Title: 2. Circuit Breakers and Recloser
12. Circuit Breakers and Recloser
2Course Outline
- Introduction
- Circuit Breaker
- The Arc
- Isolators
- Air Circuit Breakers
- Air Blast Circuit Breakers
- Vacuum Circuit Breakers
- Oil Circuit Breakers
- Sulfur Hexafluoride Circuit Breakers
- Circuit Breaker Ratings
- Circuit Breaker Controls
- High Voltage Circuit Breakers Comparison
- Reclosures
- Sectionalizers
- Fuses
- Fuse application
3Circuit Breaker
- A circuit breaker is a piece of equipment which
can Make or break a circuit either manually or
by remote control under normal conditions. - Break a circuit automatically under fault
condition - Make a circuit either manually or by remote under
fault condition
4Operating Principle
- Circuit Breaker consists of fixed and moving
contacts called electrodes - Under normal operating condition these contacts
remain closed and will not open automatically
unless the system becomes faulty .These contacts
can be opened manually or by remote control. - When a fault occurs in a circuit the trip coils
of the circuit breaker get energized and the
moving contacts are pulled apart by some
mechanism ,thus opening the circuit.
5Simplified Diagram of Circuit Breaker Control
6Electric Arc
7Electric Arc
- When contacts of circuit breaker starts
separating the contact resistance starts
increasing. This increases the (I square r) loss
which is heat produced . - This heat increases the energy of electrons in
the contact areas and the ionized particles tries
to maintain the current when contacts are
separated.This flow of charged particles form one
contact to other is called an arc . - The medium surrounding the arc also contains ions
. - Due to this charged particles the arc continues
even if the breakers contacts are separated. - The voltage (potential gradient) across the arc
is less and so it continues even for low voltages.
8ARC in AC and DC circuits
- DC arcs are to be interrupted by increasing the
resistance interruption method in which
resistance of the arc is increased so that the
arc voltage can no longer maintain the current
and the arc is extinguished. - Size of DC circuit breaker increases as the
voltage level increases. - AC arcs current reduces to zero in each cycle (2
times) - If the circuit breaker contacts are opened at
time when the current passed through zero and
dielectric strength of the medium is build up
rapidly so that arc cannot strike again then arc
can be extinguished successfully. - Size of AC circuit breaker can be small compared
to same voltage DC circuit breaker.
9Principles of Arc extinction
- Separate the contacts of circuit breaker such
that the arc resistance increases to a very high
value. The pd between the contacts is unable to
maintain the arc current. For high voltage
circuit breakers this method is impracticable
since a separation of many meters will be
required.(High Resistance Method) - The ionized particles between the contacts tend
to maintain the arc. If the arc path is deionized
,the arc extinction is facilitated .This may be
achieved by cooling the arc or by bodily removing
the ionized particles from the space between the
contacts.(Low Resistance Method)
10Important terms
- Arc Voltage It is the voltage that appears
across the contacts of the circuit breakers
during the arcing period as the contacts are
opened. - Recovery voltage It is the normal frequency
voltage that appears across the contacts of
circuit breaker after final arc extinction. - Rate of rise of restriking voltage (RRRV) It is
the rate of increase of restriking voltage .RRRV
depends upon 1) recovery voltage and 2) Natural
frequency of oscillation
11Restriking Voltage
- It is the transient voltage that appears across
the contacts at or near current zero during
arcing period. - If dielectric strength rise is greater than the
rise of restriking voltage then the arc will not
restrike.
12Current Chopping
- It is the phenomena of current interruption
before natural current zero is reached. It occurs
in air blast circuit breaker because they retain
same extinguishing power irrespective of the
magnitude of current to be interrupted. - When interrupting low inductive current
e.g.magnetising current of transformer, a rapid
deionizing effect causes current , to fall below
its zero value before natural current zero is
called current chopping.
