Title: Commercial Thermostats Portfolio Wholesaler Version 307
1Commercial Thermostats PortfolioWholesaler
Version- 3-07
- http//customer.honeywell.com
2Why Commercial Stats?
- Honeywell Commercial stats comply with the
commercial building codes - Economizer, 2 hour override, autochangeover, No
Hold - Commercial stats have the right feature set
- Occupied/Unoccupied terminology ( Not wake,
leave, sleep, return) - Autochangeover out of the box
- Partial and Full Lockout Levels with Override
buttons - Commercial stats have a commercial algorithms
- More aggressive to deal with commercial buildings
loads - More sensitive and shorter sensor response time
- Commercial stats support auxiliary commercial
devices - Any number remote sensors (Residential requires
1, 4, or 9 sensors) - Economizers (other stats enable on Fan G
terminal waste energy) - Actuators (modulating, floating)
- More Impactful Energy Savings
- Economizer, Holiday button, Overrides, No Hold
3Segmentation of Thermostat Platforms
T7351F
TB8220
Advanced Control PID Algorithm Multi
Stage Remote Sensing Economizer Control Temp.
Lockouts 365 Day Scheduling Holiday
Programs Dehumidification
TB7220
Semi-Advanced Control Commercial Algorithm Multi
Stage Remote Sensing Economizer
Control Touchscreen interface
Basic Control Commercial Algorithm Multi
Stage Remote Sensing Economizer Control
T7300F Q7300
- Obsolete by Summer 2007?
- Commercial Algorithm
- Multi Stage
- Remote Sensing
- Economizer Control
Application Requirements
4Commercial VisionPRO Preference Results
End Users Prefer Commercial VisionPRO
5CommercialPRO 7000 Features
1 Choice in Thermostats Honeywell is the
leading brand in temperature control
Large Display Display size is more than twice
the size of competing thermostats in this class
Economizer OutputActivates Economizer based on
time of day or Economizer logic, resulting in
less energy usage and better indoor air quality.
Up to 2 Heat / 2 Cool Conventional and 3 Heat / 2
Cool Heat Pump
Configurable Recovery RampsAutomatically changes
temperature so it ramps up gradually, helping
prevent oversized equipment from going beyond
desired temperature
Saves EnergyEffortless, 7-day programming saves
up to 33 on annual heating and cooling costs
Energy Star Compliant
2-Year Warranty
Holiday SetbackLets users easily select
temperature to maintain while theyre away from
the building without re-programming
Remote Temperature Sensing Compatible with 10K or
20K remote temperature sensors, allowing for
various averaging options. Increases temperature
response and improves comfort level faster.
Multiple Lockout LevelsSave energy and money by
preventing unauthorized setting changes
Title 24 Energy/Air Quality CompliancePreoccupanc
y Purge and Override Limits meet all fresh air
and override limitation requirements
Automatic Daylight Savings ShiftThermostat
automatically adjusts for daylight savings time
6Commercial VisionPRO 8000 Features
1 Choice in Thermostats Honeywell is the
leading brand in temperature control
Economizer OutputActivates Economizer based on
time of day or Economizer logic, resulting in
less energy usage and better indoor air quality.
Up to 2 Heat / 2 Cool Conventional and 3 Heat / 2
Cool Heat Pump
Configurable Recovery RampsAutomatically changes
temperature so it ramps up gradually, helping
prevent oversized equipment from going beyond
desired temperature
Saves EnergyEffortless, 7-day programming saves
up to 33 on annual heating and cooling costs
Energy Star Compliant
5-year Warranty
Holiday SetbackLets users easily select
temperature to maintain while theyre away from
the building without re-programming
Remote Temperature Sensing Compatible with 10K or
20K remote temperature sensors, allowing for
various averaging options. Increases temperature
response and improves comfort level faster.
Multiple Lockout LevelsSave energy and money by
preventing unauthorized setting changes
Title 24 Energy/Air Quality CompliancePreoccupanc
y Purge and Override Limits meet all fresh air
and override limitation requirements
Automatic Daylight Savings ShiftThermostat
automatically adjusts for daylight savings time
7T7351F Features
1 Choice in Thermostats Honeywell is the
leading brand in temperature control
Economizer OutputActivates Economizer based on
time of day or Economizer logic, resulting in
less energy usage and better indoor air quality.
Up to 3 Heat / 3 Cool or 2 Heat / 4 Cool
Conventional and 3 Heat / 2 Cool Heat Pump
Configurable Recovery RampsAutomatically changes
temperature so it ramps up gradually, helping
prevent oversized equipment from going beyond
desired temperature
Saves Energy365-day programming saves money on
annual heating and cooling costs
Energy Star Compliant
1-year Warranty
Holiday SetbackLets users easily select
temperature to maintain while theyre away from
the building without re-programming
Remote Temperature and Humidity
Sensing Compatible Honeywells line of commercial
temperature and humidity sensors. Increases
temperature response and improves comfort level
faster.
Multiple Lockout LevelsSave energy and money by
preventing unauthorized setting changes
Title 24 Energy/Air Quality ComplianceOverride
Limits and economizer output meet all
requirements
Automatic Daylight Savings ShiftThermostat
automatically adjusts for daylight savings time
8TB Commercial Stats Application Guide
- Schools Individual Zone Control
- CANCEL PERIOD button allows the thermostat to
remain in permanent unoccupied mode to provide
energy savings to school classrooms not being
used. When a teacher wants to use a classroom,
they press the OVERRIDE button and the thermostat
enters the occupied period providing the
necessary comfort. - Restaurant Food Service
- Honeywells COMMERCIAL ALGORITHM provides the
best comfort control to react to the challenging
environments of food service environments.
