltage abnormality until the SPD fails. This
    effect is accelerated on Wye systems where SPDs
    are designed for grounded systems. (SPDs for
    ungrounded systems generally have higher MCOV to
    allow for L-G voltage fluctuations.) Failures of
    this nature are not defects in the SPDs
    workmanship or material. This is an installation
    error and is not covered by warranty.
  • A differential voltage circuit monitors neutral
    to ground voltage. When N-G voltage becomes
    excessive, an amplifier energizes a resistor.
    Eventually, that resistor will overheat and cause
    thermally sensitive shrink wrap to shrink around
    the resistor. This does not occur on transient or
    instantaneous N-G overvoltages. When the SPD is
    deenergized, the shrink wrap covered resistor can
    be accessed by qualified personnel under the
    display plate cover.

12
Return To Normal Status
  • Once damaged modules are replaced, the phase
    light or lights will return to their green state,
    and the service light will stop illuminating.
    Also, the audible alarm will stop sounding. If
    the audible alarm silence switch was depressed to
    turn off the alarm, the silence alarm light will
    remain on. You need to depress the silence switch
    again to activate the audible alarm and turn of
    the silence alarm light.
Write a Comment
User Comments (0)
About PowerShow.com