2. Circuit Breakers and Recloser - PowerPoint PPT Presentation

1 / 71
About This Presentation
Title:

2. Circuit Breakers and Recloser

Description:

2. Circuit Breakers and Recloser * Dr.Latif Shaikh Fuses Fuse is a device used in circuit for protecting electrical equipments against overloads and /or short circuits. – PowerPoint PPT presentation

Number of Views:414
Avg rating:3.0/5.0
Slides: 72
Provided by: Lat54
Category:

less

Transcript and Presenter's Notes

Title: 2. Circuit Breakers and Recloser


1
2. Circuit Breakers and Recloser
2
Course Outline
  • Introduction
  • Circuit Breaker
  • The Arc
  • Isolators
  • Air Circuit Breakers
  • Air Blast Circuit Breakers
  • Vacuum Circuit Breakers
  • Oil Circuit Breakers
  • Sulfur Hexafluoride Circuit Breakers
  • Circuit Breaker Ratings
  • Circuit Breaker Controls
  • High Voltage Circuit Breakers Comparison
  • Reclosures
  • Sectionalizers
  • Fuses
  • Fuse application

3
Circuit Breaker
  • A circuit breaker is a piece of equipment which
    can Make or break a circuit either manually or
    by remote control under normal conditions.
  • Break a circuit automatically under fault
    condition
  • Make a circuit either manually or by remote under
    fault condition

4
Operating Principle
  • Circuit Breaker consists of fixed and moving
    contacts called electrodes
  • Under normal operating condition these contacts
    remain closed and will not open automatically
    unless the system becomes faulty .These contacts
    can be opened manually or by remote control.
  • When a fault occurs in a circuit the trip coils
    of the circuit breaker get energized and the
    moving contacts are pulled apart by some
    mechanism ,thus opening the circuit.

5
Simplified Diagram of Circuit Breaker Control
6
Electric Arc
7
Electric Arc
  • When contacts of circuit breaker starts
    separating the contact resistance starts
    increasing. This increases the (I square r) loss
    which is heat produced .
  • This heat increases the energy of electrons in
    the contact areas and the ionized particles tries
    to maintain the current when contacts are
    separated.This flow of charged particles form one
    contact to other is called an arc .
  • The medium surrounding the arc also contains ions
    .
  • Due to this charged particles the arc continues
    even if the breakers contacts are separated.
  • The voltage (potential gradient) across the arc
    is less and so it continues even for low voltages.

8
ARC in AC and DC circuits
  • DC arcs are to be interrupted by increasing the
    resistance interruption method in which
    resistance of the arc is increased so that the
    arc voltage can no longer maintain the current
    and the arc is extinguished.
  • Size of DC circuit breaker increases as the
    voltage level increases.
  • AC arcs current reduces to zero in each cycle (2
    times)
  • If the circuit breaker contacts are opened at
    time when the current passed through zero and
    dielectric strength of the medium is build up
    rapidly so that arc cannot strike again then arc
    can be extinguished successfully.
  • Size of AC circuit breaker can be small compared
    to same voltage DC circuit breaker.

9
Principles of Arc extinction
  • Separate the contacts of circuit breaker such
    that the arc resistance increases to a very high
    value. The pd between the contacts is unable to
    maintain the arc current. For high voltage
    circuit breakers this method is impracticable
    since a separation of many meters will be
    required.(High Resistance Method)
  • The ionized particles between the contacts tend
    to maintain the arc. If the arc path is deionized
    ,the arc extinction is facilitated .This may be
    achieved by cooling the arc or by bodily removing
    the ionized particles from the space between the
    contacts.(Low Resistance Method)

10
Important terms
  • Arc Voltage It is the voltage that appears
    across the contacts of the circuit breakers
    during the arcing period as the contacts are
    opened.
  • Recovery voltage It is the normal frequency
    voltage that appears across the contacts of
    circuit breaker after final arc extinction.
  • Rate of rise of restriking voltage (RRRV) It is
    the rate of increase of restriking voltage .RRRV
    depends upon 1) recovery voltage and 2) Natural
    frequency of oscillation

11
Restriking Voltage
  • It is the transient voltage that appears across
    the contacts at or near current zero during
    arcing period.
  • If dielectric strength rise is greater than the
    rise of restriking voltage then the arc will not
    restrike.

