Title: ARI Workshop Psychrometrics
1ARI Workshop - Psychrometrics
- Review of the Process
- Defining State Points
- Application of Mixed Air Calculation
- Defining Sensible Heat Ratio
- Application of Sensible Heat Ratio
- Defining Supply Airflow
- Re-World Example Exercises
2Psychrometric Chart
3Properties of Saturated Air
dry-bulbtemp.
humidityratio
dry-bulb temp.
humidityratio
25F 30F 35F 40F 45F 50F 55F
19.14 24.19 29.94 36.51 44.34 53.63 64.63
60F 65F 70F 75F 80F 85F 90F
77.61 92.89 110.82 131.83 156.38 185.03 218.42
4Plotting Saturated Points
218.42
185.03
156.38
131.83
110.82
92.89
77.61
64.63
53.63
44.34
36.51
29.94
24.19
19.14
0
5Saturation Curve
100 relative humidity curve
6Relative Humidity Curves
relative humidity
100
90
80
70
60
50
40
30
20
10
0
7Properties
dew point
humidity ratio
wet bulb
dry bulb
relative humidity
8Specific Volume
specific volume lines (cubic feet / pound of
dry air)
14.5
14.0
13.5
13.0
9Sensible Heating
10Sensible Cooling
11Adding Moisture
12Removing Moisture
13Sensible Latent Energy
14State Point
78F
50
40
72F
95F
15Mixed Air
mixture
outdoorair (OA)
C
supply fan
B
cooling coil
A
Re-circulated air (RA)
16Outside Return Air
outdoor air
B
A
Re-circulated air
95F
80F
17Determining Mix
C
B
4,000 cfmmixed air
1,000 cfmOA
1,000 cfm 4,000 cfm
0.25
A
3,000 cfmRA
OA RA mixture
25 75 100
18Mixed Air Temperature
95F 0.25 23.75F 80F 0.75
60.00F mixture 83.75F
19Mixed Air State Point
B
70F
C
95F
A
83.75F
80F
20Space Sensible Latent Heat
supply air
return air
sensible heat
latent heat
21Sensible Heat Ratio
Sensible Heat Gain Sensible Heat Gain Latent
Heat Gain
SHR
22SHR Scale
78F DB 65F WB
index point
23Drawing an SHR Line
0.80 SHR line
A
index point
24Drawing an SHR Line
B
D
0.60 SHR line
C
index point
80F
25Coil Curves
26Determining Airflow
STEP 1 Calculate the sensible heat ratio (SHR)
80,000 Btu/hr sensible heat gain 20,000 Btu/hr
latent heat gain
80,000 Btu/hr 100,000 Btu/hr
SHR
0.80
27Design Parameters
room 78F DB, 50 RH outdoor air (OA) 95F
DB, 78F WB ventilation 25 OA
28Plotting Design Points
STEP 2 Plot room, outdoor, and entering
conditions
95F 0.25 23.75F 78F 0.75
58.50F mixture 82.25F
B
C
0.80 SHR
A
29Determining Supply Airflow
STEP 3 Identify supply air conditions
B
C
0.80 SHR
A
D
56.5F
78F
30Determining Airflow
STEP 4 Solve the supply airflow equation
SupplyAirflow
Sensible Heat Gain1.085 (Room DB Supply DB)
80,000 Btu/hr1.085 (78F 56.5F)
3,430 cfm
31Completing the Loop
B
C
A
D
56.5F
D
SA
C
B
82.2F DB 68.6F WBmixture
3,430 cfm 56.5F DB 55.2F WB
OA
A
RA