ELECTRICAL INSTALLATION PLANNING - PowerPoint PPT Presentation

1 / 32
About This Presentation
Title:

ELECTRICAL INSTALLATION PLANNING

Description:

... Type of structure/location & what it is used for Number & type of circuits Current carrying capacity of the cable Voltage drop Fault ... Calculation Assessment ... – PowerPoint PPT presentation

Number of Views:106
Avg rating:3.0/5.0
Slides: 33
Provided by: Valu106
Category:

less

Transcript and Presenter's Notes

Title: ELECTRICAL INSTALLATION PLANNING


1
ELECTRICAL INSTALLATION PLANNING
  • LSEGG307A
  • 9080F

2
Assessments
Theory Test 1 Theory Test 2 Assignments Final
Examination
10 20 10 60
3
Lesson Content
  • Protection against harmful effects
  • Correct functioning
  • Supply characteristics
  • Determining Maximum demand
  • Voltage drop limitations
  • Arrangement into circuits
  • External Factors
  • Protection against
  • Integrity of fire rated construction
  • Direct contact
  • Indirect contact
  • Thermal effects
  • Overcurrent
  • Faults
  • Mechanical movement

4
SELECTION OFCABLE EQUIPMENTWITH REGARD TO
  • Type of structure/location what it is used for
  • Number type of circuits
  • Current carrying capacity of the cable
  • Voltage drop
  • Fault loop impedance
  • Maximum demand
  • Fault levels
  • Metering
  • Damp situations
  • Voltage levels

5
What you will require each week
  • AS/NZS 30002007
  • AS/NZS 3008 1998
  • Calculator

6
THIS SUBJECT WILL BE EXAMINED IN THE CAPSTONE TEST
7
Lesson 1
Determining a Wiring System for an Installation
8
What determines the type of building structure
chosen?
  • How it is going to be used
  • Local authority requirements
  • Cost
  • Time requirements
  • Site access
  • Appearance/Aesthetics
  • Domestic
  • Multiple domestic
  • Commercial
  • Industrial

9
What Determines The Type of Cable System Chosen?
  • Power requirements of each of the loads connected
  • How the loads are used
  • Flexibility
  • Safety of Human Property and Livestock
  • Not be too inconvenient if a fault occurs
  • Be able to be easily worked on and tested
  • Compatible with the climate
  • Not be overloaded
  • Not have too much voltage drop
  • Not be affected by the Environment/Atmosphere

Constant or Intermittent
Temperature, High Humidity, Corrosive
atmospheres, Mechanical damage, etc
10
What Determines The Type of Cable System Chosen?
  • Power requirements of each of the loads connected
  • How the loads are used
  • Flexibility
  • Safety of Human Property and Livestock
  • Not be too inconvenient if a fault occurs
  • Be able to be easily worked on and tested
  • Compatible with the climate
  • Not be overloaded
  • Not have too much voltage drop
  • Not be affected by the Environment/Atmosphere

Temperature, High Humidity, Corrosive
atmospheres, Mechanical damage, etc
AS/NZS 3000 1.6.1
11
Other Factors That An Electrician Has To
Consider/Abide by -
  • AS/NZS 3000 and other electrical standards
  • Local supply authority standards
  • Building codes
  • Fire ratings
  • Heritage orders etc
  • Appearance
  • Speed of installation
  • Cost

Concealed or Surface
Materials Labor
12
Timber Frame
Advantages
  • Insulator, so earthing not a problem
  • Material relatively soft so cable damage not a
    major problem

Disadvantages
  • Drilling in structural members is limited
  • All service holes have to be drilled on site

13
Steel Frame
Used extensively used in office partitions
Advantages
  • Most service holes are pre punched and
    de-burred/flanged
  • Very lightweight construction.

Disadvantages
  • Earthing of the frame has to be considered
  • Additional holes made must be de-burred

14
Timber Steel Frame
TPS inside frame is most commonly used
Why?
15
Full Brick Concrete Slab
Concrete slab Deck work
MD conduit with Building wire
Why not TPS?
16
Industrial Installations
Cable Ladder/tray
Steel Conduit
Steel Wire Armour
SWA Cable is more Expensive than Steel Conduit so
why is more commonly used?
MIMS
17
Exercise 1
18
Planning Arranging Circuits
Why do we break the installation up into circuits?
Why not put all the loads on one or two circuits?
19
Circuits
How many? What size?
  • Reduce the inconvenience in the event of a fault
  • Safe inspection, testing maintenance
  • Unwanted nucence tripping
  • Fault protection.

Different loads require different tripping times
AS/NZS 3000 Clause 1.6.1
AS/NZS 3000 Clause 2.6.2.1
AS/NZS 3000 Clause 1.5.5.3
20
Circuits
How many? What size?
  • The current required by each load
  • The nature usage of each load
  • Economics
  • Flexibility of the installation

The smaller the cable the cheaper
21
Loading Of The Circuit
To major factors that have to be considered
  • The power requirement of the load
  • How the load is used

If used for more than 15 minutes it is considered
an Extended Period
22
Example 1
Circuit requirements for a 4.8kW 230 Volt HWS
Maximum current
20A
Will it be used for extended periods?
On its own circuit?
Or with other loads on one circuit?
23
Example 2
Circuit requirements for two 4.8kW 230 Volt HWS
4mm2 TE 2.50/m 2.5mm2 TE 0.85/m
Cheaper to make two circuits
24
Example 3
Commercial installation
Containing 45 x 60W light fittings
Are the lights likely to be all operating at the
same time?
11.7A
Protection will eventually trip. 2 Circuits are
required
25
Example 3
Commercial installation
Containing 45 x 60W light fittings
Are the lights likely to be all operating at the
same time?
11.7A
Protection will eventually trip. 2 Circuits are
required
26
Example 3
Domestic installation
Are the lights likely to be all operating at the
same time?
11.7A
Would the protection trip if all the lights were
on for a short period?
AS/NZS 3000 Clause 2.5.3.1
Would the cable be damaged if all the lights were
on for a short period?
27
Socket Outlets
Do we put more than 1 double socket outlet on a
single circuit?
What is the minimum size cable that we can
generally use?
AS/NZS 3000 Table 3.3
AS/NZS 3000 Table C8
28
Known Loads Connected To Socket Outlets
What type of loads are in the kitchen and laundry
of a house?
Would you put all these loads on the one circuit?
29
Exercise 2
30
Maximum Demand
  • The Current that is normal expected by this type
    of load

Average Current
AS/NZS 3000 Clause 1.6.3
AS/NZS 3000 Clause 2.2.2
31
Maximum Demand
  • By
  • Calculation
  • Assessment
  • Measurement
  • Limitation
  • Calculation Using
  • Appendix C
  • HB 301

15 minutes Extended Period
AS/NZS 3000 Clause 1.6.1 (b)
Must be negotiated with user
Consumer Sub-main size can be determined by sum
of the individual outgoing protection devices
82A
10A
16A
16A
20A
20A
32
Maximum Demand
  • Maximum Demand Value
  • AMPS

Installation Type
Protection Requirements
Cable Size
Length of Run
Voltage Drop
Fault Loop
Fault Level
Write a Comment
User Comments (0)
About PowerShow.com