ECE 8830 Electric Drives - PowerPoint PPT Presentation

1 / 38
About This Presentation
Title:

ECE 8830 Electric Drives

Description:

In variable-speed applications in which a small variation of motor speed with ... The performance of the drive for subway traction application is shown below: ... – PowerPoint PPT presentation

Number of Views:115
Avg rating:3.0/5.0
Slides: 39
Provided by: ankineedu
Category:

less

Transcript and Presenter's Notes

Title: ECE 8830 Electric Drives


1
ECE 8830 - Electric Drives
Topic 12 Scalar Control of AC Induction
Motor Drives Spring
2004
2
Introduction
  • Scalar control of an ac motor drive is only
    due to variation in the magnitude of the control
    variables. By contrast vector control involves
    the variation of both the magnitude and phase of
    the control variables.
  • Voltage can be used to control the air gap
    flux and frequency or slip can be used to control
    the torque. However, flux and torque are
    functions of frequency and voltage, respectively
    but this coupling is disregarded in scalar
    control.

3
Introduction (contd)
  • Scalar control produces inferior dynamic
    performance of an ac motor compared to vector
    control but is simpler to implement. In
    variable-speed applications in which a small
    variation of motor speed with loading is
    tolerable, a scalar control system can produce
    adequate performance. However, if precision
    control is required, then a vector control system
    must be used.

4
Speed Control
  • Three simple means of limited speed control
    for an induction motor are
  • 1) Reduced applied voltage magnitude
  • 2) Adjusting rotor circuit resistance
  • (suitable for a wound rotor machine
  • and discussed earlier)
  • 3) Adjusting stator voltage and frequency
  • These are discussed in section 9.2 Ong text and
    are not presented further here.

5
Constant Air Gap Flux
  • Generally, an induction motor requires a
    nearly constant amplitude of air gap flux for
    satisfactory working of the motor. Since the air
    gap flux is the integral of the voltage impressed
    across the magnetizing inductance, and assuming
    that the air gap voltage is sinusoidal,
  • Thus a constant volts/Hz ratio results in a
    constant air gap flux.

6
Constant Air Gap Flux (contd)
  • The torque-speed curves with a constant air
    gap flux at different excitation frequencies are
    shown below

7
Constant Air Gap Flux (contd)
  • From the curves on the previous slide, it can
    be seen that we will obtain the same torque at
    the same value of slip speed if we operate at a
    constant air gap flux. This is the basis for
    constant volts/Hz control of an induction motor.
    This type of control may be implemented either in
    open loop or in closed loop.

8
Constant Air Gap Flux (contd)
  • A set of 6-step voltage waveforms illustrating
    constant volts/Hz is shown below

Ref D.W. Novotny and T.A. Lipo, Vector Control
and Dynamics of AC Drives
9
Open Loop Volts/Hz Control of a Voltage-Fed
Inverter
  • Three regions of operation for the induction
  • motor are possible
  • 1) Holds slip speed constant and regulates stator
    current to obtain constant torque.
  • 2) Holds stator voltages at its rated value and
    regulates stator current to obtain constant
    power.
  • 3) Holds stator voltage at its rated value and
    regulates slip speed just below its pull-out
    torque value.

10
Open Loop Volts/Hz Control of a Voltage-Fed
Inverter (contd)

11
Open Loop Volts/Hz Control of a Voltage-Fed
Inverter (contd)
12
Open Loop Volts/Hz Control of a Voltage-Fed
Inverter (contd)
  • The open loop volts/Hz control of an induction
    motor is very popular because of its simplicity.
    A block diagram of such a control system is shown
    below

13
Open Loop Volts/Hz Control of a Voltage-Fed
Inverter
  • The power circuit comprises
  • 1) A diode rectifier supplied by either a
  • single-phase or three-phase supply
  • 2) An LC filter
  • 3) A PWM voltage-fed inverter.
  • The primary control variable is the frequency
    ?e??r. The commanded phase voltage Vs is
    generated by a gain stage based on the speed ?e
    to maintain a constant air gap flux.