12
Current Chopping
  • It is the phenomena of current interruption
    before natural current zero is reached. It occurs
    in air blast circuit breaker because they retain
    same extinguishing power irrespective of the
    magnitude of current to be interrupted.
  • When interrupting low inductive current
    e.g.magnetising current of transformer, a rapid
    deionizing effect causes current , to fall below
    its zero value before natural current zero is
    called current chopping.

13
Current Chopping
14
Resistance Switching
15
Resistance Switching
  • The switching Resistor (R) is connected in
    parallel with the CB contacts. Current chopping
    produces high voltage oscillations which can be
    prevented by this method.
  • During arc interruption CB contacts separate
    first and after arc gets extinguished S opens
    depending upon the time delay provided to it.
  • When the fault occurs the CB contacts open and
    arc is struck between them. Since R is in
    parallel with Cb contacts ,a part of arc current
    flows through this resistance so arc current
    decreases and deionization rate increases. The
    arc resistance also increases so current through
    R increases. This continue till the arc current
    is insufficient to maintain the arc.

16
Circuit Breaker Rating
  • Breaking capacity It is the current (r.m.s.)
    that a Circuit Breaker is capable of breaking at
    given recovery voltage and under specified
    conditions.
  • Making Capacity The peak value of current
    (including DC component) during the first cycle
    of current wave after closure of circuit breaker
    is known as making capacity. Making capacity
    2.55 symmetrical breaking capacity
  • Short time rating It is the period for which
    the CB is able to carry fault current while
    remaining closed.
  • Normal current rating It is the r.m.s. value of
    current which the CB is capable of carrying
    continuously at its rated frequency under rated
    specified conditions.

17
IEEE Standards for Selection of Circuit Breakers
  • Step 1.Calculate highest value of initial RMS
    current considering symmetrical fault. The
    current can be obtained by sub -transient
    reactance of synchronous generators and transient
    reactance of synchronous motors and induction
    motors are neglected.
  • Following Multiplying factors are applied to take
    into account dc components and decrement of dc
    components in current. If short circuit KVA
    exceeds 5000,000 ,then add 0.1 to the given
    factors

8 cycles or slow breaker 1.0
5 cycle breaker 1.1
3 cycle breaker 1.2
2 cycle breaker 1.4
18
IEEE Standards for Selection of Circuit Breakers

19
1) CB rated 1500A,1000MVA,33kV,3sec,3phase oil
CB.Find a)rated normal current b) breaking
capacity c)rated symmetrical current d)Rated
making current e) short time rating f)rated
service voltage
20
Problem -A generator connected through a 5 cycle
circuit breaker to a transformer is rated
8000KVAand 13.8kV with the reactance of
Xd10,Xd16,and Xd100 .It is operating at
no load and rated voltage when 3 phase short
circuit occurs between breaker and transformer.
Find1.Sustained short circuit current in the
breaker2.The initial symmetrical rms current in
the breaker3.Maximum possible dc component in
the breaker4.Current to be interrupted by the
breaker5.The interrupting KVA
  •  

21
  •  

22
Requirements of Circuit Breaker
23
Classification of Circuit Breakers
24
(No Transcript)
25
Air Circuit Breakers
  • 1.In this Circuit Breaker the arc is elongated
    using arc runners and arc splitters so as to
    increase the resistance of the arc.
  • 3.This increases the voltage required to maintain
    the arc and if the available voltage cannot
    sustain the arc ,the arc gets extinguished.
  • 2.At current zero ,the recovery voltage across
    the contacts becomes less than the arc voltage
    and the arc gets extinguished.
  • 4. The energy in the system inductance at current
    zero is zero .Hence arc interruption is easier.

26
(No Transcript)
27
Air Circuit Breakers
  • 1.Used For low voltage levels and current levels
  • 2.As voltage level increases, the size of breaker
    becomes large so not convenient for higher
    voltage and current levels.
  • 3.Air is used as medium to extinguish the arc
    which have inferior extinguishing properties
    compared to SF6 or Vacuum circuit breakers
  • 4.Operating control is manual as well as
    automatic.
  • 5.It is used up to 6.6kV with a breaking
    capacity of 15MVA.
  • 6.Suitable for repeated operation because medium
    of arc extinction is air . So commonly used in
    Industrial Switchgears . Auxiliary switchgear
    Generating Stations

28
Air Blast Circuit Breakers
  • In this breaker, a high pressure air blast is
    used as an arc quenching medium.
  • The contacts are opened and a flow of air blast
    is maintained by opening the blast valve.
  • The air blast cools the arc and takes away the
    arcing products to atmosphere .
  • This rapidly increases the dielectric strength of
    the medium between the contacts and the arc is
    extinguished and the flow of current is
    interrupted.