13Current Chopping
14Resistance Switching
15Resistance Switching
- The switching Resistor (R) is connected in
parallel with the CB contacts. Current chopping
produces high voltage oscillations which can be
prevented by this method. - During arc interruption CB contacts separate
first and after arc gets extinguished S opens
depending upon the time delay provided to it. - When the fault occurs the CB contacts open and
arc is struck between them. Since R is in
parallel with Cb contacts ,a part of arc current
flows through this resistance so arc current
decreases and deionization rate increases. The
arc resistance also increases so current through
R increases. This continue till the arc current
is insufficient to maintain the arc.
16Circuit Breaker Rating
- Breaking capacity It is the current (r.m.s.)
that a Circuit Breaker is capable of breaking at
given recovery voltage and under specified
conditions. - Making Capacity The peak value of current
(including DC component) during the first cycle
of current wave after closure of circuit breaker
is known as making capacity. Making capacity
2.55 symmetrical breaking capacity - Short time rating It is the period for which
the CB is able to carry fault current while
remaining closed. - Normal current rating It is the r.m.s. value of
current which the CB is capable of carrying
continuously at its rated frequency under rated
specified conditions.
17IEEE Standards for Selection of Circuit Breakers
- Step 1.Calculate highest value of initial RMS
current considering symmetrical fault. The
current can be obtained by sub -transient
reactance of synchronous generators and transient
reactance of synchronous motors and induction
motors are neglected. - Following Multiplying factors are applied to take
into account dc components and decrement of dc
components in current. If short circuit KVA
exceeds 5000,000 ,then add 0.1 to the given
factors
8 cycles or slow breaker 1.0
5 cycle breaker 1.1
3 cycle breaker 1.2
2 cycle breaker 1.4
18IEEE Standards for Selection of Circuit Breakers
191) CB rated 1500A,1000MVA,33kV,3sec,3phase oil
CB.Find a)rated normal current b) breaking
capacity c)rated symmetrical current d)Rated
making current e) short time rating f)rated
service voltage
20Problem -A generator connected through a 5 cycle
circuit breaker to a transformer is rated
8000KVAand 13.8kV with the reactance of
Xd10,Xd16,and Xd100 .It is operating at
no load and rated voltage when 3 phase short
circuit occurs between breaker and transformer.
Find1.Sustained short circuit current in the
breaker2.The initial symmetrical rms current in
the breaker3.Maximum possible dc component in
the breaker4.Current to be interrupted by the
breaker5.The interrupting KVA
21 22Requirements of Circuit Breaker
23Classification of Circuit Breakers
24(No Transcript)
25Air Circuit Breakers
- 1.In this Circuit Breaker the arc is elongated
using arc runners and arc splitters so as to
increase the resistance of the arc. - 3.This increases the voltage required to maintain
the arc and if the available voltage cannot
sustain the arc ,the arc gets extinguished. - 2.At current zero ,the recovery voltage across
the contacts becomes less than the arc voltage
and the arc gets extinguished. - 4. The energy in the system inductance at current
zero is zero .Hence arc interruption is easier.
26(No Transcript)
27Air Circuit Breakers
- 1.Used For low voltage levels and current levels
- 2.As voltage level increases, the size of breaker
becomes large so not convenient for higher
voltage and current levels. - 3.Air is used as medium to extinguish the arc
which have inferior extinguishing properties
compared to SF6 or Vacuum circuit breakers - 4.Operating control is manual as well as
automatic. - 5.It is used up to 6.6kV with a breaking
capacity of 15MVA. - 6.Suitable for repeated operation because medium
of arc extinction is air . So commonly used in
Industrial Switchgears . Auxiliary switchgear
Generating Stations
28Air Blast Circuit Breakers
- In this breaker, a high pressure air blast is
used as an arc quenching medium. - The contacts are opened and a flow of air blast
is maintained by opening the blast valve. - The air blast cools the arc and takes away the
arcing products to atmosphere . - This rapidly increases the dielectric strength of
the medium between the contacts and the arc is
extinguished and the flow of current is
interrupted.
