Title: Lecture Objectives:
1Lecture Objectives
- Analysis of Absorption Cooling Cycles
2Carnot Cycles
- COPvapor_compressionQcooling/Pelectric
COPmaxTcooling/(Tenviromnet-Tcooling)
- COPabsorptionQcooling/Qheating COPmax
Tcooling/(Tenviromnet-Tcooling)
(Theat_source-T environment)/ Theat_source -
COPmax_absorption COP vapor compression x
Correction for VC cycle
3Absorption cooling with preheater(system
improvement 1)
Rich ammonia vapor
4
5
Refrigeration and air conditioning (Ramesh et al)
4Absorption cooling with preheater
Saturated vapor at p1
1V3
Major heat source
6
1
mixing
isotherm
6h
1
Useful cooling energy
1L 2
4
5
1
Saturated liquid at p1
2 , 2
Saturated liquid at p1
1
Cooling tower
Pumping energy
COP Q cooling / Q heating (Pump ???)
5For Real energy analysis you need real h-x
diagram!
hfg for H2O
hfg for NH3
6Use of precooling(system improvement 2)
7Absorption cooling with precooling
Saturated vapor at p1
1V3
Major heat source
6
6
1
6h
mixing
Saturated liquid at p1
isotherm
1
Useful cooling energy (larger!)
1L 2
4
1
Saturated liquid at p1
2 , 2
4
5
1
Cooling tower (needs to cool more!)
Pumping energy
8System improvement 3
Generator with of Enrichment NH3
Different
8V
8L
9
10
8LLP
11
9Heat rejection with separation into liquid and
vapor (Enrichment NH3 in the vapor mixture)
This is our point
cooling
1
42V
Separator
65V
Q12 /m1
cooling
Q45 /m4
x8
m8
8
7
m1
m2
5
2
mixture
sub cooled liquid
isotherm
m3
2L
Q12
x8
x1
10Ammonia Enrichment Process(rectification)
11Absorption system with Enrichment (no preheater
nor precooler)
Saturated vapor at p2
3V
8V
mixing
3
11
8L
1
Useful cooling energy
8LLP
10
2
3L
9
Saturated liquid at p2
Saturated liquid at p1
1
12Example of H2O-NH3 System
- Text Book (Thermal Environmental Engineering)
Example 5.5 - HW 1
- Solve the problem 5.6 from the textbook
(LiBr-H2O) - Beside example 5.6, you will need to study
example 5.6 and 5.7 - Due date February 25th.
13LiBr-H2O Systems
14LiBr-H2O Systems
15Twine vessel LiBr-H2O Systems
16Useful information about LiBr absorption chiller
- http//www.cibse.org/content/documents/Groups/CHP/
Datasheet20720-20Absorption20Cooling.pdf - Practical Tips for Implementation of absorption
chillers - Identify and resolve any pre-existing problems
with a cooling system, heat rejection system,
water treatment etc, before installing an
absorption chiller, or it may be unfairly blamed.
- Select an absorption chiller for full load
operation (by the incorporation of thermal stores
if necessary) as COP will drop by up to 33 at
part-load. - Consider VSD control of absorbent pump to improve
the COP at low load. - Consider access and floor-loading (typical 2 MW
Double-effect steam chiller 12.5 tons empty, 16.7
tones operating). - Ensure ambient of temperature of at least 5C in
chiller room to prevent crystallization. - http//www.climatewell.com/index.html/application
s/solar-cooling
17System with no pump(Platen-Munter system)
http//www.youtube.com/watch?v34K61ECbGD4