SIGNSRequired by Cal/OSHA
  • Paul R. Burnett
  • Safety Program Administrator
  • Santa Clara Valley Water District
  • pburnett_at_valleywater.org

2
Accident Prevention Signs
  • As used in this section (8 CCR 3340), the word
    sign refers to a surface on which letters or
    other markings appear, prepared for the warning
    of, or safety instruction of, industrial workers
    or members of the public who may be exposed to
    hazards.
  • 8 CCR 3340(b)

3
Accident Prevention Signs
  • Danger signs shall be used only where an
    immediate hazard exists.
  • All employees shall be instructed that danger
    signs indicate immediate danger and that special
    precautions are necessary.
  • 8 CCR 3340(c)(1)

4
Accident Prevention Signs
  • Warning signs shall be used to indicate a
    potentially hazardous situation which, if not
    avoided, could result in death or serious injury.
  • All employees shall be instructed that warning
    signs indicate a potentially hazardous situation
    that could result in death or serious injury.
  • 8 CCR 3340(c)(2)

5
Accident Prevention Signs
  • Caution signs shall be used only to warn against
    potential hazards or to caution against unsafe
    practices.
  • All employees shall be instructed that caution
    signs indicate a possible hazard against which
    proper precaution should be taken.
  • 8 CCR 3340(c)(3)

6
(No Transcript)
7
Accident Prevention Signs
  • The wording of any sign shall be easily read and
    concise. The sign shall contain sufficient
    information to be easily understood. The wording
    shall make a positive, rather than negative
    suggestion and shall be accurate in fact.
  • 8 CCR 3340(e)

8
SLOW MOVING VEHICLE
  • 8 CCR 3340(d)(6)

9
BIOHAZARD
  • 8 CCR 3340(d)(7)
  • 8 CCR 5193(e)(2)(B)(4) (g)(1)(B)

10
Laser Warning Signs
  • Areas in which lasers are used shall be posted
    with laser warning signs and labels in accordance
    with American National Standards Institute (ANSI)
    Z136.1- 2000, American National Standard for Safe
    Use of Lasers, Section 4.7, which is hereby
    incorporated by reference.
  • 8 CCR 1801(d), Nonionizing Radiation

11
(No Transcript)
12
FLAMMABLE
  • All (LP gas) containers in excess of 125 gallons,
    except transportation containers and fuel
    containers on motor vehicles, shall have the word
    FLAMMABLE on each side that is readily visible.
    The letters of this sign shall be standard-type
    letters and shall have a height of at least 1/12
    of the diameter of the container
  • 8 CCR 489(a), Warning Signs on LP Gas Systems

13
No Smoking
  • No employer shall knowingly or intentionally
    permit, and no person shall engage in, the
    smoking of tobacco products in an enclosed space
    at a place of employment.
  • Where smoking is prohibited throughout the
    building or structure, a sign stating "No
    smoking" shall be posted at each entrance to the
    building or structure.
  • 8 CCR 5148(a) and (b)(1)(A), Prohibition of
    Smoking in the Workplace

14
NO SMOKING, OPEN FLAMES OR OTHER SOURCE OF
IGNITION PERMITTED WITHIN ______ FEET
  • Warning signsshall be applied (with) letters at
    least 1 1/2 inches high, in sharply contrasting
    colors, on each stationary container or on a sign
    posted adjacent to the container (of LP gas).
  • 8 CCR 489(b) see also 8 CCR 542(b)

15
CAUTION POWDER-ACTUATED TOOL IN USE
  • A sign at least 8 x 10 inches (20 x 25 cm), using
    boldface type no less than 1-inch (2.5 cm) in
    height, be conspicuously posted within 50 feet
    (15 m) of the area where the tools are being
    used. The sign shall bear wording similar to the
    following
  • 8 CCR 1691(n), Operation of Powder-Actuated Tools

16
Caution -- Ammonia
  • in sharply contrasting colors, with letters at
    least 1/12 of the tank diameter in height, but
    need not be in excess of 1 1/2 inches for tanks
    500 gallons capacity or less or 4 inches for
    tanks exceeding 500 gallons capacity.
  • 8 CCR 502(a), Anhydrous Ammonia Warning Signs

