Basic Air Sealing - PowerPoint PPT Presentation

1 / 107
About This Presentation
Title:

Basic Air Sealing

Description:

Basic Air Sealing – PowerPoint PPT presentation

Number of Views:42
Avg rating:3.0/5.0
Slides: 108
Provided by: patrickc95
Category:
Tags: air | basic | meez | sealing

less

Transcript and Presenter's Notes

Title: Basic Air Sealing


1
Basic Air Sealing
2
Basic Air Sealing
  • DHCR Policy
  • Job Set-up
  • Blower Door Set-up
  • Diagnostics
  • Basic Air sealing techniques

3
DHCR Policy
  • A blower door test must be conducted on all 1-4
    unit buildings and mobile homes during both the
    original inspection and the post inspection.
    Both single point and multi-point testing are
    acceptable methods for measuring air leakage
    rates.
  • If a single point test is used as part of the
    initial audit, the test should be conducted three
    consecutive times to ensure reasonable accuracy.
  • (PPM Chapter 5, page 114)

4
DHCR Policy
  • If a multi-point test is used, the test should
    include readings as close to 50 pascals as
    possible (e.g. 60-55-50-45-40) to provide the
    most accurate measurement of CFM 50. The
    correlation coefficient for a multi-point test
    must be at least .9900. Single point tests are
    recommended when windy conditions may result in a
    correlation coefficient less than .9900
  • (PPM Chapter 5, page 114)

5
DHCR Policy
  • For buildings with multiple units One blower
    door test of the whole building is preferred. If
    that is not possible, tests should be performed
    on each isolated portion of the building and the
    results should be added together for the total
    building air leakage measurement.
  • (PPM Chapter 5, page 114)

6
DHCR Policy
  • The AIRG is the site specific minimum airflow
    rate established by blower door testing. It is
    determined by the size and number of rooms in the
    unit, the number of occupants, the number of
    smokers occupying the unit, with a minimum
    airflow rate of 1500cfm _at_50pa.
  • (PPM Chapter 5, page 113)

7
DHCR Policy
  • 1500 cfm _at_50pa is the baseline airflow standard
  • Multiply the number of rooms by 170cfm_at_pa. This
    is the rooms air flow standard
  • Add the number of bedrooms plus one (1) to
    determine an occupancy number. If the number of
    occupants is actually greater, use the actual
    occupancy rather than the calculated potential
    occupancy number. Add one additional person for
    each smoker living in the unit to determine the
    final occupancy number. Multiply the final
    occupancy number by 340cfm _at_50. This becomes the
    number of occupants airflow standard.
  • Compare the three airflow standards. The larger
    of the three standards becomes the final air flow
    standard for the building.
  • (PPM Chapter 5, page 113)

8
DHCR Policy
  • Successful air sealing should reduce air flow to
    the Maximum Allowable at Post (MAP). Failure to
    achieve the MAP must be documented and placed in
    the building file along with the pre and post
    blower door results. Air sealing should not
    reduce that air flow below the AIRG.
  • (PPM Chapter 5, page 113)

9
DHCR Policy
  • The MAP is determined by using the formula
  • (Pre CFM50-AIRG)x 20 AIRG MAP
  • (PPM Chapter 5, page 113)

10
DHCR Policy
  • If a vented space heater which take combustion
    air from the living space (wood, coal or pellet
    stove, vented gas or oil space heater, etc) is
    present then the AIRG may be increased by 1000
    CFM50 for every 100,000 BTU/hr (input rating) to
    allow make up air for combustion.
  • (PPM Chapter 5, page 113)

11
DHCR Policy
  • Where the air flow of a building is below 1500
    cfm50 an evaluation of existing conditions that
    may affect the indoor air quality (carbon
    monoxide sources, moisture sources, CAZ pressure,
    chimney draft, etc.) is required
  • (PPM Chapter 5, page 113)

12
DHCR Policy
  • Blower door testing should be suspended if it is
    determined that harmful pollutants will be
    introduced into the living space by the operation
    of the blower door.
  • (PPM Chapter 5, page 113)

13
DHCR Policy
  • Air sealing work must be blower door assisted.
    Documentation of interim blower door testing is
    required. All interim tests are required to be
    recorded and included in the job folder.
  • (PPM Chapter 5, page 114)

14
DHCR Policy
  • A comprehensive health and safety evaluation of
    all CAZs must be completed each day following
    air sealing work.
  • Negative Pressure Test in CAZ
  • Backdraft Pressure Test
  • Ambient Air CO Test
  • (PPM Chapter 5, page 114)

