Title: HVAC
1HVAC
- HEATING
- COOLING
- VENTILATION
2Human Comfort Zone
- As humans we try to maintain a body
- temperature of 98.6 F
- Three Mechanisms
- Heat generated within the body
- Heat gained from surroundings
- Heat lost to surroundings
3Human Comfort Zone
- We shiver to
- generate heat
4Human Comfort Zone
- We sweat to
- Give off heat
5Human Comfort Zone
6Human Comfort Zone
- Blood Flow
- Decreases to hands and feet in winter
- Increase in summer to encourage heat loss
7Thermal Neutrality
- To be comfortable humans must loose heat at the
same rate as it is produced or gained.
8Factors Affecting Human Comfort
- Air temperature
- Air Speed
- Humidity
- Mean radiant temperature
- Each has a direct influence on heat loss or gain
to the human body
9Factors Affecting Human Comfort
- Air Temperature - This affects temperature
differences between the body and the
surroundings, consequently affecting the rate of
heat loss or gain by convection.
10Factors Affecting Human Comfort
- Air Speed - This affects the rate at which
- the body loses heat by convection.
- An air temperature of 35F and a wind speed of 20
miles/hour combine to give a wind chill
temperature of 11.2F. - Air speed is also very important during summer
when the body is trying to lose heat to maintain
comfort.
11Factors Affecting Human Comfort
- Humidity - Affects the rate at which the
- body loses heat by evaporation. During hot
- weather, high humidity increases discomfort
- by making it more difficult to evaporate
- perspiration into the air.
12Mean Radiant Temperature
- Mean Radiant Temperature' (MRT). This is defined
as the temperature of a sphere at the point in
question which would exchange no net radiation
with the environment.
13Factors Affecting Human Comfort
- Mean Radiant Temperature (MRT) - MRT is the
average surface temperature of the surroundings
with which the body can exchange heat by radiant
transfer. - Radiant heat transfer to and from the body is
quite apparent when sitting near a fireplace
(high MRT) or large cold window area (low MRT).
14Mean Radiant Temperature
- In general for every 1 degree F that the MRT
drops, the air temperature must be raised about
1.4 degrees F to achieve comfort conditions. - How can you raise the MRT?
- Close blinds and curtains
- Solar Film on windows
- Seal heat leaks
15Comfort
- Comfort is achieved by either increasing the
ambient temperature or by raising the mean
radiant temperature of an environment. - A higher radiant temperature means that people
become comfortable with a lower ambient
temperature and the reverse is also true.
16Bioclimate Chart
17Example 1
- Dry Bulb 73
- Relative Humidity 50
18In the zone
19Example 2
- Dry Bulb Temp. 78
- Relative Humidity 70
20(No Transcript)
21Example 2
- Dry Bulb Temp. 78
- Relative Humidity 70
- Requires a wind speed of 250 FPM
- (25060)/5280
- MPH 2.84
22Example 3
- Dry Bulb Temp. 50F
- Relative Humidity 55
23(No Transcript)
24Example 3
- Dry Bulb Temp. 50F
- Relative Humidity 55
- BTU/Hour 250
25(No Transcript)
26Definitions
- Conduction
- A method by which heat is transferred from a
warmer substance to a cooler substance by
molecular collisions. Direct contact. - Convection
- A method by which heat is transferred by
currents in a liquid or gas. - Radiation
- A method by which heat can be transferred
through objects and empty space. Electromagnetic.
27Conduction Examples
- Liquid - Liquid - Pouring cold cream into coffee
- Liquid - Gas - Ocean and Atmosphere
- Gas - Gas Cold and warm weather systems mixing
- Solid - Solid Touch a hot pot on a stove
28Conduction Rate Factors
- Contact Area
- Type of Material Cast Iron vs Stainless Steel
- Temperature Difference
- Distance heat must travel
29Convection Examples
- In a closed room cool air will settle to the
bottom while warm air will rise - Bowl of soup Hot liquid in the center moves to
the cooler outside where it drops and is reheated
at the center and the cycle continues. - Warm air rising through a heat register
30Radiation Examples
- The suns heat
- A bonfire
- Warm soil on a cool night
31Radiation Rate Factors
- Surface area
- Type of material
- Temperature difference
32More Radiation Terms
- Reflectance (or reflectivity) refers to the
fraction of incoming radiant energy that is
reflected from the surface. Reflectivity and
emissivity are related and a low emittance is
indicative of a highly reflective surface. - For example, aluminum with an emittance of 0.03
has a reflectance of 0.97.
33More Radiation Terms
- Emittance (or emissivity), refers to the ability
of a materials surface to give off radiant
energy. All materials have emissivities ranging
from zero to one. The lower the emittance of a
material, the lower the heat radiated from its
surface.
34Emissivity or Emittance
Material Surface Emittance
Asphalt 0.90 - 0.98
Aluminum foil 0.03 0.05
Brick 0.93
Fiberglass 0.80 0.90
Glass 0.95
Steel 0.12
Wood 0.90
35R-Value
- R-Value is the measure of resistance to heat flow
through the defined material. The higher the
R-Value the less heat will transfer through the
wall, making the system more energy efficient. - U-Value is the reciprocal of the R-Value
- (1/R) and is a measure of the rate of heat loss
36WINDOWS - 4 Ways to Evaluate
- U-FACTOR
- Solar Heat Gain Coefficient
- Visible Transmittance
- Air Leakage
37U-FACTOR
U-FACTOR The rate of heat loss is indicated in
terms of the U-Factor of a window assembly. The
insulating value is indicated by the R-Value
which is the inverse of the U-Value. The lower
the U-Value the greater a windows resistance to
heat flow and the better the insulating value.