29(No Transcript)
30Air Blast Circuit Breaker(Radial Flow)
31Advantages and Disadvantages
- High speed of operation
- Short arcing time
- High speed reclosing
- Less weigh as compared to oil circuit breakers
- Very less maintenance
- No possibility of explosion
- Cost is more
- For complete compress air installation is
required - These breakers are more sensitive to RRRV.
- For operation and maintenance ,highly skilled
persons are required
32Air Blast Circuit Breakers (Axial Flow)
33Axial Blast ABCB
- Air is admitted in the arc extinction chamber it
pushes the moving contact. This air blast takes
away the ionized gases along with it. Afterwards
the arc gets extinguished. High pressure air has
higher dielectric strength. - The design is such that the air expands into the
low pressure (atmospheric pressure zone).The air
at high speed removes heat from the arc, thus arc
is quenched. Diameter of arc is reduced. - Uses
- 1.Arc Furnaces
- 2.Traction Syetems
34Modification of Air Blast Circuit Breakers
35Advantages of Air Blast Circuit Breaker
36Disadvantages of Air Blast Circuit Breakers
37Applications of Air Blast Circuit Breakers
38Vacuum Circuit Breakers
- When two contacts of this circuit breaker are
separated in vacuum an arc is struck and hot
spots are formed on the surface of the contacts
.These hot spots produce metal vapor and plasma
.the amount of vapor in plasma depends on how
rapidly the vapor is emitted from contact surface
which depends on the arc current. The current is
of alternating nature, it pass through zero
several times, so the rate of vapor emission also
becomes zero , and the vapor already emitted gets
condensed . During this process the dielectric
strength builds up rapidly and the restriking of
arc is prevented.
39Vacuum Circuit Breaker
40Vacuum Circuit Breakers
- It consists of fixed contact, moving contact and
arc shield mounted inside a vacuum chamber. The
movable member is connected to the control
mechanism by stainless steel bellows. This
enables the permanent sealing of the vacuum
chamber so as to eliminate the possibility of
leakage,. - A glass vessel or ceramic vessel is used as outer
insulating body. The arc shield prevents the
deterioration of the internal dielectric strength
by preventing the deterioration of the internal
dielectric strength. - Applications
- Outdoor application where maintenance required is
minimum.In the high voltage system from 22 KV to
66kV power Circuits.
41Working of Vacuum Circuit Breaker
- When two contacts of circuit breaker are
separated in vacuum arc is struck and hot spots
are formed on the surface of the contacts. These
hot spots produce metal vapour and plasma. - At current zero the rate of vapour emission
becomes zero. - The vapour already emitted gets condensed .
- During this process the dielectric strength
builds up and the restriking of arc is prevented.
42Vacuum Circuit Breakers
- Compact in size
- Reliable and long life
- Heavy fault can be interrupted effectively
- No gas is generated after arc extinction
operation - Operation is not noisy
- Arc energy is low
- No risk of fire
- Vacuum has to be maintained at desired level
always
43Oil Circuit Breakers
44Oil Circuit Breakers
- This breaker makes use of oil for quenching the
arc. - The circuit breaker which uses more oil or which
is bulky is called bulk oil circuit breaker. - The construction is simple and it consists of
fixed and moving contacts enclosed in a strong
weather tight earthed tank containing oil up to
a certain level and an air cushion above the oil
level. - Application
- These breakers are used up to 11 KV with an
interrupting capacity of 250MVA.
45Oil Circuit Breaker (Working)
- Under normal working conditions, the fixed and
moving contacts are closed. On the occurrence of
fault, the moving contacts come down and an arc
is struck between the contacts. The oil between
the contacts gets decomposed and hydrogen gas
bubble is formed around the contacts. The
hydrogen gas cools the arc and rthe turbulence
effect cause the lengthening of arc. The
deionization of medium between contacts takes
place and at some critical length of gap between
the contacts ,the arc is extinguished. - The hydrogen gas bubble produces a very high
pressure in the oil. The tank is therefore made
strong to withstand a large pressure. The oil
moves upwards when hydrogen bubble is formed. The
air is present between the oil level and tank top
and acts as cushion and absorbs mechanical shock
produced due to upward oil movement.
