Title: Computer Multi Control III CMCIII
1Computer Multi Control IIICMCIII
2Inhaltsverzeichnis
- 7030.000 CMCIII Processing Unit
- 7030.010 CMCIII Processing Unit Compact
- 7030.030 CMCIII CAN-Bus Unit for 2 unit channels
- 7030.040 CMCIII I/O Unit
- 7030.050 CMCIII Power Unit
- 7030.060 CMCIII Power pack
- 7030.070 CMCIII mounting unit, 1U
- 7030.071 CMCIII mounting unit for enclosure frame
- 7030.080 CMCIII programming cable
- 7030.090 CMCIII CAN-Bus connection cable
- 7030.100 CMCIII CAN-Bus Unit for sensor
- 7030.110 CMCIII temperature sensor with CAN-Bus
- 7030.111 CMCIII temperature/humidity sensor with
CAN-Bus - 7030.120 CMCIII infrared access sensor with
CAN-Bus - 7030.130 CMCIII vandalism sensor with CAN-Bus
- 7030.140 CMCIII analogue airflow sensor with
CAN-Bus - 7030.150 CMCIII analogue differential pressure
sensor with CAN-Bus - 7030.190 CMCIII universal sensor with CAN-Bus
37030.000CMC III Processing Unit The system
monitors IT racks, enclosures or rooms. The
Processing Unit is the central unit of the CMC
III monitoring system. Up to 32 sensors / CAN-Bus
connection units may be connected. The Processing
Unit may be connected to the data network via
Ethernet, configured via Web / USB, can send
alarms via an e-mail server and connect to the
Network Management System of a company via
SNMP/OPC. Technical specificationsWxHxD 138 x
40 x 12012 front mmColour RAL
9005/7035Temperature range 0 C to 55 C
Operating humidity range5 to 95 relative
humidity, non-condensingProtection category IP
30 to EN 60 529Max. CAN-Bus sensors 32CAN-Bus
jacks RJ45 2Max overall cable length for
CAN-Bus 2 x 50 m Network interface (RJ
45)Ethernet to IEEE 802.3 via 10/100BaseT with
PoEProtocols TCP/IPv4, TCP/IPv6, SNMPv1,
SNMPv2c, SNMPv3, Telnet, SSH, FTP, SFTP, HTTP,
HTTPS, NTP, DHCP, DNS, SMTP, XML, Syslog,
LDAPUSB interface- Mini USB for system
setting- for USB for data recordingand SW
updates up to 32 GBMemory card slot SD-HCupt
to 32 GB data recordingSerial RS232 (RJ 12)for
display or GSM or ISDN unit Digital inputs
(terminal) 2Relay outputs (terminal)
1Change-over contact max. 24 V DC, 1 AService /
reset button 1Piezo signal generator 1LED
display OK/warning/alarm/ network statusRated
voltage 24 V DCRedundant power supply inputs 3
(24 V DC jack / terminal/ PoE)Realtime clock
24h energy-bufferedUser administration
LDAPUser interface WEB serverControl room
connection OPC serverSensors
Temperature/access
47030.010CMC III Processing Unit CompactThe
system monitors IT racks, enclosures or rooms.
