Update - PowerPoint PPT Presentation

About This Presentation
Title:

Update

Description:

Update Review of Laboratory Airflow Control System The Phoenix Controls SYSTEM Innovations in critical environmental control Energy savings applications Saving Energy ... – PowerPoint PPT presentation

Number of Views:298
Avg rating:3.0/5.0
Slides: 62
Provided by: James576
Learn more at: http://streaming.osu.edu
Category:
Tags: control | mind | update

less

Transcript and Presenter's Notes

Title: Update


1
(No Transcript)
2
Update
  • Review of Laboratory Airflow Control System
  • The Phoenix Controls SYSTEM
  • Innovations in critical environmental control
  • Energy savings applications
  • Saving Energy at The Ohio State University
  • A working laboratory?

3
Laboratory Ventilation
4
Laboratory Ventilation Key Issues
  • Safety ! Fume hood containment
  • Room pressurization
  • Speed of response to changes in airflow demand or
    static pressure
  • Air Change Rates
  • Temperature Control
  • Energy Conservation

5
Accel II Venturi Valve
  • Integrates over 30 years of development and
    experience and with over 200 improvements
  • Specially-designed conical diffuser
  • Inlet/Outlet insensitivity
  • Reduced low frequency noise
  • Wide turndown range (up to 201)
  • Precise repeatable positioning
  • No routine maintenance
  • Made in the USA
  • Pneumatic and electric actuators available
  • High speed for critical applications
  • Normal speed for health care and flow tracking
    applications

6
The Phoenix Controls Legacy We Dont Measure
Flow
  • Flow Metering vs. Flow Measuring
  • Flow measuring has a limited range of
    operation.
  • Flow measuring requires long, straight duct runs
    (not available in most applications).
  • Flow measuring is prone to inaccuracies due to
    the caustic nature of laboratory exhaust air
  • Flow measuring has inherent time lags due to
    airflow dynamics
  • Flow measuring requires periodic maintenance

7
Factory Calibration
  • Drastically Reduces Commissioning Time
  • Can be pre-commissioned before supply and exhaust
    air is connected
  • No sensors to set up or flows to adjust
  • No routine maintenance requirements

8
Factory Calibration
9
Pressure Independence
10
What Sets Us Apart
  • Speed of Response SPEED NO
  • No Straight Ductwork Requirements
  • Pressure Independence
  • Ability to Accurately Control at Low Flows
  • No Regular Maintenance Requirements

11
Speed of Response
12
No Straight Duct Runs
13
Intersystem Stability
14
What Sets Us Apart
  • No Routine Maintenance Requirements
  • System continues safe operation
  • System continues to save energy
  • Drastically reduces maintenance cost
  • Saves Money
  • Energy Costs
  • Maintenance Costs

15
Traditional Applications
  • Laboratories
  • One second speed of response
  • Accuracy and turndown
  • Dynamic fume hood face velocity control
  • Accurate room pressurization
  • No routine maintenance requirements
  • Interface to building management system
  • Vivariums

16
Valve Enhancements
  • Shutoff Valve

17
Shut-off Valve
  • Low- or high-speed electric
  • Single and dual valves
  • Available in all classes A, B and C

18
Applications
  • Developed for VHP gaseous decontamination
  • Other opportunities
  • HVAC isolation
  • Canopies
  • Biosafety cabinet shut-down while unoccupied
  • Teaching hoods

19
Low-leakage Shut-off Valve
  • Offered with the standard control features
    expected from Phoenix Controls
  • Zone balance, active pressure, emergency, etc.
  • Maintains quality and precision expected in a
    Phoenix Controls valve
  • Self-balancing, pressure-independent operation
  • 5 accuracy across full range

20
Applications for Low-Leakage Shut-Off Valve
  • Biocontainment
  • Biocontainment spaces
  • BSL-3 and ABSL-3 labs
  • Higher-demand vivariums
  • Life Science
  • Support vivarium BSC spaces