29
(No Transcript)
30
Air Blast Circuit Breaker(Radial Flow)
31
Advantages and Disadvantages
  • Advantages
  • Disadvantages
  • High speed of operation
  • Short arcing time
  • High speed reclosing
  • Less weigh as compared to oil circuit breakers
  • Very less maintenance
  • No possibility of explosion
  • Cost is more
  • For complete compress air installation is
    required
  • These breakers are more sensitive to RRRV.
  • For operation and maintenance ,highly skilled
    persons are required

32
Air Blast Circuit Breakers (Axial Flow)
33
Axial Blast ABCB
  • Air is admitted in the arc extinction chamber it
    pushes the moving contact. This air blast takes
    away the ionized gases along with it. Afterwards
    the arc gets extinguished. High pressure air has
    higher dielectric strength.
  • The design is such that the air expands into the
    low pressure (atmospheric pressure zone).The air
    at high speed removes heat from the arc, thus arc
    is quenched. Diameter of arc is reduced.
  • Uses
  • 1.Arc Furnaces
  • 2.Traction Syetems

34
Modification of Air Blast Circuit Breakers
35
Advantages of Air Blast Circuit Breaker
36
Disadvantages of Air Blast Circuit Breakers
37
Applications of Air Blast Circuit Breakers
38
Vacuum Circuit Breakers
  • When two contacts of this circuit breaker are
    separated in vacuum an arc is struck and hot
    spots are formed on the surface of the contacts
    .These hot spots produce metal vapor and plasma
    .the amount of vapor in plasma depends on how
    rapidly the vapor is emitted from contact surface
    which depends on the arc current. The current is
    of alternating nature, it pass through zero
    several times, so the rate of vapor emission also
    becomes zero , and the vapor already emitted gets
    condensed . During this process the dielectric
    strength builds up rapidly and the restriking of
    arc is prevented.

39
Vacuum Circuit Breaker
40
Vacuum Circuit Breakers
  • It consists of fixed contact, moving contact and
    arc shield mounted inside a vacuum chamber. The
    movable member is connected to the control
    mechanism by stainless steel bellows. This
    enables the permanent sealing of the vacuum
    chamber so as to eliminate the possibility of
    leakage,.
  • A glass vessel or ceramic vessel is used as outer
    insulating body. The arc shield prevents the
    deterioration of the internal dielectric strength
    by preventing the deterioration of the internal
    dielectric strength.
  • Applications
  • Outdoor application where maintenance required is
    minimum.In the high voltage system from 22 KV to
    66kV power Circuits.

41
Working of Vacuum Circuit Breaker
  • When two contacts of circuit breaker are
    separated in vacuum arc is struck and hot spots
    are formed on the surface of the contacts. These
    hot spots produce metal vapour and plasma.
  • At current zero the rate of vapour emission
    becomes zero.
  • The vapour already emitted gets condensed .
  • During this process the dielectric strength
    builds up and the restriking of arc is prevented.

42
Vacuum Circuit Breakers
  • Advantages
  • Disadvantages
  • Compact in size
  • Reliable and long life
  • Heavy fault can be interrupted effectively
  • No gas is generated after arc extinction
    operation
  • Operation is not noisy
  • Arc energy is low
  • No risk of fire
  • Vacuum has to be maintained at desired level
    always

43
Oil Circuit Breakers
44
Oil Circuit Breakers
  • This breaker makes use of oil for quenching the
    arc.
  • The circuit breaker which uses more oil or which
    is bulky is called bulk oil circuit breaker.
  • The construction is simple and it consists of
    fixed and moving contacts enclosed in a strong
    weather tight earthed tank containing oil up to
    a certain level and an air cushion above the oil
    level.
  • Application
  • These breakers are used up to 11 KV with an
    interrupting capacity of 250MVA.