The Processing Unit is the central unit of the
CMC III monitoring system. Up to 4 sensors /
CAN-Bus connection units may be connected. The
Processing Unit may be connected to the data
network via Ethernet, configured via Web / USB,
can send alarms via an e-mail server and connect
to the Network Management System of a company via
SNMP/OPC.Technical specificationsWxHxD 138 x
40 x 12012 front mmColour RAL
9005/7035Temperature range 0 C to 55 C
Operating humidity range5 to 95 relative
humidity, non-condensingProtection category IP
30 to EN 60 529Max. CAN-Bus sensors 4CAN-Bus
jacks RJ45 1Max overall cable length for
CAN-Bus1 x 50 m Network interface (RJ
45)Ethernet to IEEE 802.3 via 10/100BaseT with
PoEProtocols TCP/IPv4, TCP/IPv6, SNMPv1,
SNMPv2c, SNMPv3, Telnet, SSH, FTP, SFTP, HTTP,
HTTPS, NTP, DHCP, DNS, SMTP, XML, Syslog,
LDAPUSB interfaceMini USB for system
settingSerial RS232 (RJ 12)for display or GSM
or ISDN unit Digital inputs (terminal) 2Relay
outputs (terminal) 1Change-over contact max. 24
V DC, 1 AService / reset button 1Piezo signal
generator 1LED display OK/warning/alarm/
network statusRated voltage 24 V DCRedundant
power supply inputs 3(24 V DC jack / terminal/
PoE)Realtime clock 24h energy-bufferedUser
administration LDAPUser interface WEB
serverControl room connection OPC
serverSensors Temperature/access
57030.030CMC III CAN-Bus Unit for 2 unit
channelsThe system offers compatibility with
CMC-TC units. Like the CMC-TC they can be
connected to the CMC III system. Two channels are
available for connecting these units (FCS, LCP
Standard, DRC, PCU, active PSM, PSM busbars,
measurement module). The unit has two RJ45
connections with an integral CAN-Bus. Technical
specificationsWxHxD 138 x 40 x 12012 front
mmColour RAL 9005/7035Temperature range 0
C to 55 C Operating humidity range5 to
95 relative humidity, non-condensingProtection
category IP 30 to EN 60 529Interfaces RJ45 2
CMC TC UnitsCAN-Bus jacks RJ45 2
67030.040CMC III I/O UnitThe I/O Unit has 8
digital inputs and 4 relay outputs. Signals from
3rd systems may be recorded and processed in the
CMC III. The CMC III can execute control commands
via the relay outputs or send messages to third
party systems.Technical specificationsDigital
inputs (terminal) 8 NC/NORelay outputs
(terminal) 4Change-over contact max. 24 V DC, 1
ACAN-Bus jacks RJ45 2Rated voltage 24V
DCWxHxD 138 x 40 x 12012 front mmColour RAL
9005/7035Temperature range 0 C to 55 C
Operating humidity range5 to 95 relative
humidity, non-condensingProtection category IP
30 to EN 60 529
77030.050CMC III Power UnitThe Power Unit has an
input with a C14 IEC 320 connection. The input is
fused at 10 A and may be fed with 100-230 V AC.
The power input is switched via two relays to two
C13 IEC 320 connections. Via the Power Unit the
CMC III is able to supply fans or other equipment
with power, to switch them on / off or to control
them via a CMC III system-connected temperature
sensor. In addition the Power Unit measures the
following electrical parametersTechnical
specificationsMeasuring range 100 to 230 V
50/60HzMeasuring range 0 to 60 HzMeasuring
range 0 to 10 AMeasuring range /- 0 to
90Measuring range 0 to 2.3kWMeasuring range
0 to 100,000 kWhInput C14 100-230 V, 10 A50/60
HzFuse 10A Output 2x C13 100-230 V,in total
up to 10 A, 50/60 HzCAN-Bus jacks RJ45 2Rated
voltage 24V DCWxHxD 138 x 40 x 12012 front
mmColour RAL 9005/7035Temperature range 0
C to 55 C Operating humidity range5 to
95 relative humidity, non-condensingProtection
category IP 30 to EN 60 529
87030.060CMC III Power packIntegral blue LED for
indicating the status. The CMC III power pack is
required to supply the Processing Unit with
power. It may be connected to the jack or to the
terminal of the redundant power supply inputs.
For additional power supply of the CMC III
CAN-Bus unit it is also possible to connect 2
unit channels.Technical specificationsInput
C14 100-230 V, 50/60 HzOutput 24V DC, 2
AWxHxD 138 x 40 x 12012 front mmColour RAL
9005/7035Temperature range 0 C to 40 C
Operating humidity range5 to 95 relative
humidity, non-condensingProtection category IP
30 to EN 60 529
97030.070CMC III mounting unit, 1 UTo
accommodate PU, PU Compact, control units, CMC
III CAN-Bus unit and CMC III power pack.The
mounting unit can accommodate up to 3 units and