17
Unlawful To Operate This Equipment Within 10 Feet
Of High-Voltage Lines of 50,000 Volts Or Less
  • The owner, agent, or employer responsible for the
    operations of equipment shall post and maintain
    in plain view of the operator and driver on each
    crane, derrick, power shovel, drilling rig, hay
    loader, hay stacker, pile driver, or similar
    apparatus, a durable warning sign legible at 12
    feet reading
  • 8 CCR 2947

18
WARNING - LEAD WORK AREA POISON - NO SMOKING OR
EATING
  • The following warning sign be posted in each
    regulated area or work areas where the exposure
    to lead exceeds the PEL.
  • These signs are to be posted and maintained in a
    manner which assures that the legend is readily
    visible.
  • 8 CCR 1532(m) 8 CCR 5216, App B 8 CCR 5198 App B

19
JACKING GEAR IS ENGAGED
  • The jacking gear shall be engaged to prevent the
    main engine from turning over. A sign shall be
    posted at the throttle indicating that the
    jacking gear is engaged.
  • 8 CCR 8376(c)(1)(A), Ships Propulsion Machinery

20
WARNING! COTTON DUST WORK AREA May Cause Lung
Injury (Byssinosis) RESPIRATOR REQUIRED IN THIS
AREA
  • The employer shall post the following warning
    sign in each work area where the permissible
    exposure limit for cotton dust is exceeded.
  • 8 CCR 5190(j)

21
DANGER -- PERMIT-REQUIRED CONFINED SPACE, DO NOT
ENTER
  • If the workplace contains permit spaces, the
    employer shall inform exposed employees and other
    employees performing work in the area, by posting
    danger signs or by any other equally effective
    means, of the existence, location of and the
    danger posed by the permit spaces.
  • 8 CCR 5157(c)(2)

22
EXPLOSIVES
  • The front, both sides, and rear of the truck or
    trailer shall be posted with warning signs
    reading EXPLOSIVES in red letters at least 4
    inches high, with a 5/8-inch stroke on a white
    background.
  • 8 CCR 5347(c), Transportation of Blasting Agents

23
RADIO TRANSMITTING PROHIBITED IN THIS AREA
  • Warning signs shall be posted at all entrances to
    the well site with lettering RADIO TRANSMITTING
    PROHIBITED IN THIS AREA or equivalent. Lettering
    of the sign shall be at least 4 inches high in
    red letters with a 5/8-inch stroke on a white
    background.
  • 8 CCR 5314(d)

24
Warning - Disconnecting Switch - Do Not Open
Under Load
  • Unless so interlocked that they cannot be opened
    under load, disconnecting switches shall be
    provided with permanent warning signs having
    letters at least 2 inches high and reading as
    follows
  • 8 CCR 2835(h)

25
ELEVATOR EMERGENCY CALL POLICE
  • Where elevatorswithout a designated operator in
    the car, are locatedother than inresidential
    buildingsand are not provided with a telephone
    in the elevator carthey shall be provided withA
    sign that can be read from the adjacent sidewalk
    (with) letters not less than 2 inches high.
  • 8 CCR 3041(a)(3)(A)

26
Signs in Laboratories
  • Prominent signsshould be posted
  • Emergency telephone numbers
  • Location signs for safety showers, eyewash
    stations, other safety and first aid equipment,
    exits
  • Warnings at areas or equipment where special or
    unusual hazards exist.
  • 8 CCR 5191 Appendix A

27
DANGER ASBESTOS CANCER AND LUNG DISEASE HAZARD
AUTHORIZED PERSONNEL ONLY
  • The warning signsshall bear the following
    information
  • 8 CCR 1529(k)(7)(B)(1) 5208(j)(3)(B)(1)

28
DANGER CADMIUM CANCER HAZARD CAN CAUSE LUNG AND
KIDNEY DISEASE AUTHORIZED PERSONNEL ONLY
RESPIRATORS REQUIRED IN THIS AREA
  • Warning signsshall bear the following
    information
  • 8 CCR 1532(m)(2)(B), Cadmium

29
DANGER ETHYLENE OXIDE CANCER HAZARD AND
REPRODUCTIVE HAZARD AUTHORIZED PERSONNEL ONLY
RESPIRATORS AND PROTECTIVE CLOTHING MAY BE
REQUIRED TO BE WORN IN THIS AREA
  • 8 CCR 5220(j)(1)(a), Ethylene Oxide

