DIRECTIONAL CONTROL VALVES - PowerPoint PPT Presentation

1 / 45
About This Presentation
Title:

DIRECTIONAL CONTROL VALVES

Description:

Consists of a body with internal passages which are connected and disconnected ... Electrohydraulic Directional flow control valves ... – PowerPoint PPT presentation

Number of Views:2410
Avg rating:3.0/5.0
Slides: 46
Provided by: dawns7
Category:

less

Transcript and Presenter's Notes

Title: DIRECTIONAL CONTROL VALVES


1
Chapter 10
  • DIRECTIONAL CONTROL VALVES

2
Directional Control Valves
  • Consists of a body with internal passages which
    are connected and disconnected by a moveable
    part.
  • Moveable part is usually a spool.

3
4-way Directional Valve
  • Consists of a pump passage, tank passage and two
    actuator passages.
  • Has four distinct passages within its body.
  • Its main function is to reverse action in a
    cylinder.
  • Moving parts have two extremes shown
    symbolically the two squares are connected
    together but when in a circuit only one is
    connected in the circuit.

4
3-way Directional valve
  • Consists of valve-body pump passage, tank
    passage, and one actuator passage.
  • Function is to pressurize an actuator when the
    spool is in one extreme position and to exhaust
    when its in the other.
  • Used to operate single acting actuators like rams
    or spring-returns Fluid is directed into the cap
    end side of the cylinder. When in the other
    position the flow to actuator is blocked and the
    actuator passage within the body is connected to
    tank.
  • Not found very often in industrial hydraulic
    systems.

5
2-way Directional Valve
  • Consists of two passages that are connected and
    disconnected.
  • Flow through valve in one extreme position and
    blocked in the other.
  • Gives an on/off function used as a safety
    interlock and to isolate and connect various
    system parts.

6
Valve Size and Ratings
  • Come in some basic sizes ¼, 3/8, ½, 3/4 and 1¼
    inches.
  • Common to rate valves on their nominal flow
    rating. Example 3-10 gpm, 10-20 gpm, 40 gpm,
    80 gpm, and 160 gpm.
  • With ratings at the higher end the pressure
    differential pressure between P to A or B to T is
    approximately 40 psi.

7
Directional Spool valves
  • Different valves have different amount of lands
    on their spools.
  • With three large diameters spaced
  • equally apart connected with a
  • shaft such as used in 4-way
  • directional valves are known as
  • 3-land spool.
  • Most industrial valves have 2 or 4
  • land spools.
  • The small flow ratings usually use the 2-land
    spools.
  • The large flow ratings generally use the 4-land
    spools.

8
Subplate-mounted 4-way valves
  • The valves given as examples have had the tank
    and pump passages situated on one side and the
    actuator passages on the opposite side just like
    the schematic symbols are drawn.
  • In most systems, they are actually mounted on a
    subplate that has the valve body mounted to it
    and all the valve passages on the bottom surface.

9
Directional Valve Actuators
  • Spools are moved by either mechanical,
    electrical, hydraulic, pneumatic, or human
    energy.
  • Those moved by human energy are known as manually
    actuated valves. Ex levers, pushbuttons, and
    pedals
  • Used when actuators whose operation must be
    sequenced and controlled at operators discretion
  • When shifting of the valve must occur at the same
    time an actuator reaches a specific condition.

10
Pilot Operation
  • Spools are often shifted with fluid pressure
    either air or hydraulic.
  • Pressure is applied to the two extreme spool
    lands if it is a 4-land spool, or to separate
    pistons if it is a 2-land spool.

11
SOLENOID
  • An electromechanical device which converts
    electric power into linear mechanical force and
    motion which is a common way to operate a
    directional valve. Its counterpart in hydraulic
    system is a cylinder.
  • Come in two types Air gap and wet armature.

