Title: BALANCED FIRE PROTECTION:
1BALANCED FIRE PROTECTION ARE SMOKE/HEAT VENTS
NECESSARY FOR OCCUPANT AND FIREFIGHTER SAFETY IN
ONE-STORY INDUSTRIAL AND STORAGE BUILDINGS
PROTECTED BY STANDARD SPRAY SPRINKLERS?
- Presented to
-
- ICC Code Technology Committee
- Cincinnati, Ohio
- June 20, 2007
2CODE CHANGE F124-06/07FIRE CODE COMMITTEE
DISAPPROVAL REASON
- There was no definitive information presented
that smoke and heat vents do not contribute to
fire control. - In cases where the sprinkler system does not
suppress the fire but, rather, controls it, smoke
continues to be generated. -
- The discussions have focused on everything but
the safety of the occupants, including
firefighters.
3CODE CHANGE F124-06/07FIRE CODE COMMITTEE
DISAPPROVAL REASON
- Smoke and heat vents provide the fire
department with an important tool to remove the
smoke for occupant safety and enhanced fire
attack access, especially in very large area
buildings where access from the exterior is
limited at best. - Firefighter safety is also improved by
providing a faster, safer method of fire
ventilation than cutting one or more holes in the
roof. -
- The current text presents a balanced approach
between firefighter safety and building safety.
4ORIGINAL PURPOSE OF SMOKE/HEAT VENT PROVISIONS
- What was the original intended purpose for
requiring automatic smoke/heat vents and draft
curtains in one story industrial and storage
buildings (including buildings containing high-
piled storage) protected by a sprinkler system as
required by the UBC/UFC? - Assist with manual interior firefighting (in
both sprinkler control and sprinkler failure fire
scenarios). -
- Reduce property damage (building and contents).
5EXPECTED PERFORMANCE OF SMOKE/HEAT VENTS
- What was/is the expected performance of
automatic smoke/heat vent installations complying
with the UBC/UFC and IBC/IFC provisions for
smoke/heat vents and draft curtains? - Unknown. Neither the UBC/UFC or IBC/IFC contain
any performance criteria for smoke/heat vent
installations. (UBC/UFC IBC/IFC) -
- A fire in a bulk retail building in Tempe,
Arizona suggests the UBC/UFC roof vent/draft
curtain provisions are inadequate where the
sprinkler system is operational, but inadequate
for the hazard. (NFPA Fire Investigation)
6INTERACTION OF STANDARD SPRAY SPRINKLERS AND
DRAFT CURTAINS
- Do draft curtains interfere with the operation
of standard spray sprinklers? - Draft curtains may increase the number of
sprinklers which operate. FMRC Research 1994
NFPRF Research 1997/1998 -
- Draft curtains may cause a distortion in the
sprinklers which operate. NFPRF Research
1997/1998 -
- Draft curtains may interfere with pre-wetting
of combustibles. FMRC Research 1994 NFPRF
Research 1997/1998
7DELETION OF DRAFT CURTAIN PROVISIONS IN THE
IBC/IFC
- Was the expected performance of automatic
smoke/heat vent installations adversely affected
when the requirement for draft curtains was
removed from the UBC/UFC provisions for
smoke/heat vents during the drafting of the
IBC/IFC? - Smoke/heat vents and draft curtains are a team
the rate of venting through open vents is
dependent upon the temperature and the depth of
smoke layer. NFPA 204 -
- Not providing draft curtains (per the UBC/UFC)
will reduce both the temperature and depth of the
smoke layer. -
- There is a movement to use smoke vents without
draft curtains There is no RD basis for this
approach Dr. Craig Beyler, Hughes Associates,
Inc.
8OPERATION OF VENTS IN SPRINKLERED BUILDINGS
- How many smoke/heat vents will automatically
open in buildings protected by standard spray
sprinklers if the sprinkler system operates and
controls the fire (as expected by NFPA 13)? - . . . . .current design practices are likely to
limit the number of vents operated to one and
vents may in fact not operate at all in very
successful sprinkler operations. Dr. Craig
Beyler, Hughes Associates, Inc. -
- Not only is the fear of early operation not
founded, current design practice will likely lead
to 0-1 vents operating Dr. Craig Beyler,
Hughes Associates, Inc.
