Title: Sponsored by: State Energy Office
1The North Carolina Energy Code Commercial
Requirements
Sponsored by State Energy Office National
Governors Association, North Carolina
Governors Office, American Institute of
Architects NC Dept of Insurance Conducted
by
Appalachian State UniversityDept. of Technology
Energy Center Boone, NCJeff Tiller, PE,
tillerjs_at_appstate.edu
Chris Mathis and AssociatesAsheville, NC
2Total Energy Use by Sector (TBtu)
2004
1960
3Structure of 2006 NC Code
- Chapter 1 General/Administrative Enforcement
- Chapter 2 Definitions
- Chapter 3 Design Conditions
- Chapter 4 Residential Energy Efficiency
- Chapter 5 Commercial Energy Efficiency
- Chapter 6 Referenced Standards
4SCOPE
- When does the NCECC apply?
- Newly conditioned space
- New construction in existing buildings
- Alterations to existing spaces
- Additions
- Mixed use buildings
- Change in occupancy
5Change In Occupancy
- Alterations to Existing Spaces
- Applies to only portions of the systems being
altered - Applies if alteration increases energy use
- Alterations must meet the requirements
applying to the altered component - New systems in the alterations must comply
6Two Sets of Requirements multiple pathways to
compliance
- Building Design for All Commercial Buildings
- ASHRAE 90.1-2004 in the North Carolina energy
code - Design by Acceptable Practice for Commercial
Buildings - Chapter 5 part of the IECC 2006 with local
amendments
7Typical Commercial Building Energy Consumption
Patterns
8Section 5Envelope Mandatory Provisions
Section 5.4
- Air leakage
- Building envelope sealing
- Fenestration (windows and exterior glass)
- NFRC 400
- 1.0 cfm/ft2
- 0.4 cfm/ft2
- Loading Docks
- Vestibules
- NFRC National Fenestration Rating Council
9Section 5 Envelope, contd Air Leakage
- ..Building envelope shall be sealed, caulked,
gasketed or weather-stripped to minimize air
leakage. - Seams between panels
- Joints between systems
- Joints around penetrations
10502.3 Basic Requirement Air Leakage - Building
Envelope Sealing
Caulk between wall panels particularly at corners
and changes in orientation
Caulk around penetrations of chimney flue vents
or attic hatches
Caulk around doors and windows
Caulk between wall arch floor where floor
penetrates wall
Caulk between wall and roof
Caulk at penetrations of utility services or
other service entry through walls floors and roofs
Caulk between wall panels and top and bottom
plates in exterior walls
Caulk between wall and foundation
Weatherstrip doors
11Major Air Leakage Sites
- Cavities above suspended ceilings
- Plenum return spaces (Highly depressurized)
- Ventilated walls
- Equipment tunnels and chases
- Mechanical rooms and mezzanines
- Unconditioned adjacent space (Storage, warehouse,
plant, etc.) - Exhaust and ventilation fans, plus wind and stack
effect, are major driving forces
12Is Air Barrier Continuous?
- Brand-new NC building
- Drywall leftoff of exteriorwall abovedropped
ceiling - Building usesabove-ceiling areaas return
- When HVAC operates, entire wall cavity goes to a
negative pressure, increasing air leakage,
effectively reducing insulation value, and
potentially causing moisture problems
13Limiting Air Leakage Pathways
- Materials and connections must
- stop air flow
- withstand jobsite abuses
- withstand forces of wind and pressure
- Penetrations must be sealed
- plumbing, wiring, communications
- ductwork
- windows and doors
- Functional penetrations, such as air intakes for
exhaust fans, must be dampered - Vestibules (5 Stories or more, with exceptions)
14Section 5 Envelope -- Vestibules
- Required at building entrances
- Self closing doors
- Exceptions
- a. Building entrances with revolving doors.
- b. Doors not used as a building entrance.
- c. Doors opening directly from a dwelling unit.
