Title: Lesson 35 Per Phase Analysis
1Lesson 35Per Phase Analysis
2Learning Objectives
- Derive the relationship between line to line
voltages and line to neutral voltages in a
balanced Y-Y three phase circuit. - For a balanced Y-Y three phase circuit convert
the line to line voltage phasor to the line to
neutral voltage phasor and vice versa. - Plot the phasors of line to line voltages and
line to neutral voltages for a Y-Y three phase
circuit. - Derive the relationship between line current and
phase load current in a balanced Y- ? three phase
circuit. - For a balanced Y- ? three phase circuit convert
the line current phasor to phase load current
phasor and vice versa. - Plot the phasors of line current and phase load
current in a balanced Y- ? three phase circuit.
3Y-Y system
Review
Y Load
Generator
Lines
4PHASE/LINE VOLTAGES
Â
5Line/Phase Voltages for a Wye Circuit
- Using the following relationship
- we can also convert back
- Therefore, given any voltage at a point in a
balanced, 3-phase Y system, you can determine the
remaining 5 voltages by inspection.
6Law of Sines
- The ratio of the length of a side to the sine of
its corresponding opposite angle is constant - Applying the law of sines to the vector EAB
EAN
EBN
7Nominal voltages
- If phase voltage Van 120 V then line voltages
Vab 208 V. - This is referred to as 120/208-V system.
- Two other common nominal voltages are 220/380-V
and 347/600-V.
8Currents for a Wye Circuit
- For Y loads, line current and phase current are
the same.
Line current
Phase current
9Wye-Wye Single Phase Equivalent
Original circuit
Single-phase equivalent
10Example Problem 1
- EAB 208?0? V .
- Find the phase voltages and line currents.
11? load definitions
Review
Y-Y
Â
For ? loads, phase voltage and line voltage are
the same thing.
Line currents are the currents in the line
conductors. Phase currents are the currents
through phases .
12Line/Phase Currents for a Delta Circuit
Iab
Ica
Iab
Ibc
Line current
Phase current
13Line/Phase Currents for a Delta Circuit
- Relationship between line and phase currents
- For a balanced ? system, the magnitude of line
current is 1.732 times the magnitude of the phase
current and line current lags phase current by
30?. - Therefore, given any current at a point in a
balanced, 3-phase ? system, you can determine the
remaining 5 currents by inspection.
14Line/Phase Currents for a Delta Circuit
Phasor diagram
15Equivalent Ckt to solve Wye-Delta Problem
- This is just an equivalent circuit of the load
side! - What is missing from the equivalent circuit?
- Ia , Eab , Ean
- You can only use the equivalent circuit to solve
for load side voltages and currents - Vab, Iab
- Notice that this equivalent circuit uses LINE
VOLTAGE - 1 mistake with DELTA circuits is using the wrong
kind of voltage! -
16Example Problem 2
- Ia 41.6?6.9? A .
- Determine the phase currents in the load.
- Determine the supply line voltage EAB and the
supply phase voltage EAN.
17Line Impedances in 3 Phase AC
- Impedances in transmission lines complicate three
phase analysis - Voltage drop in the transmission line must be
accounted for EAN will not be the same as Van
VAa
18Wye-Wye Single Phase Equivalent
Original circuit
Single-phase equivalent
- Notice that the neutral line impedance drop is
ignored on the single phase equivalent. - No voltage drop occurs across this neutral line
since in reality, no current flows through it.
19Wye-Wye Single Phase Equivalent
Original circuit
VAa -
Single-phase equivalent
- Use KVL on the single phase equivalent to find
unknowns - EAN VAa Van 0
20Example Problem 3
- EAB 208?0? V. Determine
- a. Line Currents
- b. Load phase voltages
21Delta To Wye (??Y) Conversion
- A Delta circuit with line impedances cannot be
solved without first performing a ??Y conversion. - The Delta load can be converted to an equivalent
Wye load
22Equivalent Delta Ckt with LINE IMPEDANCES
23Example Problem 4
- EAB 208?0? V. Determine
- a. Find load phase voltage Vab
- b. Find the load phase current Iab .