14
Open Loop Volts/Hz Control of a Voltage-Fed
Inverter (contd)
  • As the frequency becomes small at low speed,
    the voltage drop across the stator resistance can
    no longer be neglected and so a boost voltage V0
    needs to be supplied allowing the rated flux (and
    thus the full torque) to be available down to
    zero speed. The effect of the boost voltage is
    negligible at higher frequencies.

15
Open Loop Volts/Hz Control of a Voltage-Fed
Inverter (contd)
  • The drives steady state performance for a fan
    or pump-type load (TLK?r2) is shown below

16
Open Loop Volts/Hz Control of a Voltage-Fed
Inverter (contd)
  • As the frequency is increased the speed
    increases almost proportionally and we move along
    the load torque curve from points 1-gt2-gt3 etc.
    moving smoothly through the different operating
    modes of the induction motor.

17
Open Loop Volts/Hz Control of a Voltage-Fed
Inverter (contd)
  • Let us now look at the effects of dynamic
    variations in load torque and line voltage.
  • Suppose the load torque is changed from TL to
    TL for the same frequency command, the speed
    will drop slightly from ?r to ?r. This type of
    speed variation can easily be tolerated by a fan
    or pump.
  • Now suppose the operating point is a and the
    line voltage drops so that the operating point
    moves to b. Again the speed is tolerable for some
    applications.

18
Open Loop Volts/Hz Control of a Voltage-Fed
Inverter (contd)
  • The safe acceleration/deceleration
    characteristics are shown below

19
Open Loop Volts/Hz Control of a Voltage-Fed
Inverter (contd)
  • Assume a pure inertia type load and the motor
    initially operating at point 1. A small step
    increase in command frequency will initially move
    the operating point to point 2 (the rated torque)
    and then steadily increase to point 3. The
    frequency can then be decreased slightly to
    achieve the steady state operating point 4. All
    of these transitions are done in a gradual manner
    to prevent the machine from becoming unstable.
    Decrementing the frequency command in a step will
    shift the operating point from 1 to 5 due to a
    negatively developed torque.

20
Open Loop Volts/Hz Control of a Voltage-Fed
Inverter (contd)
  • The motor torque and speed are related by
  • where J moment of inertia,
  • Te torque developed by motor,
  • and TL load torque
  • With the rated Te the slope of the
    acceleration curve d?r/dt is determined by J. The
    higher J, the smaller the slope.

21
Open Loop Volts/Hz Control of a Voltage-Fed
Inverter (contd)
  • Typical Volts/Hz drive performance is shown
    below

22
Energy Savings with Variable Frequency Drives
  • Considerable energy savings can be achieved
    with variable frequency drives compared to
    constant frequency drives (see figure below and
    text).

23
Closed Loop Volts/Hz Control with Slip Regulation
  • An improvement over open loop Volts/Hz control
    is closed loop Volts/Hz control with slip
    regulation (see block diagram below).

24
Closed Loop Volts/Hz Control with Slip Regulation
(contd)
  • Here the speed loop error generates a slip
    command ?sl via a proportional-integral
    controller and limiter. This slip command is
    added to the feedback speed signal ?r to get the
    frequency command ?e which, in turn, generates
    the voltage command through a volts/Hz function
    generator. Since slip is proportional to torque
    at constant flux, this approach may be considered
    as open loop torque control within a speed
    control loop.

25
Closed Loop Volts/Hz Control with Slip Regulation
(contd)
  • If a step-up speed command is provided, the
    motor accelerates freely until a slip limit
    (corresponding to the motors torque limit) is
    achieved and then settles down to the steady
    state load-limited torque.
  • If ?r is stepped down, the drive behaves as a
    generator and decelerates with constant negative
    slip - ?sl. However, the value of - ?sl must
    be limited to a safe margin below the slip speed
    corresponding to the pull-out torque point.