15
Job Set-up
16
Diagnostics
17
(No Transcript)
18
(No Transcript)
19
(No Transcript)
20
(No Transcript)
21
(No Transcript)
22
(No Transcript)
23
(No Transcript)
24
(No Transcript)
25
(No Transcript)
26
(No Transcript)
27
(No Transcript)
28
Blower Door Set-up
29
Perform an Evaluation of Current Airflow Rates
  • Properly configure building
  • Combustion appliances disabled
  • winter mode
  • conditioned areas open for testing
  • ductwork registers opened
  • Conduct Blower Door Test
  • select best location for 1 family and
    multi-family (out of wind and away from heavily
    trafficked areas)
  • Interpret Results
  • CFM 50

30
Provide Airsealing Measures
  • Repair obvious holes in the bldg. envelope
  • missing or broken windows, doors,
  • below grade entries,
  • fallen plaster from walls and ceilings
  • door and window weatherstripping

31
This Could Be the Single Largest Air Reduction
Measure you will perform
  • Install high density cellulose at the envelope
    (at least 3.5 pounds per
    cubic foot)
  • sidewalls, wherever possible
  • attics with floor decks
  • band joist areas between floors

32
(No Transcript)
33
(No Transcript)
34
  • Seal interstitial frame with durable materials (
    high density cellulose, flashing, mastic)
  • enclosed stairwells
  • attached roof cavities
  • interior wall cavities
  • chimney and soil vent penetrations

35
(No Transcript)
36
(No Transcript)
37
(No Transcript)
38
(No Transcript)
39
(No Transcript)
40
(No Transcript)
41
(No Transcript)
42
(No Transcript)
43
(No Transcript)
44
(No Transcript)
45
(No Transcript)
46
(No Transcript)
47
(No Transcript)
48
(No Transcript)
49
(No Transcript)
50
(No Transcript)
51
(No Transcript)
52
(No Transcript)
53
(No Transcript)
54
(No Transcript)
55
(No Transcript)
56
Distribution System
57
No Duct Tape Please
  • Seal ductwork with durable materials (latex
    based mastic/butyl backed metal tape)
  • fan cabinet and plenum attachments
  • that big hole where the air filter goes
  • as many return air leaks as is humanly possible
  • boot connections to the floor or wall

58
(No Transcript)
59
(No Transcript)
60
(No Transcript)
61
(No Transcript)
62
(No Transcript)
63
(No Transcript)
64
(No Transcript)
65
(No Transcript)
66
(No Transcript)
67
(No Transcript)
68
(No Transcript)
69
(No Transcript)
70
(No Transcript)
71
(No Transcript)
72
(No Transcript)
73
(No Transcript)
74
(No Transcript)
75
(No Transcript)
76
(No Transcript)
77
(No Transcript)
78
(No Transcript)
79
(No Transcript)
80
(No Transcript)
81
(No Transcript)
82
Attic By-Passes
83
(No Transcript)
84
(No Transcript)
85
(No Transcript)
86
(No Transcript)
87
(No Transcript)
88
(No Transcript)
89
(No Transcript)
90
(No Transcript)
91
(No Transcript)
92
(No Transcript)
93
(No Transcript)
94
(No Transcript)
95
(No Transcript)
96
(No Transcript)
97
(No Transcript)
98
(No Transcript)
99
(No Transcript)
100
(No Transcript)
101
(No Transcript)
102
(No Transcript)
103
(No Transcript)
104
Whats Not Worth Doing
  • Installing fluffy cellulose in sidewalls/attics
  • Caulking/sealing dusty,dirty surfaces
  • Exterior caulking (except to correct drainage
    plane)
  • Using duct tape as a building repair material
  • Purchasing new storm windows
  • Obsessive caulking of trim and moldings

105
When To Stop
  • When Youve reached the AIRG
  • When you dont know what to do next.
  • When reducing the number further may cause a
    Health Safety problem
  • Negative pressure in CAZ
  • Pets/Smokers
  • Add Direct Ventilation when Testing shows
    necessary

106
Basic Air SealingWhat We Covered
  • DHCR Policy
  • Job Set-up
  • Blower Door Set-up
  • Diagnostics
  • Basic Air sealing techniques

107
Thats All Folks
Write a Comment
User Comments (0)
About PowerShow.com