Title: VARIABLE SPEED PUMPING
1VARIABLE SPEED PUMPING
Techsys Corporation
2BASICS
- VARIABLE SPEED PUMPING is only advantageous when
there is a - VARIATION in the FLOW
- demand of a system
- If the system is fixed flow with no variations
the VFD pumping is not beneficial
3PUMP CURVE
The Pump curve defines the Pump Capacity At
various flow rates
The Power curve is defined Vs Flow and Head
4SYSTEM CURVE
The System curve defines the System
Resistance At various flow rates
5Constant Flow Pumping
Power Absorbed at 100 Design Flow Rate
Static Head
6Variable Speed Pumping
The variable Speed Curve Can track the System
Curve Or a Fixed pressure
7Variable Speed Efficiency Curves
- Best Efficiency follows a quadratic equation
- The Affinity Laws cover Power, Speed Head at
variable speed
8POWER LOSS PUMP SPEED
Power is proportional to the CUBE of the pump
speed
9PUMP Vs SYSTEM CURVE
If the flow rate changes the fixed speed pump
must follow the curve And take the system curve
with it
10PUMP SPEED CHANGE FOLLOWS SYSTEM CURVE
- Changing Pump Speed tracks the system Curve
- Can follow the system requirements without
- Excess loading on the pump or system
11POWER VARIATION
- For every 10 speed change
- POWER changes by
- 27
- 0.9 x 0.9 x 0.9 0.729 72.9 of full load
12TYPICAL PUMP SELECTION
- Most engineers select a pump and add a
- SAFETY FACTOR
- This Safety Factor is the cause of inefficiency.
- Typically any variation from B.E.P. of more than
15 will cause major energy losses
13RUNNING COST SAVINGS
RUNNING COSTS Savings are the main advantage of
VFD Pumping
14RUNNING COST SAVINGS
- Based on
- 50 average flow
- demand
- Standard ISO pump
- 20c/kW hr
- BEP eff 76
Payback periods 6 12 months Motor size
dependant
15TYPICAL NON-VFD CONTROL
- There are three main ways for operators
- to attempt to match the system curve
- with Fixed speed pumps
- Throttle the discharge
- Re-circulate unwanted flow
- Start Stop the pump within
- pressure bands
16Throttled system
17Power Consumption with Throttled Control
18PUMP THROTTLING
19THROTTLED DISCHARGE
- Excessive power consumption
- Causes pump damage from cavitation
- Valve damage due to excess velocity
- Creates water hammer
- Not desirable
20Throttling Example
Wasted Power
Based on a 37kW pump with dump valve control
21FIXED SPEED PRESSURE CONTROL
Typical pressure control system CUT IN
Pressure CUT Out Pressure Suitable for operation
when Cycling is limited
22PRESSURE SYSTEM
- Best range of operation of a pump
- is generally 60 80 of Full Flow
- Pressure system needs to operate out of this
range
23VFD Vs PRESSURE SYSTEM
- VFD System can vary the flow efficiently over
most of the pump curve
24VFD Vs PRESSURE SYSTEM
Starting costs become significant at high cycle
rates
25VFD Vs PRESSURE SYSTEM
Any system that Operates below 50 of DESIGN
FLOW of the pump for over 20 of the time
should consider VFD pumping
26What Control Parameter ?
- PRESSURE
- Provides the ability to sense the load
- Easy to sense
- Provides a full picture of the system load via
the system curve - Suits over 90 of applications
27Typical Control Parameters
28WHY MULTI PUMP SYSTEM ?
- CAN HOLD BEST
- EFFICIENCY POINT
- OVER A GREATER RANGE
- MORE ECONOMICAL FOR THE FULL RANGE OF FLOW RATES
- COST OF COMPONENTS (VFD AND SWITCHGEAR) LOWER FOR
SMALLER POWERS - SEAL COOLING CONSIDERATIONS FOR MINIMUM FLOW RATES
29MULTI PUMP
Efficient Range 60-100 of design flow
rate If the flow span is greater than this then
the system is operating outside best efficiency
50
40
60
70
Pump curve
30MULTI PUMP
Pump Head
50
40
50
40
60
60
70
70
Efficient Range 30-100 of design flow rate
with multiple pumps
31The different types of pumps
Advantages using VFD
Centrifugal pumps Best performance
Reciprocating positive displacement pumps Fine
adjustment and tuning
Rotary positive displacement pumps Surge
dampening and adjustment
32VFD PUMP SYSTEM MANUFACTURERS
MODELS
33VFD PUMP SYSTEMS
There are numerous BMS and Electricians that
program PLCs for Pump control Operation -Buyer
Beware There is significantly more than meets
the eye Use reference site for evaluation
34DIFFERENT TYPES OF VFD CONTROL SYSTEMS
- Three types of VFD pump control
- On pump control Motor VFD
- Lead VFD backup soft start
- True VFD VFD rotates to all pumps.
35ON MOTOR VFD
- Neat Engineering solution
- Purpose built Inverter for pumps
- Very compact
36ON MOTOR VFD
- Suffer from Vibration and
- overheating
- Replacement components can
- be difficult to source
- Multi mump co-ordination
- difficult
37ONE VFD PER PUMP
- Operational VFD on each pump
- When extra pumps are required the system calls in
additional VFD/Pump combinations - The system can have all of the VFDs functioning
at a speed - All pumps vary the speed together
38ONE VFD PER PUMP
- Most expensive option
- Pumps operate furthest from B.E.P. as the load is
shared on all pumps - Tight control difficult
- Does not justify extra expense for risk
management
39LEAD VFD - LAG SOFT STARTER
- Multiple pump
- First pump started is the VFD pump
- Lag pumps operate on fixed speed
- Set point 20
40LEAD VFD - LAG SOFT STARTER
- System pressure can
- Spike at changeover
- Requires rapid reaction
- time at changeover
- Needs damped reaction
- at operating set point
- Basic instability at
- SET Point
41ROTATING VFD SYSTEM
- VFD starts on First pump
- As the load increases the First pump is switched
to fixed speed - The second pump starts on VFD etc.
42ROTATING VFD SYSTEM
- Smoothest operation
- Best set point holding characteristics
- Lowest starting current
- Softest on pumps and reticulation
43RISK ANALYSIS OF SYSTEMS
44CURRENT DRAW FOR VARIOUS SYSTEMS
45SUMMARY
- VFD Systems are ideal for pumping with
- systems that have variable flow rates
- Variable speed systems generally operate best
with Pressure control - Multiple pumps typically are most efficient and
are the least expensive - Use a Brand Name control system