Title: Symmetrical Components, Unbalanced Fault Analysis
1ECE 476POWER SYSTEM ANALYSIS
- Lecture 21
- Symmetrical Components, Unbalanced Fault Analysis
- Professor Tom Overbye
- Department of Electrical andComputer Engineering
2Announcements
- Be reading Chapters 9 and 10
- HW 8 is due now.
- HW 9 is 8.4, 8.12, 9.1,9.2 (bus 2), 9.14 due Nov
10 in class - Start working on Design Project. Tentatively due
Nov 17 in class - Second exam is on Nov 15 in class. Same format
as first exam, except you can bring two note
sheets (e.g., the one from the first exam and
another)
3Single Line-to-Ground (SLG) Faults
- Unbalanced faults unbalance the network, but only
at the fault location. This causes a coupling of
the sequence networks. How the sequence networks
are coupled depends upon the fault type. Well
derive these relationships for several common
faults. - With a SLG fault only one phase has non-zero
fault current -- well assume it is phase A.
4SLG Faults, contd
5SLG Faults, contd
6SLG Faults, contd
With the sequence networks in series we
can solve for the fault currents (assume Zf0)
7Example 9.3
8Line-to-Line (LL) Faults
- The second most common fault is line-to-line,
which occurs when two of the conductors come in
contact with each other. With out loss of
generality we'll assume phases b and c.
9LL Faults, cont'd
10LL Faults, con'td
11LL Faults, cont'd
12LL Faults, cont'd
13LL Faults, cont'd
14Double Line-to-Ground Faults
- With a double line-to-ground (DLG) fault two line
conductors come in contact both with each other
and ground. We'll assume these are phases b and
c.
15DLG Faults, cont'd
16DLG Faults, cont'd
17DLG Faults, cont'd
18DLG Faults, cont'd
- The three sequence networks are joined as follows
Assuming Zf0, then
19DLG Faults, cont'd
20Unbalanced Fault Summary
- SLG Sequence networks are connected in series,
parallel to three times the fault impedance - LL Positive and negative sequence networks are
connected in parallel zero sequence network is
not included since there is no path to ground - DLG Positive, negative and zero sequence
networks are connected in parallel, with the zero
sequence network including three times the fault
impedance
21Generalized System Solution
- Assume we know the pre-fault voltages
- The general procedure is then
- Calculate Zbus for each sequence
- For a fault at bus i, the Zii values are the
thevenin equivalent impedances the pre-fault
voltage is the positive sequence thevenin voltage - Connect and solve the thevenin equivalent
sequence networks to determine the fault current - Sequence voltages throughout the system are
22Generalized System Solution, contd
- Sequence voltages throughout the system are given
by
This is solved for each sequence network!
5. Phase values are determined from the
sequence values
23Unbalanced System Example
For the generators assume Z Z? j0.2 Z0
j0.05 For the transformers assume Z Z? Z0
j0.05 For the lines assume Z Z? j0.1 Z0
j0.3 Assume unloaded pre-fault, with voltages
1.0 p.u.
24Positive/Negative Sequence Network
Negative sequence is identical to positive
sequence
25Zero Sequence Network
26For a SLG Fault at Bus 3
The sequence networks are created using the
pre-fault voltage for the positive sequence
thevenin voltage, and the Zbus diagonals for the
thevenin impedances
Positive Seq. Negative Seq.
Zero Seq.
The fault type then determines how the networks
are interconnected
27Bus 3 SLG Fault, contd
28Bus 3 SLG Fault, contd
29Faults on Lines
- The previous analysis has assumed that the fault
is at a bus. Most faults occur on transmission
lines, not at the buses - For analysis these faults are treated by
including a dummy bus at the fault location. How
the impedance of the transmission line is then
split depends upon the fault location
30Line Fault Example
Assume a SLG fault occurs on the previous system
on the line from bus 1 to bus 3, one third of
the way from bus 1 to bus 3. To solve the system
we add a dummy bus, bus 4, at the fault location
31Line Fault Example, contd
The Ybus now has 4 buses
32Power System Protection
- Main idea is to remove faults as quickly as
possible while leaving as much of the system
intact as possible - Fault sequence of events
- Fault occurs somewhere on the system, changing
the system currents and voltages - Current transformers (CTs) and potential
transformers (PTs) sensors detect the change in
currents/voltages - Relays use sensor input to determine whether a
fault has occurred - If fault occurs relays open circuit breakers to
isolate fault
33Power System Protection
- Protection systems must be designed with both
primary protection and backup protection in case
primary protection devices fail - In designing power system protection systems
there are two main types of systems that need to
be considered - Radial there is a single source of power, so
power always flows in a single direction this is
the easiest from a protection point of view - Network power can flow in either direction
protection is much more involved
34Radial Power System Protection
- Radial systems are primarily used in the lower
voltage distribution systems. Protection actions
usually result in loss of customer load, but the
outages are usually quite local.
The figure shows potential protection schemes for
a radial system. The bottom scheme is preferred
since it results in less lost load
35Radial Power System Protection
- In radial power systems the amount of fault
current is limited by the fault distance from the
power source faults further done the feeder have
less fault current since the current is limited
by feeder impedance - Radial power system protection systems usually
use inverse-time overcurrent relays. - Coordination of relay current settings is needed
toopen the correct breakers
36Inverse Time Overcurrent Relays
- Inverse time overcurrent relays respond
instan-taneously to a current above their maximum
setting - They respond slower to currents below this value
but above the pickup current value