30
CANCER-SUSPECT AGENT AUTHORIZED PERSONNEL ONLY
  • Entrances to regulated areas shall be posted with
    signs bearing the legend
  • 8 CCR 5209(e)(1)(A ), Carcinogens

31
CANCER-SUSPECT AGENT EXPOSED IN THIS AREA
IMPERVIOUS SUIT INCLUDING GLOVES, BOOTS AND
AIR-SUPPLIED HOOD REQUIRED AT ALL TIMES
AUTHORIZED PERSONNEL ONLY
  • Entrances to regulated areas containing
    operations covered in paragraph (c)(5)shall be
    posted with signs bearing the legend
  • 8 CCR 5209(e)(1)(B), Carcinogens

32
DANGER (INSERT APPLICABLE CHEMICAL NAME) CANCER
HAZARD AUTHORIZED PERSONNEL ONLY NO SMOKING OR
EATING RESPIRATOR REQUIRED
  • 8 CCR 5214(l)(2)(A), Arsenic

33
In case of fire Use stairway for exit Do not
use elevator
  • All automatic elevators shall have not less than
    one sign at each landing printed on a contrasting
    background in letters not less than 1/2 inch high
    to read
  • 8 CCR 3041(c)(6), Emergency and Signal Devices

34
WARNING - HIGH VOLTAGE KEEP OUT
  • Permanent and conspicuous warning signs shall be
    posted on all doors or gates that provide access
    to enclosures containing exposed energized parts
    and conductors. Such signs shall be legible at 12
    feet and shall read substantially as follows
  • 8 CCR 2811, Warning Signs (Vaults)

35
HIGH VOLTAGE
  • A conspicuous and permanent "HIGH VOLTAGE" sign
    shall be placed on the outside at the point where
    a high-voltage conductor enters the building.
  • 8 CCR 2824(c)(4), Overhead Lines
  • Where the conductors are not in conduit, a
    similar sign shall be placed on the inside of the
    building also, at the point of entrance.

36
DANGER - UNSAFE ROOF KEEP OFF
  • The roofs of tanks and reservoirs in service
    shall be externally inspectedat intervals not to
    exceed one year. Where a roof has been found to
    be unsafe or has not been inspected Legible
    signs shall be posted at all approaches to the
    tank or reservoir roofshall read "DANGER -
    UNSAFE ROOF - KEEP OFF", or equivalent wording in
    letters at least two inches (2") in height.
  • 8 CCR 6803(a)

37
STOP -- Tank Car Connected
  • Caution signs shall be so placed on the track or
    (anhydrous ammonia) carand shall be left up
    until after the car is unloaded... Signs shall be
    of metal or other suitable material, at least 12
    by 15 inches in size and bear the words "STOP --
    Tank Car Connected" or "STOP -- Men at Work" the
    word, "STOP", being in letters at least 4 inches
    high and the other words in letters at least 2
    inches high. The letters shall be white on a blue
    background.
  • 8 CCR 509(d)(1)

38
Blue Stop Signs
  • The employer shall provide blue stop signs for
    use by day, and in addition, blue lights
    fornight work, and cause them to be displayed
    before employees are permitted to work in, upon,
    or under any standing railroadcarswhere
    unanticipated movement or disturbance of
    suchcars might endanger employees or equipment.
  • 8 CCR 3333(a)

39
Unlawful to operate this equipment within 10 feet
of high-voltage lines of 50,000 volts or less
  • Each ENG (Electronic News Gathering) vehicle
    equipped with elevating mast, dish, antenna, or
    similar apparatus, shall be posted with durable,
    permanent warning signs.
  • 8 CCR 2981(e)(1)

40
22 May 2000 LOS ANGELES -- The antenna mast of a
KABC-7 TV news van contacted power lines,
critically injuring reporter Adrienne Alpert, who
was covering a seat belt safety news conference
at Hollywood Forever Cemetery. Alpert had
third-degree electrical burns over 25 percent of
her body, losing half her left arm, half her
right leg, part of her left foot and several
fingers of her right hand.
41
(Private Roads Mine Safety)
  • Roads used for two-way traffic on which vehicles
    do not travel on the right side all the way shall
    be posted with signs indicating the side of the
    road to travel.
  • Public and permanent railroad crossings shall be
    posted with warning signs or signals, or shall be
    guarded when trains are passing...
  • 8 CCR 7014(e) and (i)

