A'C' Circuit Analysis - PowerPoint PPT Presentation

1 / 74
About This Presentation
Title:

A'C' Circuit Analysis

Description:

Equivalent a.c. as compared to d.c. was sought. While the average of an a.c. signal is zero (verify), it is ... 1. On the same Argand diagram; sketch V & i. ... – PowerPoint PPT presentation

Number of Views:54
Avg rating:3.0/5.0
Slides: 75
Provided by: t4taf
Category:

less

Transcript and Presenter's Notes

Title: A'C' Circuit Analysis


1
A.C. Circuit Analysis
  • Bigger generator produce a.c.
  • Hence needless to change from d.c. to a.c.
  • Equivalent a.c. as compared to d.c. was sought.
  • While the average of an a.c. signal is zero
    (verify), it is practically true that an a.c.
    current causes heat dissipation in a resistor.

2
Average Power
a.c. circuit
2
3
Average Power
  • Instantaneous power
  • Average power

4
Average Power

5
Average Power
6
Average Power
7
d.c. equivalent circuit power
d.c. circuit
-
8
d.c. equivalent power
  • Average power

9
Root-Mean-Square value
10
Root-Mean-Square value
  • r,m,s. value of
  • Or


11
Root-Mean-Square value
12
Root-Mean-Square value
13
r.m.s value of a.c. signal
  • r.m.s value
  • Example
  • Domestic supply
  • 240V, 50Hz

14
r.m.s value of a.c. signal
15
(No Transcript)
16
Power Factor
  • The load is NOT purely resistive

17
Power Factor
18
Power Factor
  • Most industrial loads are inductive

19
Power Factor
i

-
20
Power Factor
  • Let

21
Power Factor
  • Exercise
  • Clearly, i is a complex number.
  • 1. On the same Argand diagram sketch V i.
  • 2. Consider the phase angle between V i
    analyse its value as L and/or w change.

22
Power factor
  • Results
  • 1. i lags V (or V leads i) by an angle called a
    phase angle
  • 2. The phase angle is a function of the product
    wL.
  • 3. Cosine of the angle is called the power factor

23
Power factor
  • The power factor is a tool used in power
    analysis Its value indicated how inductive a
    circuit is.
  • Exercise
  • On the same phasor diagram draw the real power,
    apparent power reactive power.

24
Real, Apparent Reactive Power
Im
V
P1
Re
?
?
i
P Apparent power
P1 Real power
P2
P2 Reactive power
P
25
Real Apparent Power
  • It is clear that the Apparent Power is bigger
    than the real reactive power.
  • In reality the reactive power is stored
    released from the L every half cycle. It has no
    practical usage,
  • The Real Power is the one doing the intended work
    we wish it to be as high as possible.

26
Power Factor Correction
  • In order to decrease the Reactive Power the
    phase angle is decreased.
  • This is easily checked from the drawing below. It
    is clear that Real Power is not changed but the
    Apparent Power is also reduced in the exercise.
  • The decrease of the phase angle is called Power
    Factor Correction

27
Power Factor Correction
  • If we add a current I such that it is purely
    imaginary. Hence I leads the ref phasor (V) by 90
    deg. The vector sum will be
  • Interestingly note that the magnitude of the new
    current is smaller than the old. This provides
    useful practical results.

28
Power Factor Correction
Im
I
II
P1
Re
V
O
i
P22
Pn
P Apparent power
P1 Real power
P2 Reactive power
P2
P
P22 New Reactive Power
Pn New Apparent Power
I Current to reduce Reactive Power
29
Power Factor Correction
  • It is of engineering interest to correct the
    power factor the reasons are
  • 1. The useless Reactive Power is reduced
  • 2. The Apparent Power is reduced hence more
    power is available from source (for other users).
  • 3. The Real Power is NOT changed load remains
    unaffected.

30
Power Factor Correction
  • Let us have a current lagging the voltage by an
    angle ? take the voltage as the reference
    phasor.
  • i(t) I cos(wt?)
  • The r.m.s. value can be obtained from the
    previous method of comparison with the power
    dissipated in R.

31
Power Factor Correction
  • Exercise
  • Let the current in an inductive circuit be given
    by
  • i(t) I cos(wt ?).
  • Consider the power dissipated in R and equate it
    to an equivalent amount of power dissipated in R
    of a purely resistive load R. Find the r.m.s
    value.