38Solar Heat Gain COEFFICIENT
The SHGC is the fraction of incident solar
radiation admitted through a window. SHGC is
expressed as a number between 0 and 1. The lower
a windows solar heat gain coefficient, the less
solar heat it transmits.
39VISIBLE TRANSMITTANCE
The visible transmittance is an optical property
that indicates the amount of visible light
transmitted. Theoretical values vary between 0
and 1, but most values are between 0.3 and 0.8
40Air Leakage
Heat loss and gain occur by infiltration through
cracks in the window assembly. Air leakage is
expressed in cubic feet of air passing through a
square foot of window area. .3 is recommended
for Oregon
41Low-E Windows
- Glass is coated with silver or tin oxide which
allows visible light to pass through but reflects
infrared heat radiation back into the room. - Reduces heat loss
- Allows visible light to pass through but reflects
infrared heat radiation away from the room - Reduces heat gain
42High number for cold climate. Low number for warm
climates
The lower the number the better the insulating
value
The best windows have air leakage rating between
0.1 and 0.6 cfm/ft.
Varies from 0 to 1.0 The higher the the more
light is transmitted.
43Single-Glazed with Clear Glass
44Single-Glazed with Bronze or Gray Tinted Glass
45Double-Glazed with High-Solar-Gain Low-E Glass,
Argon/Krypton Gas
46Triple-Glazed with Moderate-Solar-Gain Low-E
Glass, Argon/Krypton Gas
47Ventilation
- Multi Point Fan Systems
- One fan located in the attic
- Connects to baths and kitchen
- Timed to run at high speed during high use times
such as morning (showers, bacon ) and evening. - Xvent
48Heat Recovery Ventilation
- How it works
- In the heating season the core transfers heat
from the outgoing, stale household air to preheat
the incoming, fresh air. - Cross-current sections, ensure the two air
streams are always kept separate preventing the
incoming fresh air from being contaminated by the
outgoing stale air.
49Heat Recovery Ventilation
- During the air-conditioning season, the HRV
reverses this process, removing some of the heat
from the incoming air and transferring it to the
outgoing air.
50Heat Recovery Ventilation
51Ventilation
- Heat Recovery System - uses fans to maintain a
low-velocity flow of fresh outdoor air into the
building (incoming air stream) while exhausting
out an equal amount of stale indoor air (exhaust
air stream). Fresh air is supplied to all levels
of the building while stale air is removed from
areas with high levels of pollutants and moisture.
52Ventilation
- Heat Recovery System
- Air Exchange - Expels stale, polluted indoor air
and gaseous pollutants and continually exchanges
them with a continuous flow of fresh, revitalized
outdoor air to improve Indoor Air Quality.
53Ventilation
- Heat Recovery System
- Excess Humidity Control - Helps prevent
uncontrolled excess humidity by expelling excess
humidity from the air, thereby reducing the risk
of window condensation, mildew and mold, which
prevents structural damage and deterioration to
your home.
54Ventilation
- Heat Recovery System
- Heat Recovery Core - As warm air is expelled from
your house, it warms the incoming cold, fresh air
before its circulated throughout your home. The
result is a constant supply of fresh air, no
unpleasant drafts and greater home comfort.
55HRV
56HRV
- Sized to ventilate the entire house at a minimum
of .35 air changes per hour. - Minimum CFM requirement can be calculated as
follows - Determine square footage and multiply times
ceiling height. - Divide by 60 minutes
- Multiply times .35 (minimum air changes)
57HRV Calculation
- Example
- Determine square footage and multiply times
ceiling height. - Divide by 60 minutes
- Multiply times .35 (minimum air changes)
58HRV
- Calculate the minimum CFM for a home
- with 2000SF main level, 1000SF second level
and 750 SF finished basement - Note Main and second level have 9 foot
- ceilings and basement has 8 foot
- ceiling.
59Solution
- 3000 SF x 9 27000
- 750 x 8 6000
- Total 33000
- 33000/60 550
- .35 x 550 192.5 CFM
60HEPA Filter
High Efficiency Particulate Air Filter
61Energy Recovery Ventilators
62How are HRVs Installed?
63How are HRVs Installed?
64How are HRVs Installed?
65Radiant Floor Heat
- Three types
- Radiant Air Floors
- Electric Radiant Floors
- Hot Water (Hydronic)
66Radiant Floor Heat
- Types of installation
- Wet Installations
- Large thermal mass of a concrete slab floor
- lightweight concrete over a wooden subfloor
-
- Dry Installations
- Where the installer "sandwiches" the radiant
floor tubing between two layers of plywood or
attaches the tubing under the finished floor or
subfloor.
67Radiant Floor Heat
- Air Heated Radiant Floors Not recommended for
residential applications - Electric Radiant Floors -
68Electric Radiant Heat - Wet Installation
69Wet Installation
70Wet Installation
71Dry Installation
72Dry Installation
73Hydronic Radiant Heat
74Wet Installation
- PEX piping in Concrete (thick slab)
75Wet Installation
- Thin Slab Application Gypcrete over plywd
76Electric Toe Kick Heat
77Toe Kick Electric Heat
78Heat Pump and Furnace
Indoor Cooling Coil
Thermostat
Furnace
Heat Pump
Air Cleaner
79Heat Pump and Air Handler
Thermostat
Air Handler
Heat Pump
Air Cleaner
80Air Conditioner and Furnace
Thermostat
Indoor Cooling Coil
Air Cleaner
Air Conditioner
Furnace
81Air Conditioners and Air Handlers
Thermostat
Air Handler
Air Conditioner
Air Cleaner
82Cooling
83(No Transcript)