is secured in the 482.6 mm (19") frame. The
accommodation components are plugged-in from the
front and automatically locked. In the rear
section of the system there is an integral
attachment facility for cable clamping
7610.000.Technical specificationsWidth 482.6
mm (19)Height 44.25 mm (1 U)Depth 141 mm
Material Sheet steel, zinc plated / front
aluminiumTemperature range 0 C to 55 C
Operating humidity range5 to 95 relative
humidity, non-condensing
107030.071CMC III mounting unit for enclosure
frameTo accommodate PU, PU Compact, control
units, CMC III CAN-Bus unit and CMC III power
pack.The mounting unit can accommodate up to 1
units and is mounted on the enclosure frame. The
accommodation component is plugged-in from the
front and automatically locked. In the rear
section of the system there is a facility for
integral cable clamping.Technical
specificationsWidth 170 mm Height 44.25 mm
(1 U)Depth 160 mm Material Sheet steel,
zinc-platedTemperature range 0 C to 55 C
Operating humidity range5 to 95 relative
humidity, non-condensing
117030.080CMC III programming cableThe
programming cable is required for commissioning
of the Processing Unit (PU) or PU Compact. Supply
includes CD with USB driver software.Technical
specificationsConnector 1 USB series A (for
laptop)Connector 2 Mini USB (for CMC III
PU)Length 3 m Temperature range 0 C to
55 C Operating humidity range5 to 95
relative humidity, non-condensing
127030.090/.091/.092/.093/.094/.095CMC III CAN-Bus
connection cableThis can be used to connect the
PU withthe CAN-Bus sensors III, units III,
control units III as a bus. Also for cabling them
together.The cable is used for information and
power transmission of the individual CAN-Bus
units.Technical specificationsConnector 1
RJ45Connector 2 RJ45Length 0.5m/1m/1,5m/2m/5m/
10m Temperature range 0 C to 55 C
Operating humidity range5 to 95 relative
humidity, non-condensing
137030.100CMC III CAN-Bus Unit for sensorThe
sensor has an interface to connect an CMC II
(CMC-TC) sensor of the predecessor
seriesTechnical specificationsInterfaces
RJ12 1 CMC II sensorCAN-Bus jacks RJ45
2Protection category IP 30 to EN 60
529Temperature range 0 C to 55 C
Operating humidity range5 to 95 relative
humidity, non-condensingWxHxD 110 x 30 x 40
mmColour RAL 9005/7035
147030.110CMC III temperature sensor with
CAN-BusAn NTC temperature sensor is integrated
in the sensor housing.An external NTC
temperature sensor with 2 m connection cable is
also included. Technical specificationsNTC
resistance 10 k Ohm at 25 CTemperature
measurement range (internal sensor) 0 C to
55 C Temperature measurement range (external
sensor) - 40 C to 80 C Measurement
accuracy /- 2K between 10C and
40CResolution 0.1K Jack for external sensor
1CAN-Bus jacks RJ45 2Protection category IP
30 to EN 60 529Temperature range 0 C to
55 C Operating humidity range5 to 95
relative humidity, non-condensingWxHxD 80 x 28
x 40 mmColour RAL 9005/7035
157030.111CMC III temperature / humidity sensor
with CAN-BusAn electronic temperature sensor for
sensor measurement is integrated in the sensor.
An electronic humidity sensor for measuring the
relative humidity is also integrated. Measuring
range 0 C to 55 C Measuring range 5 to
95 relative humidityTechnical
specificationsCAN-Bus jacks RJ45 2Protection
category IP 30 to EN 60 529Temperature range
0 C to 55 C Operating humidity range5
to 95 relative humidity, non-condensingWxHxD
80 x 28 x 40 mmColour RAL 9005/7035
167030.120CMC III infrared access sensor with
CAN-BusThe sensor reports if the the rack door
is open or closed. It is also possible to monitor
side panels, roof plates or room doors. The
sensor has an integral infrared diode as
transmitter and an infrared receiver. If the
infrared light is reflected, for example, by a
door, the access sensor reports 'door
closed'.Technical specificationsMode of
operation visualTransmitter Infrared
diodeReceiver Infrared receiverCAN-Bus jacks
RJ45 2Protection category IP 30 to EN 60
529Temperature range 0 C to 55 C
Operating humidity range5 to 95 relative
humidity, non-condensingWxHxD 80 x 28 x 40
mmColour RAL 9005/7035
177030.130CMC III vandalism sensor with
CAN-BusThe sensor measures and monitors the
acceleration in three axes x, y and z. The
position of the enclosure is also monitored, e.g.