12
Air Gap Solenoid
  • Older of the two designs that consists of a
    T-plunger, wire coil, and C frame.
  • How it works
  • Electric current passes through a wire, setting
    up an electric field around the wire. This
    current is made stronger by the wire coiling.
  • An iron path is setup around the coil by the C
    frame, and another iron path in the center of the
    coil by the T-plunger, which is moveable.
  • At rest the T-plunger is partially out of the
    coil, when current is applied the plunger is
    attracted into the center causing the plunger to
    hit a pushpin, in turn shifting the spool in the
    valve.
  • With the spool shifted the plunger fully seats
    within the coil resulting in the magnetic field
    traveling completely through an iron path.
  • As the plunger moves in the air gap gradually
    decreases, thus increasing the solenoid force.

13
Wet Armature Solenoid
  • Been more accepted due to their increased
    reliability resulting from better heat transition
    characteristics and elimination of pushpin seals.
  • Consists of a coil, rectangular frame armature
    and tube.
  • The coil is surrounded by the plastic
    encapsulated rectangular frame with a hole that
    runs through the coil center and two sides of the
    frame.
  • The tube fits within this bore and screwed into
    the directional valve body.
  • The tube houses an armature which is bathed by
    system fluid with in the valve.

14
Wet Armature Solenoid
  • How it works
  • An electric current creates a magnetic field
    around the coils, which is magnified by the iron
    rectangular frame and the armature.
  • The armature is partially out of the coil as the
    coil begins to receive current. As it increases
    the armature is pulled into the coil.
  • The directional valves shifts as the armature
    hits the pushpin.
  • When the spool shifts the armature is fully
    centered within the coil and the coil magnetic
    field is moved completely through an iron path.
  • As the armature moves in the gap gradually
    decreases thus increasing the solenoid force.

15
AC Hum
  • Current moves from zero to positive, through zero
    to negative and back to zero at 60 Hz known as
    Alternating current (AC).
  • Magnetic field and solenoid force is greatest
    when current is at positive and negative peaks.
  • As current goes through zero the solenoid force
    decreases, this action pushes out the plunger.
  • As the force raises again, the plunger is pulled
    back in.
  • This in and out motion causes a humming, buzzing,
    or chattering known as AC Hum.

16
Shading Coils
  • To minimize AC hum, shaded coils are used.
  • Air gap Copper loops attached to the C-frame
    are used.
  • Wet armature copper wire ring at the pushpin
    end of the tube.
  • Works because current is generated in the shading
    coils that lags behind the applied current which
    is generally sufficient enough to hold the
    plunger/armature in place when the magnetic field
    of the coil is at its lowest value.

17
Eddy Currents
  • AC magnetic current fluctuations that cause stray
    currents, which move in tiny circles around the
    iron magnetic paths. They consume power and
    generate heat reducing solenoid force.
  • Air Gap - to minimize the C frame and plunger are
    made up of thin metal sheets, insulated from one
    another with an oxide coating which allows the
    magnetic current to flow but the eddy currents
    cannot.
  • Wet armature to minimize the square frame is
    made from laminated thin metal sheets. This is
    not practical for the armature, so it is made of
    one piece.

18
Solenoid Inrush current
  • AC current is a source of heat generation for a
    solenoid, which over time will cause the coil to
    fail.
  • The goal is to achieve sufficient holding and
    shifting force with as little current as
    possible, to avoid the over generation of heat
    eventually leading to coil failure.
  • The designing sufficient AC resistance is known
    as impedance.
  • The result of pure resistance to electron flow of
    the conductor material. E.g. copper offers less
    resistance than aluminum
  • The effect generated by the electromagnetic field
    surrounding the coil which tends to restrict
    current flow the stronger the magnetic field the
    less current flows in solenoid windings.
  • As energized the magnetic field is not at peak
    due to the high resistance gap, so resistance
    flow is coming from the pure resistance to the
    electron flow from conductor material
    consequently high inrush current is experienced
    in coil windings. This decreases as the plunger
    becomes fully seated which at this time
    impedance is at its peak and AC current is at is
    minimum.

19
Solenoid Inrush current
  • As energized the magnetic field is not at peak
    due to the high resistance gap, so resistance
    flow is coming from the pure resistance to the
    electron flow from conductor material
    consequently high inrush current is experienced
    in coil windings. This decreases as the plunger
    becomes fully seated which at this time
    impedance is at its peak and AC current is at is
    minimum.
  • If anything obstructs the plunger/armature large
    amounts of current will rush into the coils
    generating large amounts of heat.
  • Causes plastic material on coil ends to melt.
  • Causes encapsulated designs to get bubbles on the
    coating.
  • Wire insulation deteriorates quickly causing coil
    failure in a minute or two.

