Title: Managing Harmonics A case study Jim Bridgeman PFC Engineering
1Managing Harmonics A case studyJim
BridgemanPFC Engineering
2Introduction
- Basics of harmonic resonance
- Effects of harmonic resonance
- Typical solutions applied to resonant Power
Systems - Harmonic magnification case study
3The Basics of Harmonic Resonance
4Effects of Harmonic Resonance
5Effects of Harmonic Resonance
6Effects of Harmonic Resonance
- Increased voltage distortion, possibly resulting
in equipment malfunction - Loss of transformer output due to increased
heating - Interference with communication systems
- Premature failure of motors
- Premature failure of power factor correction
capacitors
7Typical Solutions Applied to Resonant Power
Systems
- Detuning reactors
- Partial harmonic filtration
- Full harmonic filtration
8Typical Solutions Applied to Resonant Power
Systems Detuning Reactors
9Typical Solutions Applied to Resonant Power
Systems Partial Filtration
10Typical Solutions Applied to Resonant Power
Systems Full Filtration
11Comparison of Harmonic Resonance Solutions
12Comparison of Harmonic Resonance Solutions
13Case Study Harmonic Magnification at a Car
Battery Factory
- Large 5th harmonic magnification excited by 600
kVAr of capacitors - Costly installation of detuning reactors appeared
to be the only solution - A more cost effective solution involving
reconfiguration of the existing plant was found
14Case Study Initial System Configuration
(Transformer T1)
- Plain capacitors
- All non-linear loading
- No load damping
15Case Study Initial System Configuration
(Transformer T2)
- Nearly all linear loading
- Significant load damping
16Case Study Effects of 5th Harmonic Voltage
Magnification
17Case Study Effects of 5th Harmonic Voltage
Magnification
18Case Study Reasons for severity of 5th harmonic
voltage magnification
- High base level of harmonics due to all
non-linear load being connected to this supply - Connection of plain capacitor banks
- Total lack of harmonic damping from linear loading
19Case Study Proposed Solution to Problem of
Harmonic Magnification
20Case Study Improvement in Harmonic Performance
with Re-configured Load
21Case Study Effects of 5th Harmonic Voltage
Magnification
22Conclusions
- Harmonic resonance can be caused by connection of
Power Factor Correction equipment - Various methods of avoiding this scenario
involving blocking / filtration systems are
available - Careful examination of the problem and more
appropriate load configuration can provide more
cost effective solution to the problem - Questions?