when an enclosure has fallen over.Technical
specificationsMode of operation Acceleration
sensorMonitoring x, y and z axisMeasuring
range -2/4/8 to 2/4/8 gResolution 0.1 g
CAN-Bus jacks RJ45 2Protection category IP 30
to EN 60 529Temperature range 0 C to 55
C Operating humidity range5 to 95 relative
humidity, non-condensingWxHxD 80 x 28 x 40
mmColour RAL 9005/7035
187030.140CMC III analog airflow sensor with
CAN-BusThe sensor measures and monitors the
current analog air speed. It can be displayed via
the CMC III. For example, the degree of filter
mat pollution can be displayed over the
respective time period.Technical specifications
of sensorMode of operation Differential
temperature measurement method Rated voltage
24V DCSensor interface 4 to 20 mAMeasuring
range 0.5 to 15 m/sProtection category IP
65Technical specificationsJack for airflow
sensor 1CAN-Bus jacks RJ45 2Protection
category IP 30 to EN 60 529Temperature range
0 C to 55 C Operating humidity range5
to 95 relative humidity, non-condensingWxHxD
110 x 30 x 40 mmColour RAL 9005/7035
197030.150CMC III analogue differential pressure
sensorwith CAN-BusThe sensor is used to monitor
the differential pressure for climate control
applications, e.g. raised floor cooling, cold
aisle containment etc. The sensor has two
measuring points that may be connected via air
hoses to the position, e.g. in the cold
aisle.Technical specificationsMode of
operation Differential pressure sensorPressure
measuring points 2Measuring range -500 to 500
PaCAN-Bus jacks RJ45 2Protection category IP
30 to EN 60 529Temperature range 0 C to
55 C Operating humidity range5 to 95
relative humidity, non-condensingWxHxD 110 x 30
x 40 mmColour RAL 9005/7035
207030.190CMC III universal sensor with CAN-Bus
The sensor has 3 interfacesFirst input
optionally as(digital input / S0Bus /
Wiegand)Second input optionally as(digital
input / S0Bus / Wiegand)Third input as- analog
input 4..20mATechnical specificationsTerminals
for signal 6CAN-Bus jacks RJ45 2Protection
category IP 30 to EN 60 529Temperature range
0 C to 55 C Operating humidity range5
to 95 relative humidity, non-condensingWxHxD
110 x 30 x 40 mmColour RAL 9005/7035
217030.200CMC III CAN-Bus AccessThe unit includes
an infrared access sensor, an interface for a CMC
III reader system and an interface for a door
handle.The infrared access sensor reports if the
enclosure door is open or closed. Codes for
releasing the door may be input via a reader
system. The door can be released with a connected
electrical handle and the door handle be
monitored.Technical specificationsMode of
operation visualTransmitter Infrared
diodeReceiver Infrared receiverInterfaces 1
CMC III readerInterfaces RJ12 1 handleCAN-Bus
jacks RJ45 2Protection category IP 30 to EN 60
529Temperature range 0 C to 55 C
Operating humidity range5 to 95 relative
humidity, non-condensingWxHxD 110 x 30 x 40
mmColour RAL 9005/7035
227030.220CMC III coded lock The coded lock is
suitable for mounting on enclosure doors or next
to a room door. For operating the reader it has
to be connected to the CMC III Processing Unit
via the CMC III CAN-Bus Access 7030.200.The
reader unit is automatically detected by the CMC
II System Processing Unit. With Integral LED for
indicating the status. It releases the doors. By
entering a numerical code, authorisation is
checked in the Processing Unit and a door release
is triggered accordingly.Technical
specificationsNumerical code 00000000 to
99999999 (variable)Numerics 0-9, C,
EnterConnection cable 3 m Protection category
IP 30 to EN 60 529Temperature range 0 C to
55 C Operating humidity range5 to 95
relative humidity, non-condensingColour RAL
9005/7035WxHxD 50 x 190 x 25 mm
237030.230CMC III transponder readerThe
transponder reader is suitable for mounting on
enclosure doors or next to a room door. For
operating the reader it has to be connected to
the CMC III Processing Unit via the CMC III
CAN-Bus Access 7030.200.The reader unit is
automatically detected by the CMC II System
Processing Unit. With Integral LED for indicating
the status. It releases the doors. By
contact-free holding the transponder card in
front of the reader unit, authorisation (UID of
card) is checked in the Processing Unit and a
door release is triggered accordingly. Technical
specificationsTechnology Transponder 13.56
MHzThe following tags can be readISO 14443A
Mifare 1K, Mifare 4K, Mifare Ultralight, Mifare
DESFire, SLE66R35ISO 14,443B AT88RF020, SR176,
SRIX512, SRIX4KISO 15693 I-Code SL2, Tag-it
HF-I, SRF55VxxP, LRI512, EM4135,TempSense (KSW),
Tag-it HF, I-Code SL1, SR176 (²), SLE55Rxx (²,3),
SLE66CL160S.ISO 18000-3Frequency 13.56 MHz
Connection cable 3 m Protection category IP
30 to EN 60 529Temperature range 0 C to
55 C Operating humidity range5 to 95
relative humidity, non-condensingWxHxD 50 x 190
x 25 mmColour RAL 9005/7035