Restaurants have high heat load demands from
cooking equipment, high heat/cool demands from
frequent atrium entrance openings/closings, and
high load demands based on fluctuating occupant
numbers. The ECONOMIZER function allows
restaurants to meet the appropriate ventilation
requirements and is also important to BALANCE the
air intake of the restaurant.
9TB Commercial Stats Application Guide
- Office Buildings After Hours Control
- Honeywell commercial thermostats can perform
after-hours control for office building tenants
through the use of the OVERRIDE button. The
override button can be configured for a length of
time (1, 2, 3, 4 hours) and can be configured for
an exact override setpoint. - Commercial Codes
- Honeywell TB Commercial stats comply with
commercial building codes and meet the most
rigorous standard, Californias Title 24. The
commercial stats do not have HOLD button, which
allows the thermostat to be in PERMANENT
SCHEDULE. The OVERRIDE button allows the tenant
to override an unoccupied mode for up to 4 hours.
- The PRE-OCCUPANCY purge function and ECONOMIZER
function allows the building owner to meet all
HVAC ventilation codes for commercial buildings.
10T7351F Application Guide
- Schools
- The 365 DAY CALANDER makes the T7351F ideal for
classroom use as up to 10 HOLIDAYS can be
scheduled into the HOLIDAY scheduler. - The DEHUMIDIFICATION features can be implemented
to control dew points in school buildings. - For school gymnasiums or auditoriums, the
T7351Fs PID ALGORITHM is the best control
algorithm available that can heat and cool large
spaces quickly and accurately. - Banks
- The T7351F is ideal for banks because the 365 DAY
CALANDER can program up to 10 HOLIDAYS into the
HOLIDAY scheduler. - Churches
- For public worship locations, the T7351Fs PID
ALGORITHM is the best control algorithm available
that can heat and cool large spaces quickly and
accurately. The PID ALGORITM is specifically
tuned for over-sized equipment and has a short
sensor time constant that can react quickly to
load changes.
11T7351F Application Guide
- Retail
- The T7351F CUSTOMIZABLE RECOVERY RAMP feature
guarantees that your store will be at the exact
temperature specified when the store opens. - Office Building Zones
- The T7351F is the only Honeywell thermostat that
integrates with OCCUPANCY sensors for office
zones that are normally unoccupied or partially
occupied. - The T7351F WALL MODULES, including the T7771 and
T7770B/C/D models, provide end-users with
flexibility to control optimal comfort during
occupied events. - The T7351F CUSTOMIZABLE RECOVERY RAMP feature
guarantees that the office zone will be at the
exact temperature specified when the office
opens.
12ZonePRO TB6980/7980 VAV Modulating/Floating
Digital Stats
- Attractive look and feel
- Easy to operate, override button
- Backlight button
- SKU and Inventory count reduction
- Four models cover all floating and modulating
- applications
- VAV, electric heat, aux heat, hydronic
- AHU System Limited Cooling, Seasonal Changeover
- TB6980A1007, TB6980B1006, TB7980A1006,
TB7980B1005 - - Additional outputs for analog/triac, triac
- Accessories Air duct probe, electromechanical
relays, -
- Powerful Features
- C or F selectable
- Autochangeover VAV AHU level
- Max/min temp limits
- Night setback with temporary override
- Battery free data backup
13T6570 Series Fan Coil Stats
F/C
Digital display of setpoint /or temperature
PI control EEPROM memory
Installer setup options time delays range stops
Pushbutton adjustment
Line volt rated
Custom Logo option
Simple user interface
Manual fan speed control
14Remote Sensors
15Installation
- Temperature Averaging Networks
- T7770A1006 (20K NTC)
- T7770A3002 (10K NTC)
- TB8220 or TB7220- Setup 340 4
Two 10Ks in series 20K. Each has 50 weight
Two 20Ks in parallel wired in series with a 10K
20K.Each 20K has 25 weight, the 10K has 50
weight
16Installation
- Temperature Averaging Networks
Thermostat
S2
S1
Four 20Ks in series-parallel 20K.Each 20K has
25 weight
T7770A3002
T7770A3002
T7770A3002
T7770A3002
T7770A3002
Four 10Ks in series-parallel wired in series
with a 10K 20K.Each 10K in series-parallel has
12.5 weight, the other 10K has 50 weight
17Installation
- Temperature Averaging Networks
Four 10Ks in series-parallel wired in series
with two 20Ks in parallel 20K.Each 20K has
25 weight, each 10K has 12.5 weight
18Installation
- Temperature Averaging Networks
Thermostat
S1
S2
T7770A1006
T7770A1006
T7770A3002
T7770A3002
T7770A3002
T7770A1006
T7770A1006
Four 20Ks in parallel wired in series with two
10Ks in parallel wired in series with one 10K
20K.Each 20K has 6.25 weight, each 10K in
parallel has 12.5 weight, the 10K in series has
50 weight
19Installation
- Temperature Averaging Networks
Thermostat
S1
S2
T7770A1006
T7770A1006
T7770A1006
T7770A3002
T7770A3002
T7770A1006
T7770A1006
T7770A1006
Four 20Ks in parallel wired in series with two
10Ks in parallel wired in series with two 20Ks
in parallel 20K.Each of the four 20Ks in
parallel has 6.25 weight, each 10K in parallel
has 12.5 weight, each of the two 20Ks in
parallel has 12.5 weight
20Installation
- Temperature Averaging Networks
Thermostat
S1
S2
T7770A1006
T7770A1006
T7770A1006
T7770A1006
T7770A1006
T7770A1006
T7770A1006
T7770A1006
T7770A1006
Nine 20Ks in series-parallel 20K Each 20K has
an 11.1 weight
21 www.honeywell.com