42
(Private Roads - Earthmoving)
  • On private roads used for two-way traffic,
    arrangements shall be such that vehicles travel
    on the right side as much as possible. Signs
    shall be posted to clearly indicate variations
    from this system.
  • 8 CCR 1590(a)(2)

43
(Safety Shower / Eyewash)
  • Safety shower and eyewash fountain locations
    shall be made conspicuous by special marking,
    signs, or other identification.
  • 8 CCR 6822(b)

44
(Corrosive Samples)
  • Warning signs or legends shall be conspicuously
    posted where the substance being sampled or gaged
    is corrosive.
  • 8 CCR 6822(e)(2)

45
(Falling Trees)
  • An employee shall be stationed to direct traffic
    when there is a probability of danger in falling
    a tree adjacent to a railroad, cat road, motor
    road, or trail. Warning signs shall be posted on
    motor roads in areas of cutting.
  • 8 CCR 6276

46
(Energized Circuits)
  • Where (energized) circuits existwarning signs
    shall be posted
  • 8 CCR 1518(d)(1)

47
(Traffic Control Signs)
  • Specifications for the size and design of
    signsused for traffic control shall be as
    described in the "California Manual on Uniform
    Traffic Control Devices for Streets and Highways,
    September 26, 2006"which is incorporated by this
    reference.
  • 8 CCR 1598(b)

48
(Placement of Warning Signs)
  • Placement of (traffic control) warning signs
    shall be according to the California Manual on
    Uniform Traffic Control Devices for Streets and
    Highways, September 26, 2006which is herein
    incorporated by reference.
  • 8 CCR 1599(c)

49
(Traffic Control Warning Signs)
  • Before (telecommunications) work is begun in the
    vicinity of vehicular or pedestrian traffic which
    may endanger employees, warning signs and/or
    flags or other traffic control devices shall be
    placed conspicuously to alert and channel
    approaching traffic.
  • 8 CCR 8604(a)

50
(Energized/Moving Parts Danger)
  • If work exposes energized or moving parts that
    are normally protected, danger signs shall be
    displayed and barricades erected, as necessary,
    to warn other personnel in the area.
  • 8 CCR 8604(b)

51
(Riding on Conveyors Forbidden)
  • Riding vertical or inclined reciprocating
    conveyors shall be forbidden to all persons.
    Warning signs to this effect shall be
    conspicuously and securely posted at each point
    of access to platform or carrier. Lettering
    shall be not less than 2 in. (51 mm) high on a
    contrasting background.
  • 8 CCR 3087.2(c)(2)

52
(Dangerous Area Sign / Barrier)
  • If any dangerous or questionable ground is found
    in the roof or sides (of a mine tunnel), it shall
    promptly be made safe by one or more of the
    following means (1) Scaling or blasting down
    (2) Supporting (3) Backfilling (4) Erect
    barriers with warning signs to prevent entrance
    to the dangerous area.
  • 8 CCR 7160(c)(4)

53
(Unqualified Persons Keep Out)
  • Entrances to rooms and other guarded locations
    containing exposed energized parts shall be
    marked with conspicuous warning signs forbidding
    unqualified persons to enter.
  • 8 CCR 2340.17(b), Guarding of Energized Parts

54
(Circuit Feedback)
  • Circuits shall be labeled at all accessible
    points with suitable warning signs stating the
    locations from which feedback may occur because
    of
  • 8 CCR 2831

55
(No Headroom)
  • In existing installations, which do not comply
    with the minimum headroom clearance (6 feet 8
    inches), the obstruction shall be removed, or if
    this is impracticable, a suitable warning sign
    shall be placed near or on the obstruction so as
    to notify employees of its presence.
  • 8 CCR 3272(b)

56
(Scaffold Above)
  • When a suspended scaffold is suspended over an
    area traveled by workers, the public or vehicular
    traffic, the ground area directly under the work
    zone shall be effectively blocked by means of
    barricades, or an attendant shall be stationed so
    as to keep the area clear. Warning signs shall
    also be posted below.
  • 8 CCR 3285(b)