- d. Building entrances in buildings located in
climate zone 1 or 2. - e. Building entrances in buildings located in
climate zone 3 or 4 that are less than four
stories above grade and less than 10,000 ft2 in
area. - f. Building entrances in buildings located in
climate zone 5, 6, 7, or 8 that are less than
1,000 ft2 in area. - g. Doors that open directly from a space that is
less than 3,000 ft2 in area and is separate from
the building entrance.
15Section 5 - Prescriptive Requirements, Building
Envelope
16Common R-values Resistance to Conductive Heat
Flow
- Concrete 0.2 per inch
- ½ Drywall 0.5
- Double-paned glass 1.8
- Low-e glass about 3.0
- Fiberglass insulation 3 to 4 per inch
- Cellulose insulation 3.7 per inch
- Expanded polystyrene 4 per inch
- Extruded polystyrene 5 per inch
- Icynene foam 3.6 to 3.7 per inch
- Polyurethane foam 6.7 to 7.0 per inch
172009 IECC Climate ZonesZones 4 and Below Dont
Require Wall Vapor Barriers (Only NW Mountains
need one)
182009 NC Energy Code Climate Zones
Zone 34 No VB
Zone 5 VB Required
19- NORTH CAROLINA ZONES
- Zone 3 except
- Zone 4
- Alamance
- Alexander
- Bertie
- Buncombe
- Burke
- Caldwell
- Caswell
- Catawba
- Chatham
- Cherokee
- Clay
- Cleveland
- Davie
- Durham
- Forsyth
- Franklin
Graham Granville Guilford Halifax Harnett Haywood
Henderson Hertford Iredell Jackson Lee Lincoln Mac
on Madison McDowell Nash Northampton Orange Person
Polk Rockingham Rutherford Stokes Surry Swain Tran
sylvania Vance Wake Warren Wilkes Yadkin Zone
5 Alleghany Ashe Avery Mitchell Watauga Yancey
20NC Energy Code Chapter 5 Prescriptive
21Roof Insulation Requirements IECC 2003 (Chapter
8 of current code)
22Roof Insulation RequirementsASHRAE 90.1-2004
(Chapter 7 of current code and Chapter 5, section
501 of new code)
23Building Envelope Example Roofs
No longer counts Batts over suspended ceiling
tiles
24Inspection is Critically Important!
- Insulation specification was R-30 foam on roof
deck according to the plans (and HVAC design) - The 2.5 inches found installed in the field would
only provide about R-15
2.5
25Commercial Wall Insulation Requirements IECC
2006 (Chapter 5 of new code)
26Steel Framing and Insulation
27Metal Framing Effects
- Thermal bridging effect of metal framing must be
accounted for in calculating U-factors
- Outside Air Film
- 1- inch Exterior sheathing (R-3.8) with
Stucco - 2 x 4 Metal Studs with R-13 in the Cavity
- 1/2 in. Gypsum Board
- Inside Air Film
28Steel Framed Walls
29U-factors for Metal Stud Walls
30Effective R-value of 2x4 Metal Framed Walls (16
o.c.)
31Wall Insulation
32How about now?
33Typical? Non-Compliant!