9PROTECTION OF BUILDING STRUCTUREBY STANDARD
SPRAY SPRINKLERS
- Will standard spray sprinklers protect the
building structure from damage without smoke/heat
vents (assuming that the sprinkler system is
operational and adequate for the hazard being
protected)? - The listing criteria for standard (spray)
sprinklers specifically tests the ability of
sprinklers to protect the building structure. UL
199 -
- Fires that occur in rack storage occupancies
are likely to be controlled within the limits
outlined in B-1.1, since no significant building
damage is expected. NFPA 13
10PERFORMANCE CAPABILITIES OF STANDARD SPRAY
SPRINKLERS
- Will standard spray sprinklers control and
extinguish a fire without intervention by
firefighters (assuming the sprinkler system is
operational and adequate for the hazard being
protected)? - Sprinkler protection installed as required in
this standard is expected to protect the building
occupancy without supplemental fire department
activity. NFPA 13
11PERFORMANCE CAPABILITIES OF STANDARD SPRAY
SPRINKLERS
- Will standard spray sprinklers reduce the
temperature within the building without
intervention by firefighters (assuming the
sprinkler system is operational and adequate for
the hazard)? - During the testing program, the installed
automatic extinguishing system was capable of
controlling the fire and reducing all
temperatures to ambient within 30 minutes of
ignition. NFPA 13
12IMPACT OF SPRINKLER OPERATION ON VENTING
- Will the operation of standard spray sprinklers
adversely impact the venting rate of smoke/heat
vents? -
- The operation of standard spray sprinklers
rapidly reduces ceiling temperatures. UL 199
NFPRF Research 1997/1998 -
- A reduction in the ceiling temperature caused by
the operation of sprinklers will reduce the
venting rate through open vents. NFPA 204
13ALTERNATIVES TO ROOF VENTS
- Is it essential for firefighting operations to
open smoke/heat vents (provided per the IBC/IFC
in buildings protected by standard spray
sprinklers) if the sprinkler system operates and
controls the fire or can the venting of smoke be
accomplished in some other manner (i.e. opening
large exterior doors)? - Sprinkler protection installed as required in
this standard is expected to protect the building
occupancy without supplemental fire department
activity. NFPA 13 -
- During the testing program, the installed
automatic extinguishing system was capable of
controlling the fire and reducing all
temperatures to ambient within 30 minutes of
ignition. NFPA 13
14ROOF VENT OPERATION IN THE EVENT OF SPRINKLER
SYSTEM FAILURE TO CONTROL FIRE
- Will automatic smoke/heat vents provided per the
IBC/IFC automatically open in buildings protected
by standard spray sprinklers if the sprinkler
system operates, but fails to control the fire? -
- Bulk Retail Facility Fire, Tempe, Arizona, March
19, 1998 -
- Sprinkler design based on a maximum of 29
sprinklers operating 66 sprinklers actually
operated. 29 smoke/heat vents provided in
building 3 smoke/heat vents actually operated. -
- Building filled with smoke from floor to ceiling
when Phoenix Fire Department arrived. - NFPA Fire Investigation Report
15MANUAL OPENING OF ROOF VENTS IN THE EVENT OF
SPRINKLER SYSTEM FAILURE TO CONTROL FIRE
- Should firefighters manually open smoke/heat
vents which do not open in buildings protected by
standard spray sprinklers if the sprinkler system
operates, but fails to control the fire? -
- Steel trusses are also prone to failure under
fire conditions and may fail in less time than a
wooden truss under the same conditions. -
- Lives will continue to be lost unless fire
departments make appropriate fundamental changes
in firefighting tactics involving trusses. - NIOSH recommends that fire departments, fire
fighters, building owners and managers take steps
to minimize the risk of injury and death to fire
fighters during fire fighting operations
involving structures with truss roof and floor
systems. - NIOSH 2005-132
16ROOF VENT OPERATION IN THE EVENT OF SPRINKLER
SYSTEM FAILURE TO DISCHARGE WATER
- Will automatic smoke/heat vents provided per the
IBC/IFC automatically open in buildings protected
by standard spray sprinklers if the sprinkler
system fails to operate (i.e. closed water supply
valve, broken supply piping or pump failure)? -
- Yes.
