Massachusetts High-Performance Green Schools - PowerPoint PPT Presentation

1 / 12
About This Presentation
Title:

Massachusetts High-Performance Green Schools

Description:

This projects features include utilizing daylight extensively, ... Increased Glazing Efficiency. Baseline windows: U value = 0.57. Shading Coefficient = 0.88 ... – PowerPoint PPT presentation

Number of Views:29
Avg rating:3.0/5.0
Slides: 13
Provided by: nut3
Category:

less

Transcript and Presenter's Notes

Title: Massachusetts High-Performance Green Schools


1
Massachusetts High-Performance Green Schools
Case Study
  • Whitman-Hanson Regional High School
  • Library Media Center.
  • This projects features include utilizing daylight
    extensively, energy efficient lighting systems,
    and high performance windows.

2
Site Analysis
  • Understand solar orientation
  • Understand wind patterns
  • Understand natural resources (wetlands) and
    topography

Fact Smart site design can preserve natural
areas, minimize stormwater runoff, control
erosion, reduce heat islands, and prevent light
pollution.
3
Energy Efficient Building Design
  • Three story design to minimize the building area
  • Natural lighting throughout
  • Courtyard design to allow natural light into core
    spaces

4
Increased Glazing Efficiency
  • Baseline windows
  • U value 0.57
  • Shading Coefficient 0.88
  • Specified Windows
  • U value 0.31
  • Shading Coefficient 0.46
  • Solar Screen, Low-E, Blue Green

Fact Windows specified provide electricity and
natural gas savings by reducing cooling load due
to solar radiation and heating energy loss due to
heat conduction through the glass.
5
Increase Insulation R Values
  • Wall Insulation
  • Increased code minimum of R-7.5 continuous
    insulation
  • to R-10 continuous
  • Roof Insulation
  • Increased code minimum R-17.7 continuous
    insulation
  • to R-20 continuous

Fact Increased building insulation levels
improve energy performance.
6
Cool Roof Technology
  • Installation of a cool roof reduces heat gain on
    the building and reduces the heat island effect.
  • Cool roof used is a white membrane installed on
    95 of the roof surface.

FACT Buildings with light colored roofs can
realize a reduction in cooling energy by as much
as 40.
7
Whitman-Hanson Regional High School Energy
Efficient Systems Lighting
  • Daylight harvesting technologies
  • Direct/Indirect pendant fixtures
  • High-bay fixtures with compact fluorescents allow
    instant on-off
  • Reduced lighting power densities
  • All lighting fixtures manufactured in MA or RI

8
Energy Efficient Systems HVAC
  • High Efficiency condensing gas-fired boilers
  • Modular design allows staging boilers to match
    heating load
  • This 235,000 sq. ft. high school uses less gas
    than one of the districts existing 8 classroom
    elementary schools

9
Energy Efficient Systems HVAC
  • Fully reactive controls
  • Automated with occupancy controlled VAV boxes
  • Demand controlled ventilation in large spaces
  • Variable Frequency Drives (VFD) control fan and
    pump motors
  • Hybrid chilled water system
  • Multiple condensing DHW heaters
  • Centrally located mechanical room
  • Variable primary pumping (no secondary pumps)

10
Whitman-Hanson Regional High SchoolRenewable
Energy Systems
  • 51 kW PV system
  • Evergreen Solar panels manufactured in MA
  • Oriented due south at a 29 angle
  • Rack system did not require roof penetrations
  • Production last year
  • equaled 59,219 KWh

11
Whitman-Hanson Regional High School Case Study
Summary
  • 577,037 KWh electric savings per year relative to
    Code
  • 11,719 Therms gas savings per year relative to
    Code
  • 100,060 energy cost savings per year
  • 972,360 gallons water savings per year relative
    to Code
  • 1,109,800 total grants and rebates earned
  • 826,853 DOEd / MSBA state incentives
  • Net incremental cost to taxpayers (-70,404)

12
Energy Efficiency Programs in Massachusetts
Write a Comment