34Concrete Block Walls
- Concrete Masonry Units
- Insulation-filled CMU used to comply
- IECC 2006 The R-value of integral insulation
installed in concrete masonry units (CMU) shall
not be used in determining compliance with Table
502.2(1)
35- Field Inspection of Big Box Retail Store in
Boone, NC
36Glazing Area Percentage
- Glazing percentage to Above Grade Wall
- Gross window area / gross wall area
- Gross wall area includes
- Above-grade walls
- Band joist and subfloor between floors
- Area of all doors and windows
37Windows - SHGC
- Solar Heat Gain Coefficient
- Requirements dependent on projection factor
- National Fenestration Rating
Council (NFRC) tested - Default SHGC range diagrams
- SHGC SC x .87
Solar Heat Gain Coefficient
Projection Factor (PF)
38NFRC Label
39IECC 2006 Commercial Glazing Requirements (new
code)
40ASHRAE 90.1 Fenestration Requirements for Climate
Zones 3 and 4
Note ASHRAE 90.1-2004 is an option for the
current and new codes
41Window Wall Fraction
42Section 6 HVAC Key Concepts
- Goal a system which minimizes system losses
and utilizes free heating and cooling - Scope and Compliance Paths
- Establish minimum equipment efficiencies
- Establish a min. level of control for systems
- Establish minimum levels of construction and
insulation of systems. - Simplified Approach/Prescriptive Path
- Submittals
43Simplified HVAC Approach Option
- Limited to buildings that meet the following
criteria - buildings with 1 or 2 stories
- buildings lt 25,000 ft2
- single-zone systems
- Unitary packaged or split system air-cooled or
evaporatively-cooled only equipment efficiencies
per tables - Economizer if required
- Outside air requirements are less than 3000 CFM
and less than 70 of airflow - Manual changeover or dual set-point thermostat
- Heat pump supplementary control
- No reheat or simultaneous heating and cooling for
humidity control
44Example 25-ton Cooling Efficiency
- Cooling efficiency
- 25 tons 300,000 Btuh
45Example 25 ton Heating
Heating efficiency 25 tons 300,000 Btuh
46Example 25 ton Controls
- Electronic, 7-day, thermostat can meet the
following requirements - Dual setpoints for heating and cooling modes
- Off-hour shutoff
- Setback capability
- Start-up (set up)
47Example 25 ton Duct Insulation
48Example 25 ton Ducts
- Table 6-D in User Manual
- R-3.5 1-inch duct liner, fiberboard, duct board,
flex duct 1.5-inch mineral fiber duct wrap - R-6.0 1.5-inch duct liner, fiberboard, duct
board, flex duct 2.5-inch flex duct, mineral
fiber duct wrap - R-8.0 2-inch duct liner, fiberboard, duct board,
flex duct 3-inch flex duct, mineral fiber duct
wrap - Duct Sealing Required (to be discussed later)
49Example 25 ton Other
- Air Balancing add note to the design drawings
or specs calling for balancing according to
ASHRAE 111, NEBB, AABCm or other
industry-recognized standard - Since no fan exceeds 300 cfm, a backdraft damper
is not required per 6.2.3.3.3
50ASHRAE / IESNA 90.1-2001HVAC Mandatory Provisions
- Applies to the Prescriptive Path and the Energy
Cost Budget method - Requirements address
- Life cycle cost analysis
- Equipment efficiencies
- Load calculations
- Controls
- Construction and insulation
- Completion requirements
51Section 6 Load Calculations
- Load Calculations are required!
- Ask for them!
