AS4391 HOT SMOKE TEST Kowloon Station Development - PowerPoint PPT Presentation

1 / 13
About This Presentation
Title:

AS4391 HOT SMOKE TEST Kowloon Station Development

Description:

Satisfactory operation of smoke detection. Correct sequence of control of alarms, smoke vents and applicable air inlet arrangements ... – PowerPoint PPT presentation

Number of Views:289
Avg rating:3.0/5.0
Slides: 14
Provided by: philh68
Category:

less

Transcript and Presenter's Notes

Title: AS4391 HOT SMOKE TEST Kowloon Station Development


1
AS4391 HOT SMOKE TESTKowloon Station
Development
2
The Project
  • Large Retail / Public Concourse Development
  • Complex layout and escape routes
  • Smoke management zoning and extraction via static
    vents
  • FSD Requirement for Hot Smoke Test

3
Prime Test Objectives
  • To verify correct performance of the smoke
    management system against approved design-
  • Satisfactory operation of smoke detection
  • Correct sequence of control of alarms, smoke
    vents and applicable air inlet arrangements
  • Attaining adequate smoke layer depths / smoke
    clear heights
  • Visual demonstration of smoke venting performance
    including satisfactory flow of smoke.
  • Conformance to HK FSD Circular Letter 2/2002

4
AS4391 Methodology
  • Standard Test Fire Sizes Available
  • Tabular Data for different heights-
  • plume volume flow rate
  • plume temperature
  • Use of Data Tables -
  • Interpolate for required height
  • Select nearest test fire size giving ceiling
    temperature 10Clt sprinkler activation temperature

5
Data per AS 4391 Table A1 A2
6
Smoke Clear Height Plume Volume
7
Test Measurement Philosophy
  • Mandatory Ceiling Temperature Measurement above
    plume
  • Vertical thermocouple tree located away from
    turbulent plume (assess rate of accumulation of
    smoke in reservoir)
  • Visual and thermographic assessment of smoke
    behaviour
  • Record actual detector operation time
  • Extract operation time simulated to match design
    sprinkler response time
  • Alcohol tray heat source per AS4391 configuration
  • Tracer smoke injected into entrained plume - high
    injection adopted to avoid burning of smoke

8
Atrium Location for Test
9
Technology
  • Type K thermocouple array and telemetry cables
  • PC based data logging
  • Infra red imaging camera
  • Video cameras
  • Communications
  • Access platform/s for installing telemetry
  • Fire extinguishers / standby fire crew with
    breathing apparatus and appliances

10
Typical Layout
11
Data Logging
  • Analysis of smoke layer growth before and during
    static extract

12
Lessons Learned from Trial
  • Relocate thermocouple tree to less turbulent
    position

13
Thermal Imaging
  • Views of the plume and smoke layer satisfactorily
    stratifying within the confines of the smoke zone