21
Shut-off Leakage (L)
Static Pressure (Pascal)
lt 0.005 CFM10-inch valve!
Static Pressure (in WC)
22
Cone Assembly
  • Pressed-fit to cone assembly
  • Gasket material
  • Class A Neoprene
  • Class B and C Viton

23
Benefits of Low-Leakage Shut-Off Valve
  • Lower-cost alternative to an isolation or
    bubble-tight blade damper
  • Provides a "peace of mind" alternative
  • Supports the future decontamination or isolation
    needs

24
More Valve Enhancements
  • 14-inch Valve

25
Applications
  • Meets industry need for higher airflow
  • Open space life science labs
  • Physical and engineering science labs
  • Operation rooms and surgical suites
  • Large chemistry labs
  • Base platform for our low-pressure offering
  • 200 2500 cfm
  • Single, dual, quad available

26
Active Pressure Monitor
27
Active Pressure Monitor
  • True differential pressure sensor
  • Multiple pressure ranges available
  • Accurate to 0.0005"
  • Audible alarm and mute button
  • Adjustable alarm delay 0-30 seconds
  • Reversible pressure alarms (vivariums)
  • Air valve flow switch alarm indication
  • Form C (SPDT) alarm relay
  • Analog output 4-20 mA or 0-10 volts

28
System Enhancements
  • Traccel/Theris System

29
Airflow
  • Why traditional VAV controls dont work

30
Overview
  • One valve controller with surplus I/O
  • Standard actuator for VAV temperature control
  • Flow tracking with volumetric offset
  • Superior room pressurization and directional
    airflow control

31
Traccel/Theris Room Controller-TP
32
Traccel Tiers
Traccel-TP
Traccel-SO
  • Open space lab
  • Support alcoves
  • Support FH alcoves
  • Lab office
  • Conference room
  • Support alcoves
  • Tracking pair
  • Temp control
  • Room pressure control
  • Tracking pair
  • Isolation mode
  • Shut-off optional
  • Optional Add 2 UI
  • Humidity control
  • Pressure monitoring
  • Supply-only
  • Ducted exhaust
  • No ability to track exhaust

Traccel-TX
  • HVAC isolation
  • Decontamination
  • BSC isolation

33
Solution Pressure-Independent Venturi
  • Zero maintenance
  • Typical 50/hr for HVAC technicians
  • Flow sensors one hour per box
  • Opportunity costs!
  • Potential energy savings
  • Use high turndowns to optimize ventilation rates
  • Example Decrease airflow by 25 CFM/terminal
    unit, 8 hours/day
  • 25 CFM x 7.50 x 8/24 hrs X 62/box/year
  • Cost of incorrect pressurization
  • Annual cost to health care industry 5 billion
  • Research integrity

34
Traccel-TP Multiple Temp Zones
Client Benefits
  • Tracking pair VAV ensures directional airflow
  • Occupancy control
  • Room temperature control
  • HVAC emergency modes
  • Additional TRIAC for floating-point reheat
  • Flexible I/O14 per I/O
  • Humidity control (UI4)
  • Shut-off capability

Traccel controllers working together to maintain
accurate pressure control
35
Traccel-TX BSC Alcove
Benefits
  • Tracking pair VAV ensures directional airflow
  • Occupancy control
  • Room temperature control
  • HVAC emergency modes
  • Additional TRIAC for floating-point reheat
  • Flexible I/O14 per I/O
  • Humidity control (UI4)
  • Shut-off capability

Flexibility to accommodate decontamination in the
future or shut-down when not in use
36
Traccel/Theris
  • LonMark Certified BACnet Interface
  • No flow sensors to maintain
  • True pressure-independence
  • High turndown ratios save energy
  • Factory characterized valves reduces
    commissioning time
  • Flexibility to more easily handle space
    reconfigurations

37
Energy Saving Products and Applications
  • What does One (1) CFM of Single Pass Air cost
    to heat and cool at The Ohio State University?