52Section 6 Mandatory Provisions-Controls
- Off-Hour controls (note exceptions under
6.4.3.2) - Automatic Shutdown (PGM T-stat OS Timer
Interlock) - Setback Controls (by climate zone - 55F heating
90F cooling) - Optimum Start Controls (gt10,000 cfm)
- Zone Isolation
53More Mandatory Provisions
- They cover
- Heat pump controls
- Humidifier and dehumidifier controls
- Freeze/Thaw protection
- Snow/Ice melting
- Ventilation controls
54Even MORE Mandatory Requirements
- Record drawings
- Operating and Maintenance Manuals
- System Balancing (Air and Water)
- System Commissioning (50,000 sf threshold)
- Good Design Practice
55Section 9 - Lighting
- Use current lighting product performance data and
current new building construction data - Apply current lamp/ballast efficacy and light
loss factors and incorporate IES recommended
light levels - Apply professional lighting design consensus of
quality lighted environments - Combine these elements into building space models
to calculate lighting power densities - Use controls
Key Concepts
56Section 9Lighting General Scope
- Applies to lighting for
- Interior spaces
- Exterior building features (facades, roofs,
entrances, exits, loading docks, canopies) - Exterior building grounds provided thru the
buildings electrical service
57Occupancy Sensors
Section 9.4.1.2
- For high usage areas with irregular schedules
- Applications
- Private offices
- Classrooms
- Conference rooms
- Break rooms
- Restrooms
58Interior Lighting Controls
- Lighting controls required for each area enclosed
by ceiling height partitions - Switch locations
- In view of lights
- On or off indication from remote location
- Occupancy sensor
59Interior Lighting Controls
- Exceptions
- Emergency/security lighting
- Stairway or corridor lighting for egress
60Guest Rooms
- Master switch required at entry
61Exterior Lighting Controls
- Automatic switching or photocell controls shall
be provided for all exterior lighting not
intended for 24-hour operation. - Automatic time switches shall have a combination
- Seven-day and seasonal daylight program schedule
adjustment - A minimum 4-hour power backup
62Tandem Wiring
- Exceptions
- Luminaires with electronic high-frequency
ballasts - Luminaires not on same switch controls or not in
the same area
63Exit Signs
- Internally illuminated exit signs shall not
exceed 5 Watts per side
64Lighting Power Densities Using the Building Area
Method
65Energy-Efficient Lighting Sources
66Total Connected Power
- Total connected lighting wattage includes
- Lamp wattage
- Ballast wattage
- Sources of bulb/ballast wattages
- Manufacturers literature
- Industry default tables
- Exceptions
- Specialized medical, dental, and research
lighting - Professional sports arena playing field lighting
- Display lighting for gallery exhibits, museums,
and monuments - Guest room lighting in hotels, motels, boarding
houses, or similar buildings - Emergency lighting automatically off during
normal building operation
67Does the Building Comply?
- Determine the total connected power in watts for
the proposed lighting - Determine the interior lighting power budget for
the entire building or space - Building complies if
- Interior lighting power budget - total connected
power ?0
68Exterior Lighting
- Criteria
- Lighting power supplied through building
electrical service - Must use energy-efficient lighting sources to
highlight paths, walkways and parking areas - ? 45 Lumens/Watt
- Fluorescent or Compact Fluorescent
- Metal Halide or High Pressure Sodium
- Exceptions
- Historical
- Safety
- Signage
- Emergency
69Section 11Energy Cost Budget Method
- Alternative to prescriptive method except
buildings with no mechanical systems - Based on overall building performanceexpressed
as energy cost budget - Mandatory Provisions all must be met
- Budget (or baseline) based on prescriptive
measures - Allows trade-offs between measures
- Useful for optimizing design
70Key Points to Check
- Envelope
- Insulation values correct? Proper installation?
- Fenestration -- glass
- Fenestration U-factor and SHGC (on plans and
in field) - Air sealing details
- HVAC
- Programmable controls?
- Economizer?
- Duct and pipe insulation?
- Ducts sealed?
1/28/2008
Mathis Consulting Company
Page 70
71Key Inspection Points (cont.)
- HVAC (continued)
- No simultaneous heating and cooling (except where
allowed for reheat) - Complex systems
- Fan power
- Temperature reset
- Zoning
- Reheat limitation
- Etc.
1/28/2008
Mathis Consulting Company
Page 71
72Key Inspection Points (cont.)
- Lighting
- If most lamps are not T-8 fluorescent or more
efficient lamps, need to check - Check controls -- occupancy and daylighting
controls - Exit signs
- Exterior lighting efficiency and controls
73So, What Now?
- In Commercial, Appendix B is not enough
- Plan review and inspection of energy features is
needed
74ASHRAE 90.1 Advanced Design Guide Office
Building
75ASHRAE 90.1 Advanced Design Guide Office
Building
76ASHRAE 90.1 Advanced Design Guide Office
Building
77ASHRAE 90.1 Advanced Design Guide Office
Building