26
Closed Loop Volts/Hz Control with Slip Regulation
(contd)
  • Since the slip speed is relatively small
    compared to the rotor speed, this mode of
    operation requires precise measurement of the
    rotor speed. Also, in negative slip mode of
    operation, the regenerated power must either be
    dissipated in a braking resistor or fed back to
    the ac mains.
  • One disadvantage of this approach is that the
    flux may drift due to load torque or supply
    voltage variations.

27
Closed Loop Volts/Hz Control with Slip Regulation
(contd)
  • A speed control system with closed loop torque
    and flux control is shown below. However,
    additional feedback control loops increases
    system complexity and potential stability
    problems.

28
Current-Regulated Voltage-Fed Inverter Drive
  • Instead of controlling inverter voltage by the
    flux loop, the stator current can be controlled
    which has the benefit of providing inherent
    overcurrent protection to the switching devices
    as well as achieving direct control of the motor
    torque and air gap flux.
  • A current-regulated VSI drive, with torque and
    flux control in an outer loop and hysteresis-band
    current control in the inner loop, is shown on
    the next slide.

29
Current-Regulated Voltage-Fed Inverter Drive
(contd)
  • Flux control loop -gt stator current amplitude
  • Torque control loop -gt frequency command
  • Only need 2 current sensors since iaibic 0
  • (for an isolated motor neutral).

30
Current-Regulated Voltage-Fed Inverter Drive
(contd)
  • The performance of the drive for subway
    traction application is shown below

31
Traction Drives with Parallel Machines
  • Multiple voltage-fed inverters can be operated
    in parallel. An example of such a system for a
    locomotive drive is discussed in the Bose text,
    pp. 348-349.

32
Current-Fed Inverter Control
  • Some of the same principles for control of
    voltage-fed inverters can be applied to
    current-fed inverters. However, the current-fed
    inverter cannot be operated open loop.
  • The simplest implementation of a closed loop
    control system for a current-fed inverter,
    allowing independent control of dc link current
    Id and slip ?sl, is shown on the next slide.

33
Current-Fed Inverter Control (contd)

34
Current-Fed Inverter Control (contd)
  • In this implementation, the fed back rotor
    speed ?r and command slip ?sl are added to give
    the command frequency ?e. The dc link current Id
    is controlled by a feedback loop that controls
    the output voltage of the rectifier, Vd.
  • With ve slip, acceleration occurs with -ve
    slip, Vd and VI both become -ve and power is fed
    back to the source.
  • The torque can be controlled either by Id or
    ?sl. However, no flux control is possible with
    this control scheme.

35
Current-Fed Inverter Control (contd)
  • Speed and flux control can be achieved in a
    current-fed inverter using the below control
    system.

36
Current-Fed Inverter Control (contd)
  • In this case the speed control loop controls
    the torque by slip control (as before) but also
    controls the current Id by a pre-computed
    function generator to maintain a constant flux.
    This open loop approach is satisfactory but the
    machine flux may still vary with parameter
    variations. An independent flux control loop (as
    shown earlier for the voltage-fed inverter) can
    be implemented for tighter flux control if
    desired.

37
Current-Fed Inverter Control (contd)
  • A volts/Hz implementation for a current-fed
    inverter is shown below
  • A particular advantage of this approach is
    that the motor flux is unaffected by line voltage
    variation.

38
Efficiency Optimization Control by Flux Program
  • Normally a motor is operated at its rated flux
    because the developed torque is high and the
    transient response is fast. Under light loads,
    this can lead to poor efficiency of the drive.
    The rotor flux can be lowered at light loads so
    that the motor losses are reduced and the
    conversion efficiency of the drive optimized. See
    text pp. 352-254 (Bose) to see how this may be
    achieved.
Write a Comment
User Comments (0)
About PowerShow.com