Title: Operation and Maintenance Reminders
1Operation and Maintenance Reminders
- FAC Section 62-555.350, OM of PWSs
262-555.350(1) Comply with Standards/Requirements
- PWSs shall operate maintain PWSs to comply with
applicable standards in FAC Chapter 62-550
applicable requirements in FAC Chapter 62-555 - FAC Chapter 62-550 standards
- Primary standards MCLs, MRDLs, treatment
techniques - inorganics - control acrylamide/epichlorohydrin
- organics - filter disinfect surface water
- disinfectant residuals - control lead copper
- DBPs - control DBP precursors in surface water
- coliforms
- radionuclides
- Secondary standardsMCLs treatment techniques
362-555.350(2) Maintain PWSs in Good Operating
Condition
- Preventive maintenance on electrical or
mechanical equipment shall be performed in
accordance with either manufacturer's
recommendations or PWS's written - preventive maintenance program
- Exercise auxiliary power sources (under load at
least monthly) - Check calibration of finished-water flow meter(s)
at WTP(s)
Most auxiliary engine/generator manufacturers
have specific recommendations for exercising
their engines/generators but in no case shall
auxiliary engines/generators be run under load
less frequently than monthly.
Some meter manufacturers may not have
recommendations for checking calibration of their
meters. However, consistent with water management
district requirements, calibration of
finished-water flow meters should be checked gt
once every 3 years to ensure accuracy within 5.
462-555.350(2) (continued)
- Test pressure-relief valve(s) for hydropneumatic
tank(s) - Exercise accessible isolation valves at WTP(s)
in distribution system
Pressure-relief valves for hydropneumatic tanks
should be tested at least annually.
Some valve manufacturers simply recommend
exercising their valves at frequency based upon
local experience. However, consistent with Water
Distribution Systems Handbook AWWA's Manual
M44, isolation valves should be exercised gt once
every 1 or 2 years.
562-555.350(2) (continued)
- Accumulated sludge
- biogrowth shall be cleaned
- routinely (at least annually)
- from treatment facilities that
- are in contact with water
- that are not designed to
- collect sludge or support
- biogrowth
- Blistering, chipped, or cracked coatings/linings
on treatment or storage facilities in contact
with water shall be rehabilitated or repaired
662-555.350(2) (continued)
- Finished-water storage tanks, including
- conventional hydropneumatic tanks with access
- manhole, shall be
- Checked at least annually to ensure hatches are
closed - screens are in place
- Cleaned gt once every 5 years to remove biogrowth,
calcium - or iron/manganese deposits, sludge from inside
of tank - Inspected for structural coating integrity
- gt once every 5 years by personnel under
- responsible charge of PE
Requirement for inspection is intended to apply
to steel or concrete tanks is not required for
tanks constructed of HDPE or fiberglass.
762-555.350(2) (continued)
- Dead-end water mains conveying
- finished water shall be flushed
- either quarterly or in accordance
- with written flushing program
- established by PWS
Requirement is intended to apply to mains gt 6" in
diameter does not apply to mains lt 6" in
diameter unless there is history of water quality
problems.
PWS may flush all dead-end water mains at least
quarterly, in which case PWS is not required to
have written flushing program. Or, PWS may
develop written comprehensive and/or spot
flushing program, in which case PWS may flush
dead-end mains less frequently than quarterly if
PWS documents, using water quality data, why less
frequent flushing is appropriate.
862-555.350(3) Use Proper Water Treatment
Chemicals
- PWSs shall ensure, lead/chief WTP
- operators shall certify on MORs, that water
- treatment chemicals conform to NSF
- Standard 60 (or standards in Water
- Chemicals Codex or Food Chemicals Codex)
- Operators may base their certifications upon
- evaluations conducted by PWS or upon third-party
- (NSF, UL, or WQA) or manufacturer certifications
NSF
WQA has certified that all Ultra Clorox Regular
or Germicidal Bleach conforms to NSF Standard 60.
