Title: A'C' Circuit Analysis
1A.C. Circuit Analysis
- Bigger generator produce a.c.
- Hence needless to change from d.c. to a.c.
- Equivalent a.c. as compared to d.c. was sought.
- While the average of an a.c. signal is zero
(verify), it is practically true that an a.c.
current causes heat dissipation in a resistor.
2Average Power
a.c. circuit
2
3Average Power
- Instantaneous power
- Average power
4Average Power
5Average Power
6Average Power
7d.c. equivalent circuit power
d.c. circuit
-
8d.c. equivalent power
9Root-Mean-Square value
10Root-Mean-Square value
11Root-Mean-Square value
12Root-Mean-Square value
13r.m.s value of a.c. signal
- r.m.s value
- Example
- Domestic supply
- 240V, 50Hz
14r.m.s value of a.c. signal
15(No Transcript)
16Power Factor
- The load is NOT purely resistive
17Power Factor
18Power Factor
- Most industrial loads are inductive
19Power Factor
i
-
20Power Factor
21Power Factor
- Exercise
- Clearly, i is a complex number.
- 1. On the same Argand diagram sketch V i.
- 2. Consider the phase angle between V i
analyse its value as L and/or w change.
22Power factor
- Results
- 1. i lags V (or V leads i) by an angle called a
phase angle - 2. The phase angle is a function of the product
wL. - 3. Cosine of the angle is called the power factor
23Power factor
- The power factor is a tool used in power
analysis Its value indicated how inductive a
circuit is. - Exercise
- On the same phasor diagram draw the real power,
apparent power reactive power.
24Real, Apparent Reactive Power
Im
V
P1
Re
?
?
i
P Apparent power
P1 Real power
P2
P2 Reactive power
P
25Real Apparent Power
- It is clear that the Apparent Power is bigger
than the real reactive power. - In reality the reactive power is stored
released from the L every half cycle. It has no
practical usage, - The Real Power is the one doing the intended work
we wish it to be as high as possible.
26Power Factor Correction
- In order to decrease the Reactive Power the
phase angle is decreased. - This is easily checked from the drawing below. It
is clear that Real Power is not changed but the
Apparent Power is also reduced in the exercise. - The decrease of the phase angle is called Power
Factor Correction
27Power Factor Correction
- If we add a current I such that it is purely
imaginary. Hence I leads the ref phasor (V) by 90
deg. The vector sum will be - Interestingly note that the magnitude of the new
current is smaller than the old. This provides
useful practical results.
28Power Factor Correction
Im
I
II
P1
Re
V
O
i
P22
Pn
P Apparent power
P1 Real power
P2 Reactive power
P2
P
P22 New Reactive Power
Pn New Apparent Power
I Current to reduce Reactive Power
29Power Factor Correction
- It is of engineering interest to correct the
power factor the reasons are - 1. The useless Reactive Power is reduced
- 2. The Apparent Power is reduced hence more
power is available from source (for other users). - 3. The Real Power is NOT changed load remains
unaffected.
30Power Factor Correction
- Let us have a current lagging the voltage by an
angle ? take the voltage as the reference
phasor. - i(t) I cos(wt?)
- The r.m.s. value can be obtained from the
previous method of comparison with the power
dissipated in R.
31Power Factor Correction
- Exercise
- Let the current in an inductive circuit be given
by - i(t) I cos(wt ?).
- Consider the power dissipated in R and equate it
to an equivalent amount of power dissipated in R
of a purely resistive load R. Find the r.m.s
value.
32Power Dissipated in R
- Exercise Find the r.m.s. value of
- i(t) Icos(wt ?)
- Solution
- T 2p/w
- The instantaneous power dissipated in R is
33Power Dissipated in R
34Power Dissipated in R
35Power Dissipated in R
36Power Dissipated in R
37Power Dissipated in R
- The above finding shows that the r.m.s. value is
not dependent on the angle (lag or lead). - Hence we shall use the r.m.s. values without any
further calculations.
38Average Power in r.m.s values
- We can therefore consider the average power
absorbed as - P ½VI cos?
- Where ? is the phase angle between v(t) i(t)
and V I are the peak values of the sinusoidal
signals. i.e. - v(t) Vcos(wt)
- i(t) Icos(wt-?)
39Average Power in r.m.s values
- Clearly, the r.m.s. values of v(t) i(t) are
(V/v2) (I/v2). - Since i(t) lags v(t) the average power absorbed
is - P (V/v2) (I/v2)cos?
- ½VIcos?
40Average Power in r.m.s values
- But alternatively, and better still, if we
considered the r.m.s. values - P VIcos?
- Where V I are the r.m.s. values.
- Since the r.m.s. values are the ones normally
stated (NOT the peak values), we shall use the
r.m.s values only.
41Practical Example pf correction
- A 2kW motor with 0.8 power factor (lag) is
connected to 415V, 3-phase, 50Hz power supply.
Determine the current drawn by the motor. It is
required to improve the pf to 0.9 (lag) by
connecting a capacitor in parallel with the
motor. Determine the size of capacitor, the new
current drawn and the reduced volt-amperes.
42Practical Example pf correction
I
415V
2 kW
50Hz
0.8 p.f
43Practical Example pf correction
- The solution requires the connection of a
capacitor as shown below - Let the currents be as shown
- I new current from supply
- I original current from supply (which still
goes to the motor) - i current drawn by the capacitor
44Practical Example pf correction
I
I
i
415V
2 kW
C
50Hz
0.8 p.f
45Practical Example pf correction
- Let V supply voltage ref phasor.
- P VI cos? 2000
- cos? 0.8
- V 415 0
- w 2.p.50 100p
46Practical Example pf correction
47Practical Example pf correction
48 Practical Example pf correction
V
C
49Practical Example pf correction
50Practical Example pf correction
51Practical Example pf correction
V
I
52Practical Example pf correction
53Practical Example pf correction
54Practical Example pf correction
55Practical Example pf correction
56Practical Example pf correction
57Practical Example pf correction
58Practical Example pf correction
59Practical Example pf correction
- N.B. The reduced Volt-amperes can be used to
supply another load. - Note The capacitor is used to reduce the
current and yet the power ( and current) to the
load remains unaltered.
60Practical Example 2 (Supply line losses)
- A large consumer of 30 kW is supplied power at
o.5 p.f, and 240 V, 50Hz. The supply wires have
resistance of 0.001 per km. If the source is
located 200km away, determine (i) the source
voltage - (ii) The line losses.
- (b) In order to improve the system the p.f is to
be increased to 0.85 by a capacitor bank
connected in parallel with the load.
61Practical Example pf correction
- Determine the improvement i.e.
- reduction is VA
- reduction in line losses.
62Practical Example pf correction
- Let ref phosor be voltage at the load.
63Practical Example pf correction
64Practical Example pf correction
65Practical Example pf correction
R
30kW
C
0.5 pf.
66Practical Example pf correction
67Practical Example pf correction
68Practical Example pf correction
69Practical Example pf correction
V
70Practical Example pf correction
71Practical Example pf correction
72Practical Example pf correction
- It is clear that the improvement in p.f. has two
advantages - (i) Reduces the supplied VA so that the balance
is used to supply other consumers.
73Practical Example pf correction
- (iii) Reduces the line losses which
is just a wastage to supplier. - Hence most power supply company give a penality
charge called Maximum Demand (MD) charge so that
the consumer is persuaded to improve the p.f.
74Practical Example pf correction
- The present load shedding in Uganda could
probably be reduced if industries improved their
p.fs. However, the biggest load on supply
network is domestic which is resistive.