45
Oil Circuit Breaker (Working)
  • Under normal working conditions, the fixed and
    moving contacts are closed. On the occurrence of
    fault, the moving contacts come down and an arc
    is struck between the contacts. The oil between
    the contacts gets decomposed and hydrogen gas
    bubble is formed around the contacts. The
    hydrogen gas cools the arc and rthe turbulence
    effect cause the lengthening of arc. The
    deionization of medium between contacts takes
    place and at some critical length of gap between
    the contacts ,the arc is extinguished.
  • The hydrogen gas bubble produces a very high
    pressure in the oil. The tank is therefore made
    strong to withstand a large pressure. The oil
    moves upwards when hydrogen bubble is formed. The
    air is present between the oil level and tank top
    and acts as cushion and absorbs mechanical shock
    produced due to upward oil movement.

46
Bulk Oil Circuit Breaker
  • Advantages
  • Disadvantages
  • oil has high dielectric strength
  • Oil absorbs arc energy while decomposing
  • Good cooling property of the gas formed due to
    decomposition
  • It acts as an insulator between the live parts
    and earth
  • Long arcing time
  • Do not permit high speed of interruption
  • Arc interruption control can be obtained only by
    increasing the length of arc

47
Low Oil circuit Breakers
  • Operation
  • When the contacts are separated in oil arc is
    formed. The heat of arc decomposes oil and gases
    are formed. These gases expand due to heating of
    the arc. The gas flowing near the contact zone
    cause cooling and splitting of the arc and the
    arc gets extinguished.

48
Minimum Oil Circuit Breakers
  • In this breaker, the supporting ,current
    interruption and top chamber are made of
    porcelain .Hence, clearance between live parts is
    small and requires less quantity of oil, hence
    the breaker is called Minimum Oil Circuit
    Breaker. The chambers are completely filled with
    oil. The oil from upper chamber does not come to
    lower.
  • The fixed contact is enclosed in the quenching
    chamber. Moving contact makes sliding contact
    with the lower fixed contact. The operating rod
    is operated by operating mechanism, the three
    poles operate simultaneously.
  • The voltage ratings are from 3.6kV to 420 KV.
  • Applications Minimum oil circuit breakers are
    available in for all voltages and highest
    breaking capacity hence they are preferred in
    almost all protection schemes

49
Maintenance of Oil Circuit Breakers
50
Minimum Oil Circuit Breaker
  • Advantages
  • Disadvantages
  • Requires less quantity of oil
  • Requires smaller space
  • Maintenance is less
  • Cost per breaking capacity in MVA is less
  • Suitable for both manual and automatic operation
  • Possibility of fire and explosion.
  • Difficult to remove gases from the space between
    contacts.
  • Oil deteriorates rapidly due to carbonization
  • Smaller quantity of oil, so carbonization
    increases.

51
SF6 circuit Breaker (Properties of SF6
gas)
  • Electronegative It has the ability of an atom to
    attract and hold electrons. Such gas have high
    dielectric stremngth.SF6 is electronegative .It
    forms negative ions ,Negative ions are heavy and
    immobile so they do not flow easily .Hence SF6
    gas has high dielectric strength.
  • Rate of rise of dielectric strength is very high.
  • Can be liquefied and stored in steel tanks
  • Dielectric strength increase linearly with
    pressure.
  • Gas is inert. Therefore contacts will not get
    eroded.
  • Gas is non inflammable , Colorless ,odorless,
    Non-toxic
  • Thermally stable up to 55 degrees

52
Sulfur Hexafluoride Circuit Breaker
53
Operation of SF6 Circuit Breaker
  • Under normal operating conditions the contacts
    are closed .
  • On occurance of fault contacts are opened. The
    movable contact moves away from the fixed
    contact.
  • The arc is struck between the fixed and moving
    contacts.
  • High pressure SF6 gas now flows over the arc and
    it absorbs the free electrons from the arc.
  • This builds up the dielectric strength between
    the gap very fast and the arc is extinguished

54
Advantages and Disadvantages of SF6 Breaker
  • Advantages
  • Silent operation, compact size
  • Vary short arcing time
  • No risk of fire
  • No reduction in dielectric strength due to
    operation
  • No current chopping problem
  • Can interrupt larger currents
  • Suitable for explosive environment due to
    totally enclosed body
  • Disadvantages
  • Costly
  • Requires conditioning of SF6 gas from time to
    time
  • SF6 gas is suffocating ,so its leakage can cause
    suffocation of the persons in surrounding areas.
  • Special facilities are required for transporting
    gas
  • Additional equipments are required for
    reconditioning

