Title: CONTROLS OF SUPER CRITICAL BOILERS
1CONTROLS OF SUPER CRITICAL BOILERS
Presentation By AJAY SHUKLA Sr.Faculty PMI,
2Boiler Turbine Control
3Boiler Following Mode
4Turbine Following Mode
5Coordinate Mode Control
6Coordinate Mode Control
7Drum and OT Control Comparison
8Drum and OT Control Comparison
9OT Control Overview
10Cycle of Supercritical Power Plant
11(No Transcript)
12Supercritical Power Plant
13OT Control Overview
14OT Start up Control mode
15Super Critical Units Controls Mode
16Flushing Mode
17Flushing Mode
18Start-Up System with Recirculation
Start-Up System Recirculation Pump in Main
Bypass Line
SH
Separator
Flash Tank
WW
C
ECO
HWL
To Condenser
C
Deaerator
HPH
C
BFP
19Start UP System
20START-UP
- If the water system of the boiler is empty
(economizer, furnace walls, separators), then the
system is filled with approximately 10 TMCR feed
water flow. - When the level in the separator reaches
set-point, the WR valve will begin to open. - When the WR valve reaches gt30 open for
approximately one minute, then increase feed
water flow set-point to 30 TMCR. As the flow
increases, WR valve will reach full open and ZR
valve will begin to open. - The water system is considered full when
- The separator water level remains stable for
two(2) minutes - and
- The WR valve is fully opened and ZR valve is gt15
open for two(2) minutes.
21(No Transcript)
22SEPARATOR STORAGE TANK LEVEL CONTROL
- Separator level is maintained by the combined
action of a separator storage tank level feed
water demand and the positioning of WR and ZR
drain valves. - Feed water demand is developed in response to
separator storage tank level error and total fuel
flow so as to prevent tank level from dropping
too low. - The WR and ZR valves are controlled in a split
range manner to maintain the liquid level once
the level reaches a high limit. - The WR valve will respond first and then the ZR
when the WR exceeds its linear operating range. - Tank geometry is such that fluctuations in tank
level are very dynamic, for this reason, only
proportional control action established through
the WR/ZR function curves is used to position
these valves in response to level error.
23UG VALVE CONTROL
- Control objective
- Maintain minimum economizer inlet flow.
- Control action
- The boiler circulating pump is started following
the start of a turbine-driven feed water pump and
the final clean-up cycle. This pump circulates
feed water from the evaporator outlet back to the
economizer inlet. - Located at the outlet of this pump is the UG
valve which controls economizer inlet flow during
the start-up phase of operation. Demand for this
recirculation control valve is established based
on measured economizer inlet flow compared to a
minimum boiler flow set point.
24Separator water circuit of Super Critical
25FEEDWATER CONTROL LOOP
- Control objective
- Develop total unit feed water demand as required
to support unit load. - Adjust feed water demand to maintain desired
separator outlet temperature. - Adjust separator outlet temperature set point as
required to maintain acceptable platen superheat
spray control range. - Incorporate separator storage tank level (wet
mode) feed water demand. - Maintain minimum required economizer inlet flow.
- .
26Feedwater Control
27Feed water firing rate ratio control
28Feed water firing rate ratio control
29Feed Forward with model
Process
Setpoint
Feed Forward
f(x)
S
P /-
C -/
D
K
?
C /-
P /-
30Feed Forward
process
FF
setpoint
PROCESS
FF
f(x)
P /-
C -/
P /-
C -/
D
D
K
K
C /-
P /-
C /-
P /-
X
S
31Model predictive control
MW
_
Fuel with model
Without model
Turbine setpoint
Water wall Temperature
C
tsec
0
60
180
240
300
120
32Firing Rate Master
33Fuel Rate Master
34Feed Forward Firing Rate Control
35Feed Forward Firing Rate Control
36ANY QUESTIONS PLEASE
37Yuhuan 4x1000MW Preparation of light off
38Multi-combusting Nozzles with Separated Overfire
Air Damper
39(No Transcript)
40(No Transcript)
41(No Transcript)
42(No Transcript)
43(No Transcript)
44START-UP contd..
- Water flows through the economizer and
evaporator, and discharges the boiler through
the WR valve to the flash tank and via connecting
pipe to the condenser. - Start BCP and open the UG valve to establish
minimum water wall flow - at 30 TMCR.
- As the pressure is raised, first the WR and
then the ZR valves will open when - separator water level increases due to boiler
water swell. As pressure further - increases, the WR and ZR valves will start to
close as the water level decreases. - The steam temperature at the separator inlet will
reach a stable superheated - condition at app. 30 TMCR, causing the level in
the separator to decrease and - eventually disappear. The boiler is now in
once-through mode (dry mode). The - BCP (Boiler Circulating Pump) will be stopped
automatically. - It is extremely important that minimum water wall
flow be maintained at all times when firing the
boiler to prevent tube damage due to overheating.
45FEEDWATER CONTROL LOOP contd..
- Demand for feed water is established
predominately by the Boiler Master demand. - This signal, processed though a boiler transfer
function provides the feed forward component of
the total feed water demand. - The boiler transfer function is a tunable
dynamic element providing a means to dynamically
match the feed water feed forward demand to
actual evaporator heat transfer. - Optimization of the feed forward in this manner
minimizes temperature fluctuations that may
otherwise result from varying dynamic response
between the firing and feed water control systems
(as they relate to evaporator heat transfer)
thereby lessening the dependence on feedback
correction.
46FEEDWATER CONTROL LOOP contd..
- The first controller acts on a load dependent
average platen spray differential temperature. - Its output represents the required adjustment to
evaporator heat transfer/steam generation to
maintain both the steam conditions and flue gas
temperatures entering the platen superheat
section so as to ensure adequate platen spray
control range. - A second controller acts on a load dependent
separator outlet temperature set point corrected
by the platen spray differential temperature
controllers output. - This controller acts to adjust feed water in
response to firing system disturbances and the
relatively fast effect they have on separator
outlet steam temperatures. - The overall combined feed water feedback control
action is such that feed water demand is
responsive to changes in the overall unit heat
transfer profile.
47FEEDWATER CONTROL LOOP contd..
- The combined feed forward/feedback demand signal
is subject to a minimum economizer inlet flow set
point (wet mode) activated if the boiler
circulation pump is not in service and the unit
is being fired. - This ensures the minimum economizer inlet cooling
flow is maintained by the feed water supply
system in the event the start-up system is not
available. - The feed forward/feedback demand signal is
subject to a second wet mode feed water demand
developed to support separator storage tank level
control. - The resulting demand provides the set point to a
feed water master controller. - The fuel/feed water ratio protection logic
provides overriding control of individual feeder
speed demands in the event of an excessively
high fuel to feed water ratio.
48THANK YOU