57
(Boatswains Chair Above)
  • When a boatswain's chair or (a Controlled Descent
    Apparatus (CDA)) is suspended over an area
    traversed by workers, pedestrians or vehicular
    traffic, the ground area below and within the
    window cleaner's work zone shall be effectively
    blocked...or an attendant shall be stationed to
    keep the area clear. Warning signs shall also be
    posted below.
  • 8 CCR 3286(a)(3)

58
(Motor May Start At Any Time)
  • There shall be conspicuously displayed at all
    machines driven by electric motors that are
    controlled by fully automatic starters and which
    may injure employees, legible signs giving
    warning that the machines are automatically
    controlled and may start at any time.
  • 8 CCR 3320

59
(Power Take-Off (PTO) Signs)
  • Power Take-Off Guarding Signs, decals, etc.,
    shall be placed at prominent locations on
    agricultural equipment specifying that power
    drive system guards shall be kept in place.
  • 8 CCR 3440(c)(3)

60
(Doorway Warning Signs)
  • Warning signs shall be posted where (railcar)
    doorways open onto tracks, at blind corners and
    at similar places where vision may be restricted.
  • 8 CCR 3332(d)

61
(Hazardous Atmosphere)
  • To prevent inadvertent employee entry into spaces
    that have been identified as having hazardous,
    flammable or oxygen deficient atmospheres,
    appropriate warning signs or equivalent means
    shall be posted at all means of access to those
    spaces.
  • 8 CCR 3461(l), Marine Terminal Operations

62
(Access Prohibited)
  • Warning signs shall be conspicuously posted at
    each (cotton gin) lint cleaner stating that
    employee access to lint cleaner saws is
    prohibited until the lint cleaner has been
    deenergized and locked out from its energy source
    and saw cylinder rotation has stopped.
  • 8 CCR 4640(g)

63
(Ultra-Violet Radiation)
  • Areas, rooms or locations where equipment
    producing (ultra-violet) radiation is located
    shall be posted with warning signs or legends.
  • 8 CCR 5079(b), Ultra-Violet Radiation

64
(Radio-Frequency Radiation Hazard )
  • In areas where employee exposure may exceed the
    limits specified in part (b) of this section,
    employers shall provide warning signs containing
    the following information in the following
    manner
  • Warning signs of RF radiation hazards containing
    the necessary information
  • 8 CCR 5085(c)(1), RF/Microwave Radiation

65
(Radio-Frequency Radiation Hazard )

66
(No Cyanide in Nitrate Bath)
  • No salt containing any cyanide or any organic
    compound shall be added to a salt bath containing
    nitrate. Proper warning signs to this effect
    shall be posted near all such baths.
  • 8 CCR 5188(b)(1), Molten Salt Baths for
    heat-treating of metallic objects

67
(Fumigation)
  • Doors and windows shall be closed and sealed and
    legible warning signs shall be posted at all
    entrances or approaches. Signs shall state
    premises under fumigation and type of gas used
    and shall not be removed till fumigation and
    ventilation are complete.
  • 8 CCR 5223(a)(2), Fumigation

68
(Coyote Hole Blasting)
  • The area being loaded for blasting shall be
    plainly marked both in front and on top of the
    bank to be blasted with appropriate warning
    signs.
  • 8 CCR 5294(e), Coyote Hole Blasting

69
(Explosive Warning)
  • Areas where explosive materials are regularly or
    frequently detonated or burned shall be fenced or
    provided with controlled access and posted with
    warning signs.
  • 8 CCR 5330(b), Testing (of explosives)

70
(Authorized Persons Only)
  • Employees shall be prohibited from working below
    a building floor form installation, except those
    individuals actually engaged in this
    installation, removal, or inspection. Warning
    signs to this effect shall be posted at the
    perimeter of the affected work area.
  • 8 CCR 1717(d)(6)(A), Falsework

71
(Unauthorized persons stay out)
  • Signs meeting the requirements of the General
    Industry Safety Orders, Section 3340 shall be
    posted to warn unauthorized persons to stay out
    of the CDZ (Controlled Decking Zone - an area
    established specifically for the initial
    placement and securing of metal decking where
    access to the area is restricted).
  • 8 CCR 1710(n)(6)(c)(4)