962-555.350(4) Operate WTPs Within Permitted
Capacity
- No PWS shall operate any WTP
- at capacity gt plant's permitted
- operating capacity
- Permitted operating capacity of
- WTP is as specified in latest
- applicable DEP construction permit
- (or as established by DEP/ACHD if
- no permitted operating capacity is
- specified in construction permit)
- Each day licensed operators staff/visit WTPs,
they shall measure record net quantity of
finished water produced by WTP
1062-555.350(5) Monitor Maintain Effectiveness
of Disinfection
- PWSs that are using ground water that are
required to achieve 4-log virus
removal/inactivation shall monitor maintain
effectiveness of disinfection as follows - For each day WTP is in operation,
- PWS shall monitor residual
- disinfectant concentration (C)
- before or at first customer
- Monitor continuously if PWS
- serves gt 3,300 persons
- Take 1 grab sample during peak
- flow if PWS serves lt 3,300
- persons
1162-555.350(5) (continued)
- For each day WTP is in operation, PWS shall
record following on MOR - Lowest C provided before or at first customer
during peak flow - Corresponding disinfectant contact time (T) at C
monitoring point during peak flow - Resulting lowest "CT provided" before or at first
customer during peak flow - For each day WTP is in operation, PWS shall
record "CT required" to achieve necessary virus
inactivation - For each day WTP is in operation, PWS shall
compare "CT provided" to "CT required" - If "CT provided" is lt "CT required," PWS shall
- Increase disinfectant dose ( take grab samples
at least every 4 hours if not monitoring
continuously) until "CT provided" is gt "CT
required" - Notify DEP/ACHD in accordance with 62-555.350(10)
1262-555.350(6) Maintain Monitor Disinfectant
Residual
- PWSs shall maintain free chlorine residual gt 0.2
mg/L, or combined chlorine residual gt 0.6 mg/L,
throughout their distribution system at all times - PWSs shall measure disinfectant residual at point
reflecting maximum residence time after
disinfectant addition shall record result on
MOR - Take 1 grab sample/day for 5 days/week if PWS
serves gt 3,300 persons - Take 1 grab sample/day for 2 days/week if PWS
serves lt 3,300 persons - If disinfectant residual is lt required,
- PWS shall increase disinfectant dose
- as necessary, flush water mains,
- until disinfectant residual is gt required
1362-555.350(7) Maintain Pressure
- Except when water mains break or treatment or
pumping equipment fails, PWS shall maintain
pressure gt 20 psig throughout their distribution
system at all times
1462-555.350(8) Employ Licensed Operators
- PWSs shall employ licensed operators in
accordance with FAC Chapters 62-602 62-699 - This does not apply to TWSs using only
groundwater serving only businesses other than
public food service establishments as defined in,
regulated under, FS Chapter 381, 500, or 509
1562-555.350(9) Obtain Required Permits or
Approvals Before Construction or Alterations
- No PWS shall alter or replace underground
portions of, or abandon, any well without first
obtaining any required permit from appropriate
WMD or delegated permitting authority - See FAC Chapter 62-532 to determine whether
permit is required - No PWS shall alter or replace, or discontinue use
of, any water source, system components (other
than underground portions of wells), or water
treatment chemicals without first obtaining any
required permit or approval from, or submitting
any required notification to, DEP/ACHD - See FAC subsection 62-555.520(1) to determine
whether permit, approval, or notification is
required
1662-555.350(10) Notify SWP, DEP/ACHD, Water
Customers as Required
- PWSs shall call SWP immediately (lt 2 hours) after
discovery of any actual or suspected sabotage or
security breach, or any suspicious incident,
involving PWS
1762-555.350(10) (continued)
- PWSs shall call DEP/ACHD ( speak directly
- to person) as soon as possible, but never
- later than noon of next business day, in
- event of following emergency or abnormal
- conditions
- Occurrence of abnormal color, taste, or odor in