20
Continuous duty solenoid
  • One that can be held energized indefinitely
    without overheating.
  • Its heat dissipating ability is such that it will
    dissipate the heat generated at the coils lower
    holding current.
  • Most industrial hydraulic direction valves are
    this.

21
Solenoid Limitations
  • Cannot be used in wet or explosive environments.
  • When the cycle life of directional valve is
    extremely long, electrically controlled solenoids
    not used.
  • The force generated by them to shift a valve is
    limited.

22
Solenoid failure
  • Fail because of the heat, which is usually the
    result of
  • Blockage something that stops the plunger from
    being completely seated thus causing an inrush of
    current resulting in large heat generation
    eventually resulting in coil failure.
  • The valve spool can become blocked from
    contamination of build up between it and the
    valve body and thus not allowing the plunger to
    seat.
  • Due to a valve base that is not flat.
  • Wear patterns can develop between the plunger and
    the C-frame, overtime not allowing the plunger to
    fully seat.
  • High ambient temps since heat must dissipate
    from the coil, if surrounding air temp is high,
    it becomes more difficult and the coil may burn
    out. Such is the case if it is operating in poor
    ventilated area, or the machine is a source of
    heat.
  • Low voltage if line voltage drops below 100
    volts for the 60 Hz solenoid it has insufficient
    force to seat the plunger resulting with inrush
    currents eventually causing coil failure.

23
Manual Override
  • Air gap solenoids usually have a cover to protect
    them. At the cover end, a small pin is located
    in line with the plunger. Pushing this pin will
    result in manually shifting the plunger and in
    turn the valve spool, overriding the solenoid
    function.
  • In wet armatures the pin is located at the end of
    the tube which houses the armature and pushpin.
  • Used to check movement of the directional valve
    spool.
  • Used to cycle an actuator without energizing the
    complete electrical control system.

24
Solenoid controlled pilot operated spring offset
  • Two position directional valve uses a solenoid to
    shift the pilot valve spool to an extreme
    position, the spool is returned via spring.

25
Detents
  • Is a locking device which keeps a spool in the
    desired shifted position.
  • Used when two actuators are used to shift the
    spool of a two position valve.
  • Spool of detented valve has notches and groove.
    With each being a receptacle for a spring-loaded
    moveable part.
  • Directional valves equipped with detents are not
    required to keep their actuators energized to
    achieve a shifted position.

26
Center Conditions
  • 4-way directional valves are frequently three
    position valves with two extreme positions and a
    center position.
  • The two extremes are directed related to the
    actuator motion.
  • The center is designed to perform logic or
    satisfy a need or condition of the system.
  • Varieties are open, closed, tandem and float
    centers. Accomplished using the same valve body
    with the appropriate spools.

27
Open center
  • A directional valve with an open center has all
    passages connected to each other in the center
    position.
  • Used in single actuator circuits actuator
    completes its cycle, the directional valve spool
    is centered and the flow returns to the tank at
    low pressure and the actuator is free to move.
  • Disadvantage is that no other actuator can be
    operated while valve is centered and a cylinder
    load cannot be held in mid-stroke position.

28
Closed Center
  • A directional valve with a closed center has all
    passages blocked.
  • Stops the motion of an actuator and allows each
    actuator to operate independently from one power
    source.
  • Disadvantages
  • The pump flow cannot unload to tank through the
    directional valve during actuator idle time.
  • The spool leaks just as in any spool valve, so if
    the spool is subjected to system pressure for any
    longer then a few minutes, pressure will build
    in the passages causing them to leak.

