Title: Optimum Performance of


1
  • Optimum Performance of
  • Radiator Space Heating Systems
  • Connected to District Heating Networks
  • via Heat Exchangers
  • Patrick Ljunggren, Janusz Wollerstrand
  • Svend Frederiksen
  • Lund Institute of Technology
  • Department of Energy Sciences
  • Sweden

2
Topics
  • Consequences of oversizing radiators (RADs)
    Heat EXchangers (HEXs)
  • Various RAD circuit control methods
  • Constant or variable RAD circuit flow
  • Various methods of upsizing HEXs
  • ?? ºC lower DH return temperature

3
(No Transcript)
4
(No Transcript)
5
  • Minimum primary return temperature, tr1, at
    altered radiator supply temp., trf, for
    increasing HEX area

6
Mode with excessive indoor air heating, simulated
instantaneous temperatures
space heating system 100 oversized
7
Standard temperature program (constant flow) and
optimized program (variable flow)
no oversizing of radiators or heat exchanger
8
Lowered supply temperature set-point curve
unchanged flowrate (full curves) and optimized
program (variable flow, dashed curves).
100 over-sized radiators and heat exchanger
9
Low flow balancing (design supply temperature,
full curve, and reduced flow, dashed curves)
100 over-sized radiators and heat exchanger
10
Difference (in C) in annual weighted return
temperature from space heating heat exchanger
versus reference case with a return temperature
of 44.9 C
0 oversized HEX 100 oversized HEX
0 oversized radiators, constant flowrate 0 -0.5
0 oversized radiators, optimized flowrate -1.8 -3.3
100 oversized radiators, low flow balancing, constant flowrate -12.3 -13.5
100 oversized radiators, lowered set point curve, constant flowrate -12.1 -12,3
100 oversized radiators, Optimized flowrate -14.9 -16,2
11
Primary return temperature and secondary supply
temperature at design heat load, assuming optimal
radiator circuit flowrate (four different
assumptions )
12
Conclusions
  • Radiator control should be optimised to minimise
    primary return temperature
  • By combining control optimisation HEX up-sizing
    gains in primary return of around 10ºC are
    possible