raw or finished water - Failure to comply with applicable CT requirements
for disinfection - Breakdown of water treatment or pumping
facilities, or break of water main, if breakdown
or break is expected to - Adversely affect finished-water quality
- Interrupt service to gt 150 connections or gt 350
people - Interrupt service to any 1 connection for gt 8
hours or - Necessitate issuance of precautionary "boil
water" notice
1862-555.350(10) (continued)
- PWSs shall notify DEP/ACHD affected customers
by no later than previous business day before
initiating planned conversions from chloramines
to free chlorine or vice versa - PWSs shall notify DEP/ACHD by calling ( speaking
directly to person) - PWSs shall notify customers in writing or by
telephone, newspaper, radio, or TV
1962-555.350(10) (continued)
- PWSs shall notify DEP/ACHD affected customers
by no later than previous business day before
taking system components out of operation for
planned maintenance or repair work - PWSs shall notify DEP/ACHD by calling ( speaking
directly to person) if work is expected to - Adversely affect finished-water quality
- Interrupt service to gt 150 connections or gt 350
people - Interrupt service to any 1 connection for gt 8
hours or - Necessitate issuance of precautionary "boil
water" notice - PWSs shall notify affected customers in writing
or by telephone, newspaper, radio, or TV if work
is expected to - Adversely affect finished-water quality or
- Interrupt service
2062-555.350(10) (continued)
- PWSs shall describe in MORs
- All emergency or abnormal conditions, including
all breakdowns of water treatment or pumping
facilities all water main breaks - All maintenance or repair work that involves
taking system components (other than water
service lines) out of operation
2162-555.350(11) Issue Precautionary "Boil Water"
Notices as Required
- PWSs shall issue precautionary "boil water"
notices as required or recommended in DOH's
"Guidelines for the Issuance of Precautionary
Boil Water Notices" - View DOH's guidelines at
- www.doh.state.fl.us/environment/water/manual/boil.
htm
2262-555.350(12) Keep OM Logs, Keep/Submit MORs,
Keep Records
- PWSs shall keep OM log at their WTPs
- For WTPs connected to TWSs using only groundwater
- serving only businesses other than public food
- service establishments, log shall contain
- Minimum of previous 3 months of data at all times
- Date type of all maintenance performed
- Date results of all sampling analyses
performed - unless documented on laboratory sheet
- For all other WTPs, log shall contain information
listed - in, shall be maintained as described in, FAC
- subsection 62-602.650(4)
2362-555.350(12) (continued)
- PWSs shall submit MORs within 10 days after each
month - This does not apply to TWSs using only
groundwater serving only businesses other than
public food service establishments - PWSs shall use appropriate form(s) submit them
to DEP/ACHD (except for Form 62-555.900(5), which
goes to DOH Bureau of Dental Health) - Form 62-555.900(2), "MOR for Subpart H Systems"
- Form 62-555.900(3), "MOR for PWSs Treating Raw
Ground Water or Purchased Finished Water" - Form 62-555.900(4), "MOR for Consecutive Systems
that Do Not Treat Water" - Form 62-555.900(5), "MOR for PWSs Fluoridating
Water" - Form 62-555.900(6), "MOR for Consecutive Systems
that Receive Purchased Finished Water from a
Subpart H System" - Form 62-555.900(11), "MOR for Summation of
Finished-Water Production by CWSs that Have
Multiple Treatment Plants"
2462-555.350(12) (continued)
- PWSs shall keep MORs, together with
- additional operation records required
- by MOR forms, for gt 10 years
- PWSs shall keep following records
- Records documenting that finished-water
- storage tanks have been cleaned
- inspected during past 5 years
Records should include bills/receipts for
cleaning or inspection services inspection
report signed sealed by PE.
2562-555.350(12) (continued)
- Records documenting that isolation valves are
being exercised
Minimum required information.
2662-555.350(12) (continued)
- Records documenting that dead-end water mains are
being flushed
Minimum required information.