38
U.S. Short-term Energy Outlook
U.S. Energy Nominal Prices for Industrial Sectors
  • Electricity (end use prices)
  • 4.7 cents per/KW/Hr (1994)
  • 4.9 cents per/kW/Hr (2002)
  • 6.5 cents per/kW/Hr (2008)

EIA data - http//www.eia.doe.gov/steo
39
U.S. Short-term Energy Outlook
U.S. Energy Nominal Prices for Industrial Sectors
  • Natural gas (end use prices)
  • 3.75 per/MCF (1994)
  • 4.02 per/MCF (2002)
  • 8.65 per/MCF (2008)

MCF Thousand Cubic Feet EIA datahttp//www.eia.
doe.gov/steo
40
Laboratory Operating Costs
  • Utility rates cost of CFM
  • Lawrence Berkley National Laboratorys
    "Laboratory Fume Hood Energy Model"
  • Phoenix Controls LabPro software
  • Calculate /CFM
  • Annual cost per CFM to condition and move 100
    exhaust air

LBNL datahttp//fumehoodcalculator.lbl.gov
41
What Can Be Done?
  • 6 energy saving trends in Laboratory Airflow
    Controls
  • Usage Based Controls
  • Fume hood decommissioning
  • Energy waste alert
  • Unoccupied settings
  • IAQ control ventilation

42
Proven Energy Saving Concepts
43
Usage Based Controls
44
Lab Usage Patterns
Usage Based Controls
  • 24-hour operation
  • 100 outside air (no recirculation)
  • Hood occupancy in short segments
  • Total hood usage typically one hour per day and
    independent
  • Sash management varies widely

45
Zone Presence Sensor
Usage Based Controls
  • Available since the mid-1990s
  • One ZPS per 8' hood
  • Can be used in series for wider hoods
  • Field programmable via a USB port
  • Detection zone
  • Setback times and values
  • Lighting adjustments
  • Motion sensitivity

46
Usage Based Controls
47
Building Energy Costs Sample
UBC
Control Method CFM Energy Costs Savings
CV 100,000 750,000 0
VAV 59,000 442,500 307,500
UBC 42,600 319,500 430,500
If all sashes are left open If all sashes are left open If all sashes are left open If all sashes are left open
VAV 100,000 750,000 0
UBC 67,200 504,000 246,000
Annual cost per CFM 7.50
48
Sample Building Energy Costs
UBC
49
Fume Hood Decommissioning
50
Concept
Fume Hood Decommissioning
  • Ability to reduce or turn off fume hood exhaust
    when not in use
  • Potential for huge energy savings
  • Teaching labs or hoods rarely used
  • Buildings not occupied
  • Understaffed research facilities
  • Valve options
  • Valve minimum (i.e., 90 CFM)
  • Shut-off Valves (i.e., 0-5 CFM)

51
Function and Operation
Fume Hood Decommissioning
  • Can be initiated by
  • Fume Hood Monitor
  • Button sequence
  • External key switch
  • BMS command
  • Ensures safety
  • Sash must be fully closed to initiate mode
  • Mode is automatically exited if sash is opened

52
Additional Product Info
FHD
  • Features
  • Annunciated at FHM with "OFF" displayed
  • Reportable point to BMS
  • Allowed under current guidelines/standards
  • NFPA 45
  • ANSI/AIHA Z9.5
  • Patent pending

53
Energy Waste Alert
54
Concept and Operation
Energy Waste Alert
  • Notification when sash is left open and lab
    lights are off
  • Features
  • Light sensor incorporated in monitor
  • Provides audible alarm
  • Displays "EnrG" on monitor
  • Reminder to close the sashes at night

55
Unoccupied Settings
56
Unoccupied Settings
  • Celeris, Theris and Traccel digital platforms
  • Lower ACH
  • Relaxed temperature control
  • Triggered locally or via BMS schedule
  • Retrofit existing analog systems
  • Lower ACH