46Bulk Oil Circuit Breaker
- oil has high dielectric strength
- Oil absorbs arc energy while decomposing
- Good cooling property of the gas formed due to
decomposition - It acts as an insulator between the live parts
and earth
- Long arcing time
- Do not permit high speed of interruption
- Arc interruption control can be obtained only by
increasing the length of arc
47Low Oil circuit Breakers
- Operation
- When the contacts are separated in oil arc is
formed. The heat of arc decomposes oil and gases
are formed. These gases expand due to heating of
the arc. The gas flowing near the contact zone
cause cooling and splitting of the arc and the
arc gets extinguished.
48Minimum Oil Circuit Breakers
- In this breaker, the supporting ,current
interruption and top chamber are made of
porcelain .Hence, clearance between live parts is
small and requires less quantity of oil, hence
the breaker is called Minimum Oil Circuit
Breaker. The chambers are completely filled with
oil. The oil from upper chamber does not come to
lower. - The fixed contact is enclosed in the quenching
chamber. Moving contact makes sliding contact
with the lower fixed contact. The operating rod
is operated by operating mechanism, the three
poles operate simultaneously. - The voltage ratings are from 3.6kV to 420 KV.
- Applications Minimum oil circuit breakers are
available in for all voltages and highest
breaking capacity hence they are preferred in
almost all protection schemes
49Maintenance of Oil Circuit Breakers
50Minimum Oil Circuit Breaker
- Requires less quantity of oil
- Requires smaller space
- Maintenance is less
- Cost per breaking capacity in MVA is less
- Suitable for both manual and automatic operation
- Possibility of fire and explosion.
- Difficult to remove gases from the space between
contacts. - Oil deteriorates rapidly due to carbonization
- Smaller quantity of oil, so carbonization
increases.
51 SF6 circuit Breaker (Properties of SF6
gas)
- Electronegative It has the ability of an atom to
attract and hold electrons. Such gas have high
dielectric stremngth.SF6 is electronegative .It
forms negative ions ,Negative ions are heavy and
immobile so they do not flow easily .Hence SF6
gas has high dielectric strength. - Rate of rise of dielectric strength is very high.
- Can be liquefied and stored in steel tanks
- Dielectric strength increase linearly with
pressure. - Gas is inert. Therefore contacts will not get
eroded. - Gas is non inflammable , Colorless ,odorless,
Non-toxic - Thermally stable up to 55 degrees
52Sulfur Hexafluoride Circuit Breaker
53Operation of SF6 Circuit Breaker
- Under normal operating conditions the contacts
are closed . - On occurance of fault contacts are opened. The
movable contact moves away from the fixed
contact. - The arc is struck between the fixed and moving
contacts. - High pressure SF6 gas now flows over the arc and
it absorbs the free electrons from the arc. - This builds up the dielectric strength between
the gap very fast and the arc is extinguished
54Advantages and Disadvantages of SF6 Breaker
- Advantages
- Silent operation, compact size
- Vary short arcing time
- No risk of fire
- No reduction in dielectric strength due to
operation - No current chopping problem
- Can interrupt larger currents
- Suitable for explosive environment due to
totally enclosed body
- Disadvantages
- Costly
- Requires conditioning of SF6 gas from time to
time - SF6 gas is suffocating ,so its leakage can cause
suffocation of the persons in surrounding areas. - Special facilities are required for transporting
gas - Additional equipments are required for
reconditioning
55Isolators
56Isolators
- Isolator(disconnecting switch) operates under no
load condition. It does not have any current
breaking capacity or current making capacity.