29
Tandem Center position
  • A directional valve with tandem center has P and
    T passages connected and the actuator passages
    blocked.
  • Stops actuator motion but allows pump to return
    to the tank while system is idling.
  • Many times one valves T port is connected to
    another valves P port allowing for actuators to
    be operated individually or together, and
    emptying of the pump to the tank through the
    valve during idle times.
  • The P and T passages are connected together in
    the same valve body through a passage in the
    spool shaft.
  • Disadvantages
  • The flow rating for the valve is reduced.
  • If used as a replacement for valve with different
    configuration, the actuator controlled by the
    directional valve will operate backwards if all
    other things change the same.

30
Float Center
  • Directional valve with float center has P passage
    blocked and the other three positions connected
    in the center position.
  • Allows independent operation of actuators tied to
    the same power source and allows free movement of
    each actuator.
  • Does not create a buildup in pressure in the P
    passage controlling rod drift.
  • Disadvantage is that load cant be stopped or held
    in place. If this is necessary then use in
    conjunction with a pilot operated check valve.

31
Crossover conditions
  • The crossover conditions are what the valve see
    for a fraction of a second while the spool is
    shifting from one extreme to another.
  • Closed crossover does not allow a pump/electric
    motor pressure to drop during a spool shift.
  • An open crossover allows actuator lines to bleed
    slightly before reversal takes place this
    bleeding helps eliminate shock as a load changes
    direction.

32
Solenoid controlled pilot operated directional
valve
  • Directional control valves are often shifted via
    a solenoid. But the larger ones, those greater
    then 40 gpm require too much force for direct
    solenoid shifting.
  • This are done by piggy backing a solenoid
    operated directional control valve with the
    larger valve.
  • Pilot pressure moves the main valve spool but the
    solenoid controls the pilot.

33
Spool Centering in Pilot operated valve
  • Its held in the center position by fluid or
    springs.
  • Springs are most common there is a spring
    located at each end of the spool, a spring is
    compressed when the spool moves into an extreme
    position with the spring then moving it back to
    the center position. Spring centering have
    trouble handling flows beyond their intended
    capacity.
  • Hydraulically centering ensures that the spool
    will center even with excessive flow rate. To
    center a valve this way, fluid is just pumped to
    both ends of the valve spool simultaneously.

34
Choke control
  • When the main spool of the pilot operated valve
    is shifted shock can be developed as large fluid
    controls are forced to change direction quickly.
    A choke control slows the spool shift reducing
    this shock, but not totally eliminating.
  • Choke control is a sandwich valve fitting
    between the main valve body and the pilot valve.
  • Sandwich consists of two needle valves and two
    bypass check valves.
  • As the spool shifts in one direction a needle
    valve meters flow out of the pilot spring
    chamber.
  • As the spool reverses the other needle valve
    meters flow out of the other pilot spring
    chamber.
  • The more the needle valves are restricted for
    flow the slower the spool shift, thus reducing
    the shock.

35
Stroke Adjustment
  • Stroke adjustor is a screw adjustment which
    limits spool travel in the main valve of a
    solenoid controlled, pilot operated directional
    valve.
  • This is not recommended for direct AC solenoid
    valve.
  • Partially limiting the spool travel in one
    direction means that a port is not completely
    uncovered, causing a restriction through the
    valve when the spool is shifted in one direction.
  • If stroke adjustor is screwed in completely on
    extreme position is blocked out essentially
    turning a 3-position valve into a 2-positon valve
    with positions in one extreme and the center.

36
Directional Valve drain
  • Pilot valve tank passage of a solenoid
    controlled, pilot operated directional valve is
    the drain.
  • The tank port of the pilot valve is connected by
    means of an internal passage to the tank passage
    of the main valve.

37
Directional Valve pilot pressure
  • Pilot pressure is what is used to shift the main
    valve spool.
  • The P port of the pilot valve is directly
    connected to the P passage of the main valve by
    means of an internal passage, making an internal
    pilot connection. Pilot pressure is the same
    value as system pressure in this case.
  • Externally piloting is necessary when internal
    pilot pressure is too low or too high.
  • Desirable if the system pressure is too high
    also.
  • To change from internal to external an internal
    pipe plug must be added.
  • Sometimes required when back pressure check valve
    is positioned into the pressure line ahead of the
    valve.