57
GEX Shut-off
58
Function and Operation
GEX Shut-Off
  • Required exhaust flow must be sufficient to
    maintain room level offset
  • Must be maintained for at least 1 minute
  • Comes out of shut-off when exhaust demand
    increases

59
IAQ Control
60
Two Ventilation Concepts
IAQ Control
  • Air change rates
  • Reduce minimum ACH when air is "clean"
  • Drive to higher ACH when contamination is detected

61
Lab Application Next Generation VAV Control
  • Lab Multi-parameter DCV Dynamic control of min.
    ACH
  • Now all three factors affecting lab airflow can
    be varied
  • Significantly cuts energy first cost, while
    enhancing safety

Constant
6-12 ACH 10-20 ACH
Significant energy waste
VAV
VAV
VAV
Ventilation rate (cfm)
Hoods
2- 4 ACH 6-8 ACH
vivariums
Thermal Load
ACH / Dilution Requirement
62
Function and Operation
IAQ Control
  • Input from OptiNet system to Laboratory Airflow
    Control System.
  • Applications in laboratories, vivariums,
    classroom buildings throughout campus
  • Significant Retrofit Opportunities

63
A New Approach OptiNet Multiplexed Facility
Monitoring
  • OptiNet routes multiplexed air samples to central
    sensors
  • Integrated into BMS for monitoring control

Web Based User Interface
64
OptiNet A Facility Wide Sensing Infrastructure
3rd Party Analysis
65
Sensed Parameters
  • Air Cleanliness
  • Total Volatile Organic Compounds
  • Includes ammonia
  • Particles laser based particle counter
  • Carbon Monoxide (CO)
  • Comfort Ventilation
  • Temperature
  • Humidity or Dewpoint
  • Carbon Dioxide (CO2)

66
Lab Monitoring Also Helps Ensure Lab Safety
  • Validates the safe operation of a lab
  • Detect improper bench use of chemicals
  • Detect poorly containing fume hoods
  • Spills rogue reactions rapidly sensed
  • Check lab pressurization, T RH
  • Validates safe IEQ room conditions for animals
  • Allows for safer lab airflow control
  • Increased hood capture from reduced drafts
  • Drops room flows when dilution not needed
  • Greater dilution provided for spills, leaks, etc.
  • 12 to 15 ACHs can be provided automatically
  • Sources of leaks emissions can be found
  • With fact based data, source controls can be used

67
OptiNet Architecture
OptiNet Structured Cable
Air Data Router
Room Sensor
Sensor Suite
Outdoor Air Probe
Air Packets are Routed then Sensed
Vacuum Pump
68
OptiNet Architecture
OptiNet Structured Cable
Air Data Router
Room Sensor
Sensor Suite
Outdoor Air Probe
Air Packets are Routed then Sensed
Vacuum Pump
69
OptiNet Architecture
OptiNet Structured Cable
Air Data Router
Room Sensor
Sensor Suite
Outdoor Air Probe
Air Packets are Routed then Sensed
Vacuum Pump
70
OptiNet Architecture
  • The OptiNet Advantage
  • Lower Installed Costs
  • Lower Operating Costs
  • Assured Energy Savings
  • Healthier Environment

OptiNet Structured Cable
Air Data Router
Room Sensor
Sensor Suite
Outdoor Air Probe
Air Packets are Routed then Sensed
Vacuum Pump
71
Cost Effective LEED NC Points
  • Energy Atmosphere up to 4 pts.
  • EA - 1 Optimize energy up to 4 pts.
  • IEQ potential 3 pts.
  • EQ - 1 Permanent CO2 / O.A. Monitoring
  • EQ - 3.2 Construction IAQ Mgmt Plan
  • EQ - 7.2 Permanent Comfort Monitoring
  • Innovation in Design potential 2 pts.
  • IEQ monitoring point
  • Exceeds EQ 1- CO2 Monitoring
  • Real time commissioning point
  • Exceeds EA 3 Additional Commissioning