Isolator is not even used for breaking load
currents. - Isolators are used in addition to circuit
breakers ,and are provided on each side of every
circuit breaker to provide isolation and enable
maintenance. - Sequence of operation
- While opening Open circuit breaker first and
then isolators - While closing Close isolators first and then
close circuit breakers
57Circuit Breaker Controls
- Different types of controls are required for
successful operation of circuit breakers. - 1.Relays These are required to give a trip
signal to circuit breaker in case of fault
condition. Different types of relays are
available like over current, over voltage ,under
voltage, loss of excitation, reverse power etc. - 2.Sensor equipments are required to check the
condition of circuit breakers arc extinguishing
medium . - The controls are pressure sensors to sense the
pressure of air in case of air blast circuit
breakers . - In case of Sulfur hexafluoride circuit breakers
also the pressure sensors are required. - In case of vacuum circuit breakers also sensors
are required to check the vacuum level in the
breaker.
58Automatic Reclosing
- Many faults (80-90) in the overhead distribution
system like flash over of insulators, crow
faults, temporary tree contacts , etc are
temporary in nature. Thus, taking a feeder or
line permanent outage may lead to unnecessary
long loss of service to customers. Hence, many
utilities use fast automatic reclosers for an
overhead radial feeder without synchronous
machines or with minimum induction motor load.
Presence of synchronous machines will require
additional problem of synchro-check to be
addressed. The almost universal practice is to
use three and occasionally four attempts to
restore service before lock out . -
59- Subsequently, energization is by manual
intervention. The initial reclosure can be high
speed (0.2 - 0.5sec) or delayed for 3 - 5
seconds. This allows for de-ionization time for
fault arc. If the temporary fault is cleared,
then the service is restored. Otherwise, the
relay again trips the feeder. Then one or two
additional time delayed reclosures are programmed
on the reclosing relay. Typical schedule might be
instantaneous, followed by 30sec, or 35sec,
followed by 15sec. If the circuit still continues
to trip, the fault is declared as permanent and
the recloser is locked out. Reclosers use three
phase and single phase oil or vacuum circuit
breakers for overhead distribution lines. - With underground network, faults tend to be more
often permanent and reclosers are not
recommended. In case of large synchronous motors,
distributed generators or induction motor loads,
it is recommended that sufficient time is allowed
for underfrequency relays to trip these sources
of back emf out-of-the-circuit. -
60Reclosures
- Application of reclosers in distribution systems
requires selection of its ratings such as minimum
trip current, continuous current, symmetrical
interrupting current etc. - For a single phase system, single phase
reclosers can be used whereas for a three phase
system, one three phase recloser or three single
phase reclosers can be used. Reclosers have to be
selected by considering the following factors. - Voltage Rating.
- Continuous current Rating This is the maximum
load current the recloser has to carry. - Maximum Symmetrical Interrupting Rating The
maximum symmetrical fault current should not
exceed this rating. - Minimum Tripping current This is the minimum
fault current that a recloser will clear. It is
equal to two times the continuous current
rating. Usually tolerance is 10. This decides
the sensitivity of the recloser
61Example on Reclosure Selection
- Consider a three phase distribution system with a
single phase tap as shown in fig . Maximum load
on this single phase tap is 40A and that on three
phase line is 200A. Fault currents at F1,F2, F3
and F4 are also shown in the fig. Table shows
the available standard rating of single phase and
three phase reclosers. Select the ratings of
reclosers at B.
62IEEE Standard Table for Reclosure Selection
63Answer
- Recloser at B
- Maximum load current on this single phase line
40A. - Continuous current rating of this recloser must
be 1.25 - 1.5 times the maximum load current to
account for anticipated load growth. - i.e. Continuous current rating of this recloser
at B 40 1.5 60A. - From the table 1, any recloser with continuous
current rating of 100A and above is acceptable. - Maximum fault current at B 1750A.
