MINIMUM ACCEPTABLE LEVELS OF SAFETY - PowerPoint PPT Presentation

1 / 27
About This Presentation
Title:

MINIMUM ACCEPTABLE LEVELS OF SAFETY

Description:

minimum acceptable levels of safety & reliability the wiring code of trinidad and tobago tts 171 part one presented by hayden batson electrical inspector 1 government ... – PowerPoint PPT presentation

Number of Views:54
Avg rating:3.0/5.0
Slides: 28
Provided by: Hayden7
Category:

less

Transcript and Presenter's Notes

Title: MINIMUM ACCEPTABLE LEVELS OF SAFETY


1
MINIMUM ACCEPTABLE LEVELS OF SAFETY RELIABILITY
  • THE WIRING CODE OF TRINIDAD AND TOBAGO
  • TTS 171 PART ONE

2
PRESENTED BY
  • HAYDEN BATSON
  • ELECTRICAL INSPECTOR 1 GOVERNMENT ELECTRICAL
    INSPECTORATE

3
Annex C
  • Provides Sub-Circuit rating and requirements.
  • C.1 Gives the maximum sub-circuit ratings for
    domestic, commercial and industrial premises.
  • C.2 Gives the sub-circuit requirements.

4
Table C-1
5
Section B gives those that are not shown before
6
C.2.1
  • Ground-fault Circuit Interrupter protection shall
    be provided for personnel (ref sec 210-8 NEC
    1999) in
  • a) Bathrooms
  • b) Outdoor receptacles
  • c) Garages
  • d) Counter tops
  • e) Other required locations.

7
C.2.2Additional requirements for conformity.
  • Receptacle outlets shall be spaced approx. 4M
    along walls in rooms.
  • Receptacle outlet and lighting circuits shall be
    separated except by special permission of the
    CEI.

8
  • The rating for a general purpose domestic
    receptacle is 180 VA.
  • The minimum height of the service entrance
    connection shall be 4M, observing the minimum
    clearance of 6M over road ways.
  • We will maintain the IEE color code.

9
INSTALLATION METHODS
  • The exact current carrying capacity of
    conductors is affected by a number of factors
    besides CSA, one of which is the way they are
    installed.
  • Two examples are are shown using table D.5.D.1

10
(No Transcript)
11
Example 1
  • Installing a run of 10 mm2 XLPE insulated
    multi-core armored cable
  • Using Method 1, a 3 or 4 core cable connected to
    a 3-ph ac supply will carry 73A.
  • Using Method 11, a 3 or 4 core cable connected as
    above will carry 78A.

12
Example 2
  • Installing a run of 95mm2 XLPE insulated
    multi-core armoured cable.
  • Using Method 1, a 3 or 4 core cable connected to
    a 3-ph ac supply will carry 289A.
  • Using Method 11, a 3 or 4 core cable connected to
    a 3-ph ac supply will carry 304A.

13
  • When using cards with current rating tables the
    method of installation for those values must be
    observed.

14
VOLTAGE DROP CONSIDERATIONS
  • Apart from voltage drop and installation methods,
    factors such as
  • ambient temperature
  • grouping
  • thermal insulation
  • operating temperature
  • of the cable also weigh in cable selection.

15
  • Emphasis however must be placed on voltage drop.
  • WHY?
  • This value should not exceed 3 in the circuit of
    which that cable forms apart.

16
  • Not more than 6.90 V for a 230V 1-ph circuit
  • Not more than 14.4V for a 480V 3-ph circuit.

17
  • Note also that the maximum allowable drop from
    the POE to fixed current using equipment must not
    exceed 4.

18
VOLTAGE DROP TABLES
  • These are tabulated for a current of 1 Amp and a
    length of 1 Metre along the route taken.

19
  • For a balanced 3-ph system the tables relate to
    line voltage.

20
  • Therefore the total voltage drop per run
  • Vd mV x I x L
  • 1000
  • Where I current in amps
  • L length in metres
  • mV approx voltdrop/amp/metre.

21
Example
  • Consider a run of 200M to be installed in air
    (ref method 13) to carry a current of 100A from a
    supply of 415V 3-ph ac, the cable being of copper
    conductor, XLPE insulated, armoured and PVC
    sheathed.

22
  • Let mV be voltage drop in millivolts
  • Then Vd mV x I x L
  • 1000
  • Transposing mV Vd x 1000
  • I x L

23
  • Max permissible voltage drop 3 of 415V

  • 12.45V
  • Inserting values for I, L and max permissible
    voltage drop
  • Then mV 12.45 x 1000 0.62 mV
  • 100 x 200
  • Referring to the following table.

24
Select value to or just less than 0.62mV i.e.
60mV.
25
Apply current carrying capacity table.
26
  • This shows that we may have used a 25 mm2 cable
    without voltage drop consideration.

27
  • THE END
Write a Comment
User Comments (0)
About PowerShow.com