Title: RWD CONTROLLERS TECHNICAL
1RWD CONTROLLERSTECHNICAL
- HVAC Products Americas Region
2 3RWD82U controller
RWD82U Connection Diagram
4RWD82U
Applications with corresponding selectable
auxiliary function
5Main Sequences
6RWD82U - Main Sequence
2 Heating sequences or 2 Reverse Acting sequences
(Dependent)
- Application No. 10 - 19
- 2 electric heaters
- heating valve with heating pump
7RWD82U - Main Sequence
2 Heating sequences or 2 Reverse Acting sequences
(Independent)
8RWD82U - Main Sequences
Heating sequence or Direct or Reverse Acting
Sequence (3-point)
9RWD82U - Main Sequence
Heating Cooling sequences or Reverse Direct
acting sequences
10RWD82U - Main Sequence
2 Cooling sequences or 2 Direct Acting sequences
(Independent)
11RWD82U - Main Sequence
2 Cooling sequences or 2 Direct Acting sequences
(Dependent)
12RWD82U - Main Sequences
Cooling sequence or Reverse or Direct Acting
sequence (3-position)
13 14RWD62U controllerTermination
15RWD62
Applications with corresponding selectable
auxiliary function
16Main Sequences
17RWD62 - Main Sequences
Heating sequence or Direct Acting sequence
Output Y1 can be switched from D.A. to R.A.
18RWD62 - Main Sequences
2 Heating sequences or 2 Direct Acting sequences
X1
Y1
Y2
Y
Temp.
RWD62U
Outputs Y1 and Y2 can be switched from D.A. to
R.A.
19RWD62 - Main Sequences
Heating Cooling sequences or Direct Reverse
acting sequences
Output Y1 can be switched to R.A. and Y2, D.A.
20RWD62 - Main Sequences
Cooling sequences or Reverse Acting sequences
Output Y1 can be switched to D.A.
21RWD62 - Main Sequences
2 Cooling sequences or 2 Direct Acting sequences
Output Y1 and Y2 can be switched to D.A.
22 23RWD68U controller
24RWD68U
Applications with corresponding selectable
auxiliary function
25Main Sequences
26RWD68U - Main Sequence
Heating sequence or Reverse Acting sequence
27RWD68U - Main Sequence
2 Heating sequences or 2 Direct Acting sequences
(Dependent)
- Application No. 20 - 29
- Heating coil with electric heater
- By-pass system with pump 3-way valve
- Output Y1 can be switched to R.A.
28RWD68U - Main Sequence
2 Heating sequences or 2 Direct Acting sequences
(Independent)
Output Y1 can se switched to R.A.
29RWD68U - Main Sequence
Heating Cooling sequences or Reverse Direct
acting sequences
X1
Y1
Q1
Y
Q1
Temp.
RWD68U
Output Y1 can be switched to R.A.
30RWD68U - Main Sequence
Heating Cooling sequences or Reverse Direct
acting sequences
- Application No. 50 - 59
- Heating Coil and Direct Chiller
- Output Y1 can be switched to D.A.
31RWD68U - Main Sequence
2 Cooling sequences or 2 Direct Acting sequences
(Dependent)
- Application No. 60 - 69
- Direct chiller
- Output Y1 can be switched to D.A.
32RWD68U - Main Sequence
2 Cooling sequences or 2 Direct Acting sequences
(Independent)
- Application No. 70 79
- Output Y1 can be switched to D.A.
33RWD68U - Main Sequence
Cooling sequence or Direct Acting sequence
- Application No. 80 89
- Output Y1 can be switched to D.A.
34Auxiliary Functions
35RWD - Auxiliary Functions
1. Remote setpoint (_1)
- A remote setpoint transmitter QAA25U (1K Ni) or
544-764 1K Plat), connected to X2 and configured
accordingly, assumes the function of the setpoint
36RWD - Auxiliary Functions
2. PI Limiter (_2 _3)
- The limiter function with PI control enables
absolute(or relative) maximum or minimum
limitation of the supply air temperature (X2). - When the value drops below or exceeds the limiter
setpoint, the limiter function overrides the
standard control function to maintain the limiter
setpoint.
37RWD - Auxiliary Functions
3. Setpoint Compensation (_4)
- The temperature setpoint X1 is controlled by the
temperature as measured at sensor X2. - Configuration of the RWD62U defines the influence
on setpoint X1. - The example shows the supply air temperature
setpoint as controlled by the outside temperature.
38RWD - Auxiliary Functions
4. Cascade Control (_5)
- X2 - Supply air temperature sensor
- You can select the PI/PI room/supply air
temperature cascade control. In this case, the
virtual PI room temperature controller determines
the setpoint within the limiter setpoints for the
PI supply air temperature controller.
39RWD - Auxiliary Functions
5. Summer / Winter operation (_6 _7)
- X2?M terminals (Digital/analog)
- A digital switch or anlog output between
terminals X2 and M can be used to implement
summer/winter changeover.
40RWD - Auxiliary Functions
5. Summer / Winter operation (_6 _7) (Cont.)
- Digital changeover
- When the contact is closed, summer operation is
selected. Output Y1 is set to Reverse Action
(cooling). - When the contact is open, winter operation is
selected. Output Y1 is set to Direct Action
(heating). - Analog changeover
- When the X2 reach over the setpoint, summer
operation is selected. Output Y1 is set to
Reverse Action (cooling). - When the X2 is below the setpoint, winter
operation is selected. Output Y1 is set to Direct
Action (heating).
41RWD - Auxiliary Functions
6. Maximum Priority (_8)
- If the input value (010V) of the input X2 is
greater than the calculated output of the cooling
sequence, the output will use the X2 input value
as output value. This is active even when the
controller is working with the heating sequence.
42RWD - Auxiliary Functions
7. Day / Night Setpoint (For all RWDs,
independent of App. No.)
- D1?M potential-free contact (External time clock)
- A timer contact between terminals D1 and M can be
used to implement setpoint changeover for
day/night operation. - When the contact is open, the setpoint for day
operation is selected. - When the contact is closed, the setpoint for
night operation is selected.
43RWD - Software tool125-3481
- Simple windows based operation
- Numbered standard applications
- Customize applications
- Print-out of final settings
- Hide selected parameters from LCD
- Create your own application library based on
system type or customer