2762-555.350(13) Provide Update OM Manuals
- PWSs shall provide OM manual for each WTP
shall update manual as necessary to reflect WTP
alterations - OM manual shall contain operation control
procedures, preventive maintenance repair
procedures, for all WTP equipment - Bound indexed equipment manufacturer manuals
are considered sufficient - OM manual shall be available for reference at
WTP or at convenient location near WTP
WTP OM Manual
2862-555.350(14) Maintain Up-to-Date Distribution
System Map
- CWSs serving gt 350 persons or gt 150
- connections shall maintain up-to-date
- map of their water distribution system
- Map shall show
- Size approximate location of water mains if
known - Approximate location of valves fire hydrants
- Approximate location of any pressure zone
- boundaries, pumping facilities, storage tanks,
- interconnections with other PWSs
Map may be paper- or computer-based.
For small CWS, map may be single map while for
large CWS, map may consist of 1 overall map at
large scale plus many smaller-scale maps indexed
to overall map.
2962-555.350(15) Develop Implement Emergency
Preparedness/Response Plan
- CWSs serving gt 350 persons or gt 150 connections
shall develop written emergency
preparedness/response plan in accordance with
AWWA Manual M19 shall update implement plan
as necessary - CWSs shall coordinate with their Local Emergency
Planning Committee FDLE Regional Security Task
Force
3062-555.350(15) (continued)
- CWSs shall include following information in their
emergency preparedness/response plan - Communication chart
- Written agreements with other PWSs,
- response organizations, etc
- Disaster-specific plan for vandalism or
- sabotage drought hurricane structure fire
- if applicable, flood, forest or brush fire,
- hazardous material release
- Details about standby power recommendations for
amount of fuel to keep on site in reserve for
auxiliary power sources - If applicable, recommendations for amount of
chemicals to keep in inventory at WTPs
31Summary
- Implement requirements of FAC Section 62-555.350
- Perform preventive maintenance, including
exercising of isolation valves, keep records
documenting exercising of isolation valves - Clean inspect finished-water storage tanks
every 5 years keep records - Flush dead-end water mains keep records
- Ensure water treatment chemicals conform to NSF
Standard 60 - If required to achieve 4-log virus
removal/inactivation, ensure that "CT provided"
is always gt "CT required" - Maintain required minimum disinfectant residual
throughout distribution system at all times
32Summary (continued)
- Maintain pressure gt 20 psig throughout
distribution system - Call SWP immediately after discovery of actual or
suspected security breach or suspicious incident,
call DEP/ACHD as soon as possible in event of
emergency or abnormal conditions - Notify DEP/ACHD customers no later than
previous business day before planned conversions
from 1 secondary disinfectant to another before
certain planned maintenance/repair work - Issue precautionary "boil water" notices per DOH
guidelines - Keep OM logs at all WTPs, keep/submit MORs
- Maintain OM manual at all WTPs
- If CWS serving gt 350/150, maintain up-to-date
water distribution system map emergency
preparedness/response plan
33Where to Get More Information
- View or print FS at
- www.flsenate.gov/Statutes
- View or download electronic copy of latest
version of FAC Chapter 62-532, 62-550, 62-555,
62-602, or 62-699 at - www.dep.state.fl.us/legal/Rules/rulelistnum.htm
- View or download electronic copy of latest
version of MOR forms at - www.dep.state.fl.us/water/drinkingwater/forms.htm
- Order 4th (2001) Edition of AWWA Manual M19 at
- www.awwa.org
34Where to Get More Information (continued)
- Search for water treatment chemicals certified
(by third party) as conforming to NSF Standard 60
at - www.nsf.org
- www.ul.com
- www.wqa.org
- View, print, or order FL Building Code at
- www.floridabuilding.org
- Direct questions about FAC Chapter 62-555 to
- Drinking Water Program personnel at appropriate
DEP district or ACHD - John Sowerby john.r.sowerby_at_dep.state.fl.us
(850) 245-8637 in Drinking Water Program at DEP
headquarters