38
Backpressure Check Valve
  • With tandem and open center directional valves it
    is often the case that the back pressure and
    pressure required to shift the main valve spool
    is greater then the system pressure being
    supplied.
  • This can be overcome with the use of a
    backpressure check valve.
  • It has a stiffer spring, which requires more
    pressure to be present at the valve inlet to push
    the poppet off its seat, thus allowing for extra
    pressure to be supplied to the pilot valve.
  • Can be positioned in pressure or tank lines and
    can be located in the valve or externally to the
    valve.
  • If used in a tank line, the valve must be
    externally drained.

39
Electrohydraulic Directional flow control valves
  • Meet the use for higher response, stiffer
    systems, better flow characteristics with and
    efficient way to interface electronic control
    systems with hydraulic recovery systems.
  • Two types are proportional and servo.

40
Proportional vs. Servo
  • Response
  • Proportional is the time required for the valve
    to achieve maximum rated flow due to an
    electrical step input command signal.
  • Servo is the frequency response which is
    expressed in hertz with the frequency of a small
    sine wave command signal with flow amplitude of
    about -3db.
  • Servo 10-300 Hz vs. Proportional 2-10 Hz.
  • Spool center condition
  • Servo are critically lapped by carefully matching
    both the width and the position of the spool
    lands to the metering recesses within the valve.
    These require line-line contact by hand fitting
    increasing costs.
  • Proportional designed so that the spools and
    valve bodies are interchangeable resulting in a
    crossover overlap on the order 10-30 of the
    total stroke. This causes dead banding which
    results in instability.

41
Proportional vs. Servo
  • Hysteresis the measurement of the difference in
    electrical command signal as percentage of rated
    electrical command for a given flow output.
  • Repeatability an indication of the ability of
    the valve to repeat a given flow when a given
    electrical command signal is repeatedly applied
    to the valve.
  • Threshold the smallest discreet change in
    electrical command signal that will produce a
    corresponding change in output flow.
  • Open loop proportional exhibit levels as high as
    10 while closed loop for both are 3 or less.
  • Filtration requirements Servos require 3
    micrometers or less because of their close
    tolerances proportional only require about 10
    micrometers.

42
Proportional Valve
  • Consists of the torque motor pilot valve, adapter
    block, wire mesh pilot filter, internal pilot
    pressure regulator, main spool and body, and LVDT
    (linear variable differential transducer),
  • How it works
  • Main spool is in the center condition and all
    ports are blocked by the lands of the spool
  • One solenoid is energized moving the main spool
    in that direction
  • The LVDT is attached directly to the main spool
    which measures the precise movement of the spool
    and feeds this back to the electronics so that
    the correct solenoid can be activated.

43
Torque Motor Pilot
  • This is a pressure differential type proportional
    directional valve operates in two stages
  • 1st stage the pilot valve consists of coil,
    armature, suspension member, diverter plate, and
    blade.
  • 2nd stage main valve consists of a spool,
    return springs and an LVDT, similar to that of a
    standard directional valve.

44
Servo Valve
  • Consists of first stage pilot valve and second
    stage spool valve with a mechanical feedback
    spool position to the torque motor assembly.
  • 1st stage has three possible designs a flapper
    nozzle, jet pipe and jet diverter. They have
    varying nozzle sizes but typical 0.010, 0.008 and
    0.020 minimums respectively. The larger the
    orifice the more contamination tolerant the valve
    is.
  • 2nd stage spool land at the center position can
    and does vary depending on the requirements of
    the system. Most require them to be line to line
    if possible.

45
Servo Land configurations
  • Line to line results in an ideal flow gain plot
    where the output flow to the cylinder ports is
    zero with the spool in the center position and
    increases immediately with spool travel.
  • Under lapped has more clearance between the
    spool land edges and metering notches or ports in
    the spool sleeve or valve body. Results in
    higher leakage flow.
  • Overlapped Reduce leakage flow to a minimum and
    no cylinder port flow will occur until the spool
    has traveled through the overlap. Creates
    deadband (a zone of valve movement in either
    direction from center where no actuator response
    to signal occurs).
Write a Comment
User Comments (0)
About PowerShow.com