Potential of up to 9 LEED NC points
72
Arizona State University, Biodesign-BAircuity
Pilot Project
73
ASU Biodesign-B Energy Savings w/ Aircuity
74
ASU Biodesign-B Energy Savings w/ Aircuity
75
What it all means
  • Like most life-sciences labs, the airflows in
    Biodesign-B are primarily ventilation driven.
  • Most labs in Biodesign-B are over-ventilated
  • Average ventilation flows can be safely reduced
    by gt50 when monitoring air cleanliness and
    responding to spills, etc.
  • There are HUGE energy savings with FAST payback!
  • Several other soft benefits too!
  • Safer hood operation
  • Quieter labs
  • Documented performance

76
BACnet Integration
  • Via Macro or MicroServer

77
OSU Energy Initiative?
20 Energy Savings?
78
Constant Volume DesignWhat Can Be Done?
  • Nothing
  • Constant Volume Fume Hood
  • Tracking Exhaust/Supply
  • Occupied/Unoccupied
  • Reset on Air Quality
  • Two Position fume Hood Control
  • Sash Switch
  • Usage Based Controls
  • Variable Volume Fume Hood Control

79
New Smart Fan Control
  • Assures safe dilution and plume height
  • Reduces exhaust system horsepower
  • Significant Energy Savings

80
Integration Options
81
Aircuity Biodesign-B Pilot Original Financials
  • ASU avg. annual /CFM 5.14
  • Supply CFM reduction
  • Occ CFM UnOcc CFM
  • Current 16,000 16,000
  • Proposed 5,200 5,200
  • Saved CFM 10,800 (67)
    10,800 (67)
  • Year 1 energy savings 55,300
  • Project price 49,000
  • Payback period lt 11 months

82
A Working Laboratory
  • How Do you Define a Working Lab?

83
A Working Laboratory
  • What checkpoints are in place to assure that labs
    are working?
  • Are specifications being met?
  • What are the consequences?
  • What documentation of performance is required?
  • Who suffers if the specification is not met?

84
Laboratory Recommissioning
  • Documents laboratory performance
  • Fume hood face velocities
  • Lab pressurization
  • Energy Usage
  • Identifies Energy Savings Opportunities
  • Airflow reduction
  • Static pressure reduction
  • Other opportunities

85
Our Commitment
  • Superior system performance
  • Local, factory certified technicians starting up
    each project
  • Full commissioning of each system
  • Airflow checked for each laboratory condition
  • We strive to make system fail instead of the
    easy route to pass.
  • Contractor Support
  • Three year warranty on all equipment
  • Project budget is maintained

86
Advantages of Working Directly
  • Ductwork can be laid out to minimize excess
    straight runs and reduce sound.
  • Full direct accountability to the owner and
    engineer
  • A second set of eyes on the project
  • Energy goals will be met
  • No excuses or costly change orders
  • System will perform as designed and work
    flawlessly

87
Vivarium Applications
  • FSR

88
Vivarium Applications
FSR
  • Air change rates determined quality of air
  • TVOCs including ammonia
  • Particulates
  • Significant savings
  • Capital Costs
  • Energy Savings
  • Space Flexibility
  • Many benefits to vivarium staff

89
Concept and Operation
FSR
  • Phoenix to release an optional kit to be
    installed on a valve, then monitor the static
    drop across a valve continually
  • Value passed to BMS
  • BMS to monitor all readings to "low select"
  • BMS can reset fan static set point

90
Additional Product Info
FSR
  • Selection of best valves from plans is key
  • Phoenix to release as option
  • Either installed on valve
  • Sold as separate kit
  • Remembera reduction in CFM will save far more
    energy than a reduction in static
  • (Refer to white paper, "What is the true cost of
    static pressure?"

91
Our Next Step?
  • Thank You
Write a Comment
User Comments (0)
About PowerShow.com