55
Isolators
56
Isolators
  • Isolator(disconnecting switch) operates under no
    load condition. It does not have any current
    breaking capacity or current making capacity.
    Isolator is not even used for breaking load
    currents.
  • Isolators are used in addition to circuit
    breakers ,and are provided on each side of every
    circuit breaker to provide isolation and enable
    maintenance.
  • Sequence of operation
  • While opening Open circuit breaker first and
    then isolators
  • While closing Close isolators first and then
    close circuit breakers

57
Circuit Breaker Controls
  • Different types of controls are required for
    successful operation of circuit breakers.
  • 1.Relays These are required to give a trip
    signal to circuit breaker in case of fault
    condition. Different types of relays are
    available like over current, over voltage ,under
    voltage, loss of excitation, reverse power etc.
  • 2.Sensor equipments are required to check the
    condition of circuit breakers arc extinguishing
    medium .
  • The controls are pressure sensors to sense the
    pressure of air in case of air blast circuit
    breakers .
  • In case of Sulfur hexafluoride circuit breakers
    also the pressure sensors are required.
  • In case of vacuum circuit breakers also sensors
    are required to check the vacuum level in the
    breaker.

58
Automatic Reclosing
  • Many faults (80-90) in the overhead distribution
    system like flash over of insulators, crow
    faults, temporary tree contacts , etc are
    temporary in nature. Thus, taking a feeder or
    line permanent outage may lead to unnecessary
    long loss of service to customers. Hence, many
    utilities use fast automatic reclosers for an
    overhead radial feeder without synchronous
    machines or with minimum induction motor load.
    Presence of synchronous machines will require
    additional problem of synchro-check to be
    addressed. The almost universal practice is to
    use three and occasionally four attempts to
    restore service before lock out .

59
  • Subsequently, energization is by manual
    intervention. The initial reclosure can be high
    speed (0.2 - 0.5sec) or delayed for 3 - 5
    seconds. This allows for de-ionization time for
    fault arc. If the temporary fault is cleared,
    then the service is restored. Otherwise, the
    relay again trips the feeder. Then one or two
    additional time delayed reclosures are programmed
    on the reclosing relay. Typical schedule might be
    instantaneous, followed by 30sec, or 35sec,
    followed by 15sec. If the circuit still continues
    to trip, the fault is declared as permanent and
    the recloser is locked out. Reclosers use three
    phase and single phase oil or vacuum circuit
    breakers for overhead distribution lines.
  • With underground network, faults tend to be more
    often permanent and reclosers are not
    recommended. In case of large synchronous motors,
    distributed generators or induction motor loads,
    it is recommended that sufficient time is allowed
    for underfrequency relays to trip these sources
    of back emf out-of-the-circuit.

60
Reclosures
  • Application of reclosers in distribution systems
    requires selection of its ratings such as minimum
    trip current, continuous current, symmetrical
    interrupting current etc.
  • For a single phase system, single phase
    reclosers can be used whereas for a three phase
    system, one three phase recloser or three single
    phase reclosers can be used. Reclosers have to be
    selected by considering the following factors.
  • Voltage Rating.
  • Continuous current Rating This is the maximum
    load current the recloser has to carry.
  • Maximum Symmetrical Interrupting Rating The
    maximum symmetrical fault current should not
    exceed this rating.
  • Minimum Tripping current This is the minimum
    fault current that a recloser will clear. It is
    equal to two times the continuous current
    rating. Usually tolerance is 10. This decides
    the sensitivity of the recloser

61
Example on Reclosure Selection
  • Consider a three phase distribution system with a
    single phase tap as shown in fig . Maximum load
    on this single phase tap is 40A and that on three
    phase line is 200A. Fault currents at F1,F2, F3
    and F4 are also shown in the fig. Table shows
    the available standard rating of single phase and
    three phase reclosers. Select the ratings of
    reclosers at B.