17FIREFIGHTER SAFETY
- From a firefighter safety standpoint, should
firefighters conduct interior manual firefighting
operations in the event the sprinkler system
operates, but fails to control the fire? - Steel trusses are also prone to failure under
fire conditions and may fail in less time than a
wooden truss under the same conditions -
- Fire fighters should be discouraged from
risking their lives solely for property
protection activities. -
- "Use defensive strategies whenever trusses have
been exposed to fire or whenever structural
integrity cannot be verified. Unless life-saving
operations are under way, evacuate fire fighters
and use an exterior attack Brannigan 1999 Dunn
2001. - NIOSH 2005-132
18FIREFIGHTER SAFETY
- From a firefighter safety standpoint, should
firefighters conduct interior manual firefighting
operations in the event the sprinkler system
fails to operate (i.e. closed water supply valve,
broken supply piping or pump failure)? - Steel trusses are also prone to failure under
fire conditions and may fail in less time than a
wooden truss under the same conditions -
- Fire fighters should be discouraged from
risking their lives solely for property
protection activities. -
- "Use defensive strategies whenever trusses have
been exposed to fire or whenever structural
integrity cannot be verified. Unless life-saving
operations are under way, evacuate fire fighters
and use an exterior attack Brannigan 1999 Dunn
2001. - NIOSH 2005-132
19VOLUNTEER FIRE DEPARTMENT PERSONNEL CAPABILITIES
- Do most volunteer fire departments have
sufficient personnel capabilities to conduct
interior manual firefighting operations in large
industrial or storage buildings in the event the
sprinkler system operates, but fails to control
the fire, or when the system fails to operate? - In communities with less than 2,500 population,
21 of fire departments, nearly all of them
all-or mostly-volunteer departments, deliver an
average of 4 or fewer volunteer firefighters to a
mid-day house fire. . . it is likely that most of
these departments often fail to deliver the
minimum of 4 firefighters recognized by national
standards as the necessary minimum for interior
fire attack -
- An estimated 128,000 firefighters, most of them
volunteers serving in communities with less than
2,500 population, serve in departments that are
involved in structural firefighting but have not
certified any firefighters to Firefighter Level I
or II. - USFA- 303, October 2006
20PAID FIRE DEPARTMENT PERSONNEL CAPABILITIES
- Do most career (paid) fire departments have
sufficient personnel capabilities to conduct
interior manual firefighting operations in large
industrial or storage buildings with the first
arriving engine company in the event the
sprinkler system operates, but fails to control
the fire, or when the system fails to operate? -
- Sufficient resources required to provide safe
manual fire suppression activities are not
currently available in most municipalities
defended by full time firefighting personnel.
IRC Code Change RB4-06/07 -
- An estimated 79,000 firefighters serve in fire
departments that protect communities of at least
50,000 population and have fewer than 4 career
firefighters assigned to first-due engine
companies. It is likely that, for many of these
departments, the first arriving complement of
firefighters often falls short of the minimum of
4 firefighters needed to initiate an interior
attack on a structure fire, thereby requiring the
first-arriving firefighters to wait until the
rest of the first-alarm responders arrive.
USFA-303, October 2006
21OCCUPANT FIRE SAFETY RISK-INDUSTRIAL AND STORAGE
BUILDINGS
- Are large single-story industrial or storage
buildings protected by a sprinkler system
(standard spray sprinklers) without roof vents a
high risk occupancy from an occupant fire safety
standpoint? - The NFPA estimates that 50 fire fatalities
occurred in U.S. commercial (non-residential)
occupancies in 2005. NFPA fire statistics-2005 -
- Commercial occupancies include assembly,
business, educational, institutional and
mercantile occupancies, as well as industrial and
storage buildings.
22FIRE INSURANCE CARRIER REQUIREMENTS FOR ROOF
VENTS IN SPRINKLERED BUILDINGS
- Do any fire insurers mandate the installation of
smoke/heat vents in buildings protected by a
sprinkler system? - No.
- Reduces Heat and Smoke Damage? Unknown Dr.
Craig Beyler, Hughes Associates, Inc.
23FIRE INSURANCE PREMIUM CREDITS FOR ROOF VENTS IN
SPRINKLERED BUILDINGS
- Do any fire insurers offer premium reductions
for the installation of smoke/heat vents in
industrial or storage buildings protected by a
sprinkler system? - No.
-
- Reduces Heat and Smoke Damage? Unknown Dr.
Craig Beyler, Hughes Associates, Inc.
24RESEARCH ON PROPERTY PROTECTION CAPABILITIES OF
ROOF VENTS IN SPRINKLERED BUILDINGS
- Is there any research that indicates that
smoke/heat vents actually reduce property damage
in buildings protected by a sprinkler system when
the sprinkler system operates or when the
sprinkler protection is impaired? - Reduces Heat and Smoke Damage? Unknown Dr.