32
Power Dissipated in R
  • Exercise Find the r.m.s. value of
  • i(t) Icos(wt ?)
  • Solution
  • T 2p/w
  • The instantaneous power dissipated in R is

33
Power Dissipated in R
34
Power Dissipated in R
35
Power Dissipated in R
36
Power Dissipated in R
37
Power Dissipated in R
  • The above finding shows that the r.m.s. value is
    not dependent on the angle (lag or lead).
  • Hence we shall use the r.m.s. values without any
    further calculations.

38
Average Power in r.m.s values
  • We can therefore consider the average power
    absorbed as
  • P ½VI cos?
  • Where ? is the phase angle between v(t) i(t)
    and V I are the peak values of the sinusoidal
    signals. i.e.
  • v(t) Vcos(wt)
  • i(t) Icos(wt-?)

39
Average Power in r.m.s values
  • Clearly, the r.m.s. values of v(t) i(t) are
    (V/v2) (I/v2).
  • Since i(t) lags v(t) the average power absorbed
    is
  • P (V/v2) (I/v2)cos?
  • ½VIcos?

40
Average Power in r.m.s values
  • But alternatively, and better still, if we
    considered the r.m.s. values
  • P VIcos?
  • Where V I are the r.m.s. values.
  • Since the r.m.s. values are the ones normally
    stated (NOT the peak values), we shall use the
    r.m.s values only.

41
Practical Example pf correction
  • A 2kW motor with 0.8 power factor (lag) is
    connected to 415V, 3-phase, 50Hz power supply.
    Determine the current drawn by the motor. It is
    required to improve the pf to 0.9 (lag) by
    connecting a capacitor in parallel with the
    motor. Determine the size of capacitor, the new
    current drawn and the reduced volt-amperes.

42
Practical Example pf correction
  • Solution

I
415V
2 kW
50Hz
0.8 p.f
43
Practical Example pf correction
  • The solution requires the connection of a
    capacitor as shown below
  • Let the currents be as shown
  • I new current from supply
  • I original current from supply (which still
    goes to the motor)
  • i current drawn by the capacitor

44
Practical Example pf correction
  • Solution

I
I
i
415V
2 kW
C
50Hz
0.8 p.f
45
Practical Example pf correction
  • Let V supply voltage ref phasor.
  • P VI cos? 2000
  • cos? 0.8
  • V 415 0
  • w 2.p.50 100p

46
Practical Example pf correction
47
Practical Example pf correction
48
Practical Example pf correction
V
C
49
Practical Example pf correction
50
Practical Example pf correction
51
Practical Example pf correction
  • Phasor diagram

V
I
52
Practical Example pf correction
53
Practical Example pf correction
54
Practical Example pf correction
55
Practical Example pf correction
56
Practical Example pf correction
57
Practical Example pf correction
58
Practical Example pf correction
59
Practical Example pf correction
  • N.B. The reduced Volt-amperes can be used to
    supply another load.
  • Note The capacitor is used to reduce the
    current and yet the power ( and current) to the
    load remains unaltered.

60
Practical Example 2 (Supply line losses)
  • A large consumer of 30 kW is supplied power at
    o.5 p.f, and 240 V, 50Hz. The supply wires have
    resistance of 0.001 per km. If the source is
    located 200km away, determine (i) the source
    voltage
  • (ii) The line losses.
  • (b) In order to improve the system the p.f is to
    be increased to 0.85 by a capacitor bank
    connected in parallel with the load.

61
Practical Example pf correction
  • Determine the improvement i.e.
  • reduction is VA
  • reduction in line losses.

62
Practical Example pf correction
  • Let ref phosor be voltage at the load.

63
Practical Example pf correction
64
Practical Example pf correction
  • (iii) The line losses

65
Practical Example pf correction
R
30kW
C
0.5 pf.
66
Practical Example pf correction
  • (b)

67
Practical Example pf correction
68
Practical Example pf correction
69
Practical Example pf correction
V
70
Practical Example pf correction
71
Practical Example pf correction
  • Reduction in line losses

72
Practical Example pf correction
  • It is clear that the improvement in p.f. has two
    advantages
  • (i) Reduces the supplied VA so that the balance
    is used to supply other consumers.

73
Practical Example pf correction
  • (iii) Reduces the line losses which
    is just a wastage to supplier.
  • Hence most power supply company give a penality
    charge called Maximum Demand (MD) charge so that
    the consumer is persuaded to improve the p.f.

74
Practical Example pf correction
  • The present load shedding in Uganda could
    probably be reduced if industries improved their
    p.fs. However, the biggest load on supply
    network is domestic which is resistive.
Write a Comment
User Comments (0)
About PowerShow.com