Title: Radiation Shielding Information and Guidance
1Radiation Shielding Information and Guidance
- Don Parry, CHP
- District Health Physicist
- Michigan Department of Consumer Industry
Services - Radiation Safety Section
- dparry_at_michigan.gov
2Regulations and Standards Regarding Plan Reviews
- Michigans first rules on ionizing radiation were
published in February of 1958 Radiation
shielding requirements were listed in an appendix
based on NBS Handbook 76 - Ionizing Radiation Rules were modified in 1965
and more clearly indicated that Shielding shall
be approved by the Michigan Department of Health - Rule 331(2) of the current Ionizing Radiation
Rules (Promulgated in 1975) states that shielding
is subject to design approval by the department - Plan reviews have been done routinely by the
State Radiation Control Program since 1958
3Radiation Shielding Information
- Form BHS/HFS 852 Information Required for a
Radiation Shielding Plan Review - Available on Web site at
- www.michigan.gov/bhs (click on Mammography and
X-ray Machines Radiation Shielding Guidance) - Web Site includes guidance on shielding
- Radiographic or RF rooms
- Mammography Rooms
- Computed Tomography Rooms
- Linear Accelerator Vaults
- Additional Guidance
4Radiation Shielding Information
- Form BHS/HFS 852 Information Required for a
Radiation Shielding Plan Review - Be sure to include all requested information
including - Plans or blueprints of rooms and adjacent areas
to scale with compass directions. (1/4 1 foot
preferred) - Location of x-ray equipment, x-ray table,wall
bucky, exposure switch, viewing window and
control panel - Description of occupancy of adjoining areas
including above or below - Description of floor and ceiling construction
including minimum concrete thickness and density.
5Radiation Shielding Information
- Form BHS/HFS 852 (Continued)
- Be sure to include all requested information
including - Location,type, thickness and height of proposed
shielding - Indicate thickness and density of concrete and
masonry materials - Limits of travel of table, tube and image
receptor - Maximum kVp, mA and estimated workload in
mAmin/wk - For CT scanners, include a copy of the
iso-exposure curves normally provided by the
manufacturer - Name and address of facility
- Name and address to send response letter
6Radiation Shielding Information
- Plan Reviews
- Plans should be submitted prior to construction!
- Construction of an x-ray room without an approved
plan may cause shielding modifications to be done
after the room is constructed
7Radiation Shielding Information
- Certificate of Need
- Equipment that requires a CON will not be
registered until plans have been reviewed by the
Radiation Safety Section.
8Radiation Shielding Information
- Shielding Guidance
- Most medical x-ray rooms should normally be
provided with 1/8 inch thick lead for primary
barriers (including floors) and 1/16 inch thick
lead for secondary barriers (including doors) - Vertical barriers must extend from the floor to a
minimum height of 7 feet. - If it is necessary to add additional shielding to
the ceiling of the room, then the shielding in
the walls must be extended above the 7-foot
height to overlap the ceiling shielding.
9Radiation Shielding Information
- Shielding Guidance
- If there are multi story buildings in close
proximity of the x-ray room, which have occupied
spaces that could be exposed to scatter radiation
that is not attenuated by the 7-foot high wall
shielding, additional shielding may be necessary
to protect those areas - Outside walls and, particularly, windows may
require shielding to protect distant areas even
if the nearest occupied area is not immediately
adjacent
10Radiation Shielding Information
- Examples
- No Occupancy above or below
- On Slab
- Shielding should be floor to 7
- 1/16 inch thick secondary, 1/8 inch thick primary
1/8 inch lead (blue)
Leakage
Scatter
1/16 inch lead (red)
11Radiation Shielding Information
- Examples
- CT with adjacent Multi Story Building
- May need additional shielding on outside wall
Occupied uncontrolled space in adjacent building
Adjacent Multi Story Building
12Radiation Shielding Information
- Floors
- Need to use minimum thickness of concrete floor
in shielding calculations - Need to know density of concrete (147 lbs/ft3
standard)
13Radiation Shielding Information
- Examples
- Occupied space below
- Need 1/16 inch thick lead on floor with 1/8 thick
lead under table - Floor shielding should overlap wall shielding
14Radiation Shielding Information
- Examples
- Exposure switch location
Switch needs to be arms length from first
scattered and leakage radiation
Switch Location
Adjacent Multi Story Building
15Radiation Shielding Information
- Summary
- Submit shielding plans to the Radiation Safety
Section for design approval prior to
construction! - Include all information requested on form BHS/HFS
852. - Equipment that requires a Certificate of Need
will not be registered until a plan is reviewed - Most rooms will be adequately shielded with 1/8
inch thick lead for primary barriers and 1/16
inch thick lead for secondary barriers. - Be sure to consider areas above and below the
x-ray room when designing shielding.
16Contact Information
- HeadquartersRadiation Safety SectionMichigan
Department of Consumer Industry ServicesP.O.
Box 30664Lansing, Michigan 48909 Phone (517)
241-1989Fax (517) 241-1981 - Visitor/delivery address5th Floor, G. Mennen
Williams Building525 W. Ottawa StreetLansing,
Michigan 48933 - District OfficeOur district office, formerly in
Pontiac, has moved to Radiation Safety
SectionMichigan Department of Consumer
Industry Services38600 Van Dyke, Suite
375Sterling Heights, Michigan 48312 - Phone (586) 446-0200Fax (586) 446-0227