Title: First Trip
1First Trip
Jozef Levi Application Engineer Doble Engineering
Company
2Introduction
- What is First Trip?
- Definition
- What and how to monitor?
3What is First Trip?
- First Trip explanation
- Circuit breaker is mechanical device
- Require lubrication
- Recording of first operation after long idling
with breaker in service
4Definitions
- Opening time
- Trip coil current
- Auxiliary contact
- Main arcing contact and contact separation
- Control voltage
5Opening time
- The opening time is interval of time from
energizing of the opening release (opening coil)
for circuit breaker in closed position and the
instant when arcing contacts have separate in all
poles
energizing
Last arcing contact separate
6Trip Coil Current
I
Maximum Current
(A)
imax2
Contact 52a Open
Change in inductance
Trip Latch Release
t0-t2 pick-up time
imax1
t1-t2 transient time
t2 armature hit stop
t0-t3 ON period
t3-t4 fall time
t
t2
t0
t1
t4
t3
(ms)
7Auxiliary switch
- Auxiliary contacts are contacts that show the
circuit breaker position. At least one contact is
used in each control circuit (trip/close) to
control the coil supply.
- 52 a auxiliary switch
- S1 trip switch
- S4 selector switch
- Y1 trip coil
S1
S4
52a
Y1
8Main arcing contact and contact separation
- Contact separation during mechanical test
Opening time
Arcing contact parted phase A
9Main arcing contact and contact separation
- Contact separation during test with energized
breaker
Arcing contact separation
10Control voltage
- Control voltage is a DC supply to control close
circuit and trip circuits. - The operating mechanism with his control circuit
are designed for a rated control voltage but must
operate throughout a specific voltage range due
to variations in supply voltage - Close circuit Min voltage 85 of rated voltage
- Close circuit Max voltage 110 of rated voltage
- Trip circuit Min voltage 70 of rated voltage
- Trip circuit Max voltage 110 of rated voltage
11Control voltage
- Control voltage drop during trip operation
Control voltage (V)
Time (ms)
12Control voltage and Trip Coil Current
- Voltage supply imperfection frequency 300 Hz
13What to monitor?
- Two basic approaches
- 1. Monitor large number of breakers
distribution. Use of portable test device
specifically developed for first trip testing. - 2. Compare test results from same breaker
transmission. Use of regular circuit breaker test
instrument.
14Monitoring for comparison
- Use of circuit breaker test instrument
15Test Set-up
Circuit breaker in service
Test instrument
16Cable Connection
Main current measurement option l
Current probe in measuring transformer secondary
circuit
All connections are done in mechanism cubicle
17Cable Connection
Trip coil current measurement
Current probe in trip coil circuit
All connections are done in mechanism cubicle
18Test results
- Trip coil current, voltage supply and main current
Trip coil current
Supply voltage
Main current
19Test results
Initiation
Plunger stops
52 a opens
20Test results
Contact separation at First Trip
21Test results comparison
t
Contact separation at First Trip
Initiation
Contact separation at mechanical test
t time difference 2.6 ms
22Test results comparison
t
t time difference 2.6 ms
23Conclusion
- Easy to connect
- Results shows how breaker would perform in real
situations - Good for comparison with previous results
24(No Transcript)