- Interrupting current rating must be greater than
1750A. From the table 1, we see that recloser
with 100A continous current rating has 2000A
symmetrical rms short circuit current rating.
Hence, we can choose this recloser. - Minimum tripping current Continuous current
rating 2 10 tolerance - 100 2 10 of 200 220A
- Since the minimum trip current 220A is less than
the minimum fault current 250A at the line end,
it can protect the entire line. - Voltage rating of the line is 11kV. So we can
select the maximum voltage rating of 15.5kV (from
the table). -
64Sectionalizers
65Sectionalizers
- Sectionalizers are used in the bus bars so that
fault on any section of bus bar will not cause
complete shut down. - Advantages of sectionalizers
- 1.If fault occurs on any section of bus bars then
that section is isolated from other sections
without affecting the system. - 2.Fault current is much lower than in case of un
sectionalized system (as the fault is fed from
only one section) - 3.Repairing and maintenance on one section can be
carried out by de energizing that section only
eliminating the possibility of complete shut
down. - The breaker in the bus bars is acting as
sectionalizing breaker in the shown figure.
66Fuses
- Fuse is a device used in circuit for protecting
electrical equipments against overloads and /or
short circuits. - Fuse element or fuse wire is that part of the
fuse device which melts when an excessive current
flows in the circuit and thus isolates the faulty
device from the supply circuit. - Desirable qualities of fuse elements
- 1.Low melting point
- 2.Low ohmic losses
- 3.High conductivity
- 4.Free from deterioration due to oxidation
- 5.Low cost
67Thermal Characteristic of Fuse
- As the magnitude of the current increases,
melting time reduces. It should be obvious that
larger magnitude currents will lead to higher
power dissipation (I2R) in the fuse and hence
faster rise in temperature of the element. This
would imply that melting time of the fuse should
be inversely proportional to magnitude of square
of current. The relationship between the
magnitude of the current that causes melting and
the time needed for it to melt is given by the
fuse's melting time current characteristics
(TCC). To cover a wide range of currents and
operating time, TCC is plotted on a log-log
paper.
68- Current Voltage Time relationship of Non Current
Limiting Fuse (Expulsion Fuse)
- Current Voltage Time relationship of Current
Limiting Fuse
69Expulsion Fuse
- The expulsion type fuse is used where expulsion
gases cause no problem such as in overhead
circuits and equipment. These fuses can be termed
as current awaiting types and the function of
interrupting medium is similar to that of an ac
circuit breaker. The temperature of arc is of the
order of 4000-5000K. At this temperature special
materials located in close proximity to fuse
element rapidly create gases. Preferred gas
generating materials are fiber, melamine, boric
acid and liquids such as oil or carbon
tetrachloride. These gases help to create a high
pressure turbulent medium surrounding the arc,
thus when the current does reach to zero and the
arc channel reduces to a minimum the ablated
gases rapidly mix with remaining ionized gas and
thereby deionize them as well as remove them from
arc area'. In turn, this leads to rapid build up
of dielectric strength that can withstand the
transient recovery voltage (TRV) and steady state
power system voltage.
70Vacuum Fuses
- Vacuum fuse is a non expulsive fuse but still a
current zero awaiting type. The design, operation
and current-voltage-time relationship of this
fuse closely matches with that of an expulsion
fuse. The main difference is that it is a
completely sealed unit and no expulsion action.
Interruption occurs because of rapid dielectric
build up that occur in a vacuum after current
zero is reached
71Current Limiting Fuse
- Basically, the current limiting fuses attempt to
constrict the arc and it is cooled by sand. A
typical current limiting fuse is shown in fig .
In this case, the fusible element is very long.
The element is completely surrounded with filler
material, typically silica sand, to contain the
arc as well as maintain a very high pressure in
the long restricted arc area caused by the
practically simultaneous melting of the full
length of element. This then allows the fuse to
produce a very high resistance in the circuit in
a very short period of time (typically hundreds
of µsec).