62
IEEE Standard Table for Reclosure Selection
63
Answer
  • Recloser at B
  • Maximum load current on this single phase line
    40A.
  • Continuous current rating of this recloser must
    be 1.25 - 1.5 times the maximum load current to
    account for anticipated load growth.
  • i.e. Continuous current rating of this recloser
    at B 40 1.5 60A.
  • From the table 1, any recloser with continuous
    current rating of 100A and above is acceptable.
  • Maximum fault current at B 1750A.
  • Interrupting current rating must be greater than
    1750A. From the table 1, we see that recloser
    with 100A continous current rating has 2000A
    symmetrical rms short circuit current rating.
    Hence, we can choose this recloser.
  • Minimum tripping current Continuous current
    rating 2 10 tolerance
  • 100 2 10 of 200 220A
  • Since the minimum trip current 220A is less than
    the minimum fault current 250A at the line end,
    it can protect the entire line.
  • Voltage rating of the line is 11kV. So we can
    select the maximum voltage rating of 15.5kV (from
    the table).

64
Sectionalizers
65
Sectionalizers
  • Sectionalizers are used in the bus bars so that
    fault on any section of bus bar will not cause
    complete shut down.
  • Advantages of sectionalizers
  • 1.If fault occurs on any section of bus bars then
    that section is isolated from other sections
    without affecting the system.
  • 2.Fault current is much lower than in case of un
    sectionalized system (as the fault is fed from
    only one section)
  • 3.Repairing and maintenance on one section can be
    carried out by de energizing that section only
    eliminating the possibility of complete shut
    down.
  • The breaker in the bus bars is acting as
    sectionalizing breaker in the shown figure.

66
Fuses
  • Fuse is a device used in circuit for protecting
    electrical equipments against overloads and /or
    short circuits.
  • Fuse element or fuse wire is that part of the
    fuse device which melts when an excessive current
    flows in the circuit and thus isolates the faulty
    device from the supply circuit.
  • Desirable qualities of fuse elements
  • 1.Low melting point
  • 2.Low ohmic losses
  • 3.High conductivity
  • 4.Free from deterioration due to oxidation
  • 5.Low cost

67
Thermal Characteristic of Fuse
  • As the magnitude of the current increases,
    melting time reduces. It should be obvious that
    larger magnitude currents will lead to higher
    power dissipation (I2R) in the fuse and hence
    faster rise in temperature of the element. This
    would imply that melting time of the fuse should
    be inversely proportional to magnitude of square
    of current. The relationship between the
    magnitude of the current that causes melting and
    the time needed for it to melt is given by the
    fuse's melting time current characteristics
    (TCC). To cover a wide range of currents and
    operating time, TCC is plotted on a log-log
    paper.

68
  • Current Voltage Time relationship of Non Current
    Limiting Fuse (Expulsion Fuse)
  • Current Voltage Time relationship of Current
    Limiting Fuse

69
Expulsion Fuse
  • The expulsion type fuse is used where expulsion
    gases cause no problem such as in overhead
    circuits and equipment. These fuses can be termed
    as current awaiting types and the function of
    interrupting medium is similar to that of an ac
    circuit breaker. The temperature of arc is of the
    order of 4000-5000K. At this temperature special
    materials located in close proximity to fuse
    element rapidly create gases. Preferred gas
    generating materials are fiber, melamine, boric
    acid and liquids such as oil or carbon
    tetrachloride. These gases help to create a high
    pressure turbulent medium surrounding the arc,
    thus when the current does reach to zero and the
    arc channel reduces to a minimum the ablated
    gases rapidly mix with remaining ionized gas and
    thereby deionize them as well as remove them from
    arc area'. In turn, this leads to rapid build up
    of dielectric strength that can withstand the
    transient recovery voltage (TRV) and steady state
    power system voltage.

70
Vacuum Fuses
  • Vacuum fuse is a non expulsive fuse but still a
    current zero awaiting type. The design, operation
    and current-voltage-time relationship of this
    fuse closely matches with that of an expulsion
    fuse. The main difference is that it is a
    completely sealed unit and no expulsion action.
    Interruption occurs because of rapid dielectric
    build up that occur in a vacuum after current
    zero is reached

71
Current Limiting Fuse
  • Basically, the current limiting fuses attempt to
    constrict the arc and it is cooled by sand. A
    typical current limiting fuse is shown in fig .
    In this case, the fusible element is very long.
    The element is completely surrounded with filler
    material, typically silica sand, to contain the
    arc as well as maintain a very high pressure in
    the long restricted arc area caused by the
    practically simultaneous melting of the full
    length of element. This then allows the fuse to
    produce a very high resistance in the circuit in
    a very short period of time (typically hundreds
    of µsec).
Write a Comment
User Comments (0)
About PowerShow.com