Title: LP Series U Uninterruptible Power Supply Technical Specification
1LP Series UUninterruptible Power
SupplyTechnical Specification Features
2LP Series U
Technical presentation
ISO 9001 UL CUL FCC Class A CE
3Key Features Benefits
- True On-Line Double Conversion provides highest
level of power reliability - Fully isolated output additional power fault
protection - Power factor corrected input (gt0.99) clean
input - Scalable Using GEDEs Unique Redundant Parallel
Architecture (RPA) maximum reliability - Superior battery management enhanced battery
life time - ECO-mode energy savings for less critical loads
e.g., during off hours, emergency lights etc - Small Footprint easy to place
4Key Features Benefits (continued)
- Excellent inrush current handling prevents
tripping protection devices - Superior overload handling protection against
unplanned overloads - Minimal Output Voltage Distortion of lt3 stable
power for the load - Multi-functional LCD screen easy to operate
- Multi language display Spanish etc
- Automatic battery testing every 500 hrs. no
surprises - Cold start unit can be started with no AC
present - No load shutdown prevents unnecessary
discharging of batteries
5Key Features Benefits (continued)
- Backfeed relay maximum safety
- EPO- Emergency Power Off maximum safety
- Multiple I/O voltages 120,240, 208 VAC
- Alarm interface RS 232 and OC contacts easy
to integrate with existing systems - Redundant power supply for critical functions
(LCD, Bypass) increased reliability - UL, C-UL and CE markings for world-wide
applications ...fits to many different mains
voltages
6Product Specifications
LP Series 8-11U 8 kVA - 6.4 kW LP Series
10-11U 10 kVA - 8 kW
- LP Series 5-11U 5 kVA- 4 kW
- LP Series 6-11U 6 kVA - 4.8 kW
Voltages and Frequencies
- Output Voltage
- 120 208 230/240
- Fully isolated, even in bypass mode
- Output Frequency
- 50 or 60 Hz
- (Front Panel Selectable)
- Input Voltage
- 208 230/240
- 120 V option (for 5/6 kVA only in additional
transformer cabinet - Input Frequency
- 45-65 Hz
Flexible input and output voltages and frequency
7Operating Mode
- True On-Line - double conversion
- Bypass enable / disable
- in frequency conversion mode no alarms
- in case of weak mains protects the equipment
against operations on mains - Programmable frequency tracking range(2, 4,
6) - compatible with gen-sets with wider frequency
range - HF PWM technique
- compact design , low-losses, excellent
characteristics
Output Completely Independent of Input Voltage
and Frequency
8LP Series U Front Panel
- LCD screen 2 lines with 16 characters
- - Information Screen
- status and alarm messages
- - Service screen
- internal settings test screens
- Set Up Screen
- setting of parameters
- Push buttons (keypads to scroll up, down, reset
and enter) - LED operation / alarm status
- On/Off switch turns unit on/off completely,
including bypass on back of unit
9Rear Panel
On/Off switch turns unit on/off completely,
including bypass
Manual Bypass
Battery fuses
Utility Bypass Protection Magnetic Circuit
breakers for overload or short circuit in the UPS
load
I/O terminals
RS232/contact interface/EPO
Conduit box
Optional SNMP or relay card
EMI
Optional RPA card
Cable entry
DC Connector for external batteries
10Technology without compromise
MANUAL BYPASS
No inrush current during start up
Bypass MCB
Elektronic
Bypass
Backfeed protection
Mains MCB
H bridge
HF input
Output
Converter
converter
RFI
Filter
External
Battery
LCD
Stepdown
Internal
Converter
Supply
Batteries
up
enter
down
operation
alarm
General alarm, Utility failure
4X
optional 120 Volt auto-input xfrmr
Bypass active, Batterey low
L N
L
UPS Shutdown
MICRO- processor CONTROL
L
RS232
External
Emergency
battery
shutdown
disconnected
INTERFACE
Option SNMP card
11Technology with Premium Performance
Input voltage187-285 V at 100 load
Bypass MCB
RFI
Input voltage 150-285 V at 50 load
internal supply
F3
P
Line MCB
N
12Technology Output Converter
Inverter DC
Isolation on bypass
240 V
Bypass
380V
voltage
208V
Output
HS
F3
H-BRIDGE
C2
Output
converter
C1
current
Output
2x 120 V 1x 120 V 208 V 240 V
transformer
temp.sensor
Heatsink
4X
IGBT
temp.sensor
Fan speed controlled by load heat sink
temperature
13Battery Specifications
- Standard 20 X batteries 12V/7Ah (5/6kVA) or
12V/12Ah (8/10kVA) - Charge voltage 271V, 13.55V/battery
- Constant current/constant voltage characteristic
boost charge current is 0.3 C - Temperature protected till 45ÂșC
- Battery extension up to 500 Ah
- Battery capacity programmable over LCD/serial port
14Superior Battery Management
- Ripple-free Boost Charging
- Temperature Compensated Charging
- Load dependent end of discharge voltage
- No-load Shutdown
- Automatic Battery Test /every 500 hours
- Deep Calibration Test
- Load dependent runtime prediction
- Load dependent battery low signal
- Maximum Up-time
- Prevents Damage
- Prolonged Battery Lifetime
- No Surprises
15Output Performance
- Output THD lt 3 for linear loads
- Output Power Factor 0.8
- Output filter performance control enabling robust
operation - Fully isolated output
- Protected against
- Low/high DC voltage
- Over-temperature
- Overload
- AC on Output
- Short circuit
No Compromise on Output Performance
16Bypass Specifications
- Bypass input voltage -10 to 10
- Bypass frequency window selectable 2, 4, 6
- Tracking rate 1 Hz/sec low, 5 Hz/sec high
- Protected against overload
- Short circuit protection
- Galvanic isolation
State-of-the-art Bypass
17Communication
- Standard RS 232 dialogue
- UPS shutdown
- Emergency Power off ( EPO )
- External DC - fuse alarm
- Optional SNMP - card
- RS 232 is not available if SNMP is
installed - Dry contacts
-
Easy to integrate into computer network
18Available Options
- Power Distribution unit (PDU)
- External battery cabinets
- External battery cable
- Seismic anchor
- SNMP interface card
- Relay interface card
- RPA kit (Redundant Parallel Architecture)
- Alarm boxes
- Connectivity products, like Splitter box
interface kits interface software for all
common OS, incl Java - 120 Volt input voltage transformer/cabinet