72
(Water for Handwashing Only)
  • Handwashing facilities shall at all times meet
    the following standards Pure, wholesome, and
    potable water shall be available for handwashing.
    Signs shall be posted, indicating that the water
    is only for handwashing purposes.
  • 8 CCR 3457(c)(2)(G)(4)

73
(Marine Terminal Signs)
  • Every marine terminal shall have conspicuously
    posted signs as follows Locations of first aid
    facilities (and) telephones telephone numbers of
    the closest ambulance service, hospital or other
    source of medical attention, police, fire
    department, and emergency squad (if any) and
    locations of firefighting and emergency equipment
    and fire exits. Signs shall be clearly worded
    and legible, and shall contain a key word or
    legend indicating the reason for the sign. Key
    words are such words as Danger, Warning, Caution.
    Legends are more specific explanations such as
    High Voltage, Close Clearance, Pedestrian
    Crossing.
  • 8 CCR 3465(d)

74
(Laundry Workers Warning)
  • persons handling soiled clothes shall be warned
    by signs in their work area against touching
    eyes, mouth, or any part of the body on which the
    skin has been broken, abrased, or injured, and
    against touching or eating food unless their
    hands have been thoroughly washed.
  • 8 CCR 4494(b)

75
(Gas Piping Shut-Off Valves)
  • Signs clearly establishing the location and
    identity of (gas piping) section shut-off valves
    shall be provided.
  • 8 CCR 4827(d)

76
(Warning Falling Materials)
  • When debris is dropped through holes in the floor
    without the use of chutes, the area onto which
    the material is dropped shall be completely
    enclosed with barricades not less than 42 inches
    high Signs warning of the hazard of falling
    materials shall be posted at each level.
  • 8 CCR 1736(f), Disposal of Waste Material in
    Demolition

77
(Falling Debris)
  • Whenever waste material is dropped to any point
    lying outside the exterior walls of the building,
    enclosed chutes shall be used unless the area is
    effectively protected by barricades, fences or
    equivalent means. Signs shall be posted to warn
    employees of the hazards of falling debris.
  • 8 CCR 1736(a)

78
(Warning Falling Tools)
  • Waste, materials, or tools shall not be thrown
    from buildings or structures to areas where
    employee(s) may be located, unless the area where
    the material falls is guardedto prevent
    employee(s) from entering and being struck by
    falling objects. Signs shall be posted to warn
    employees of the hazard.
  • 8 CCR 1513(g), Housekeeping in Construction

79
(Wheelchair Elevator Rules)
  • Durable signs with lettering on a contrasting
    background shall be permanently and conspicuously
    posted at each landing indicating that passengers
    not in a wheelchair shall use the seat and seat
    belt, and passengers in a wheelchair shall secure
    the wheels of the wheelchair.
  • 8 CCR 3094.3(f), Inclined Platform (Wheelchair)
    Lifts

80
(Pedestrian Traffic)
  • Signs indicating pedestrian traffic shall be
    clearly posted at vehicular check-in and
    check-out lines and similar locations where
    employees may be working.
  • 8 CCR 3475(f), Vehicles in Marine Terminal
    Operations

81
(Safety on Amusement Rides)
  • The owner or operator shall use effective signs,
    videos, or other similarly effective means of
    advising patrons ofinstructions, limitations,
    restrictions, and warnings deemed necessary for
    patron safety... When signs are used for this
    purpose, they shall be permanently and
    conspicuously posted at each applicable permanent
    amusement ride.
  • 8 CCR 3195.7(b)

82
(Floor Loading Limits)
  • The live loads for which each floor or portion
    thereof of a commercial or industrial building
    shall have such design live loads conspicuously
    posted by the ownerusing durable metal signs,
    and it shall be unlawful to remove or deface such
    notices. The occupant of the building shall be
    responsible for keeping the actual load below the
    allowable limits.
  • 8 CCR 3241(a)

83
Finding Sign Requirements
  • Go to http//www.dir.ca.gov/Samples/search/query.h
    tm
  • Enter your query below
  • sign 109
  • signs 218
  • warning sign 25
  • warning signs 66

84
Information
  • This slideshow is available at http//www.baesg.or
    g/signs.ppt
  • A summary table is available at
    http//www.baesg.org/signs.htm
Write a Comment
User Comments (0)
About PowerShow.com