Craig Beyler, Hughes Associates, Inc.
25CODE CHANGE F124-06/07FIRE CODE COMMITTEE
DISAPPROVAL REASON
- There was no definitive information presented
that smoke and heat vents do not contribute to
fire control. NFPRF Research-1997/1998 Bulk
Retail Facility Fire, Tempe, Arizona-1998 - In cases where the sprinkler system does not
suppress the fire but, rather, controls it, smoke
continues to be generated. NFPRF
Research-1997/1998 Bulk Retail Facility Fire,
Tempe, Arizona-1998 NFPA 204 -
- The discussions have focused on everything but
the safety of the occupants, including
firefighters. NFPA Fire Statistics-2005 NIOSH
2005-132
26CODE CHANGE F124-06/07FIRE CODE COMMITTEE
DISAPPROVAL REASON
- Smoke and heat vents provide the fire
department with an important tool to remove the
smoke for occupant safety and enhanced fire
attack access, especially in very large area
buildings where access from the exterior is
limited at best. NIOSH 2005-132 USFA-303
(2006) - Firefighter safety is also improved by
providing a faster, safer method of fire
ventilation than cutting one or more holes in the
roof. NIOSH 2005-132 USFA-303 (2006) -
- The current text presents a balanced approach
between firefighter safety and building safety.
NFPA 13 NIOSH 2005-132
27CONCLUSIONS
- Sprinkler protection is the primary means of
protecting large one-story industrial and storage
buildings. - Draft curtains may have an adverse impact on the
ability of standard sprinklers to control a fire.
(NFPRF Research-1997/1998 FMRC Research-1994) -
- No building feature which has been shown to
potentially interfere with the successful
operation of the sprinkler system should be
required by the IBC/IFC (i.e. draft curtains).
28CONCLUSIONS(CONTINUED)
- The use of roof vents without draft curtains
will adversely affect the venting capability of
smoke/heat vents which open. (NFPA 204 Dr.
Craig Beyler) - The activation of standard sprinklers will
adversely affect the venting capability of any
smoke/heat vents which open. (NFPA 204) -
- The NFPRF research clearly demonstrated that the
maximum number of smoke/heat vents which will
automatically open in a building protected by
standard (spray) sprinklers (if the sprinkler
system is operational and adequate for the hazard
protected) is one. (NFPRF Research-1997/1998
Dr. Craig Beyler)
29CONCLUSIONS(CONTINUED)
- If the sprinkler protection is adequate for the
hazard protected and is functional, the use of
interior manual firefighting in large single
industrial and storage story buildings is
unnecessary. (NFPA 13) -
- If the sprinkler protection is operational, but
inadequate for the hazard protected, or is not
functional, interior manual firefighting should
not be utilized. (NIOSH 2005-132)
30CONCLUSIONS(CONTINUED)
- The occupant fire safety risk presented by large
one-story industrial or storage occupancies
protected by a sprinkler system is minimal.
(NFPA Fire Statistics-2005) -
- Providing automatic smoke/heat vents in large
one-story industrial or storage occupancies
protected by a sprinkler system will provide
little or no additional occupant fire safety
since the occupant fire safety risk is already
minimal and since it has been demonstrated that
smoke/heat vents may not operate in buildings
protected by standard (spray) sprinklers. (NFPA
Fire Statistics-2005 NFPRF Research 1997/1998)
31CONCLUSIONS(CONTINUED)
- From the above, it can be concluded that
automatic smoke/heat vents provide no significant
increase in the level of fire protection and fire
safety, including firefighter safety, provided
for large single-story buildings containing
industrial or storage occupancies protected by
standard (spray) sprinklers.
32RECOMMENDED CODE CHANGE PROPOSAL ACTION
- A code change proposal which eliminates the
mandatory requirements for smoke/heat vents in
single-story industrial and storage buildings
protected by standard spray sprinklers should be
developed. - The code change proposal should include
mandatory requirements for some means of
ventilating the building. Several design
alternatives for providing venting (including
manual smoke/heat vents) should be included in
this proposal. -
- The purpose of providing some means of
ventilating the building should be to assist
firefighters in removing smoke from the building
after the fire has been controlled and
extinguished by the sprinkler system.
33