Title: Okuma Memorial Hall Base Isolation Retrofit


1
Okuma Memorial HallBase Isolation Retrofit
  • Taft Tucker
  • Rice University

2
Waseda University
  • Founded in 1882 by samurai scholar Okuma
    Shigenobu
  • One of oldest and most prestigious universities
    in Japan
  • About 45,000 undergrads including almost 7,000
    Science and Engineering students

3
Okuma Hall
  • shortly after Okumas death in 1922 construction
    began
  • Construction delayed by Great Kanto Earthquake
  • Construction Completed in 1927

4
Base-Isolation Retrofit
  • Would reduce superstructure damage in the event
    of earthquake
  • However, very expensive to retrofit

5
(No Transcript)
6
(No Transcript)
7
Static Analysis
  • FEM Model
  • Subjected to Japans standard lateral earthquake
    loading (Ai Coefficient)

194.5 kN
194.5 kN
194.5 kN
40.5 kN
51 kN
51 kN
123.5 kN
123.5 kN
8
Derivation of Lateral Stiffness
  • Used nodal displacements to calculate inter-story
    drift and derive lateral stiffness to be used in
    dynamic analysis

0.283 in.
9
Earthquake Analysis Fixed Base Case
  • Natural period and damping of building was found
    by solving eigenvalue problem. T .62 sec.
  • Subjected building to scaled El Centro earthquake
    with max ground acceleration 150 cm/sec2
  • Used Linear Acceleration Method to return top
    story deflection, velocity, and acceleration and
    base shear time-history plots.

10
Dynamic Analysis Results Base Shear
1183 kN
  • Max Base Shear 1183 kN

11
Dynamic Analysis Results Shear Coefficients
  • First Level 0.30 Second 0.42 Third 0.45
    Fourth 0.47

12
Dynamic Analysis Results Deflection
4.22 cm
  • Max Deflection 4.22 cm

13
Dynamic Analysis Results Velocity
41.6 cm/s
  • Max Velocity 41.6 cm/s

14
Dynamic Analysis Results Acceleration
5.47 m/sec2
  • Max Acceleration 5.47 m/sec2

15
Base Isolation Model
  • Used multiple degree of freedom model for base
    isolation analysis with base stiffness set to
    give a period of 3 seconds.
  • Passive Analysis
  • Yield Load Set to 1 of building weight
  • Compared with Uncontrolled Case
  • Damper Yield Load set to zero
  • Scaled El Centro
  • 150 cm/sec2 for comparison with fixed base case

16
Passive Control w/ Friction
  • Magnetorheological Damper used at isolation level
  • Yield load is static value throughout excitation,
    passive control
  • Behavior is similar to passive friction damper

17
Passive Results Top Story Acceleration
  • Max Acceleration 0.57 m/sec2
  • reduction of 90 compared to fixed base case

18
Passive Results Base Deflection
  • Max Base Displacement 5.1 cm
  • Decreased from 18.5 cm (72) in No Friction
    Damping Case

19
Passive Results by Story
  • Acceleration Deflection
  • Max 0.57 m/sec2 Max
    5.1 cm

20
Passive Results Base Shear
  • Max Base Shear 231 kN
  • 80 reduction from fixed base case

21
Damper Forces
Yield Force
Yield Force 1 of Building Weight
22
Is passive good for stronger EQ?
-- El Centro -- Taft -?- Hachinohe
  • As Earthquake acceleration increases,
    effectiveness at reducing deflection decreases.

23
Semi-Active Control
  • Used MR damper to vary level of damping on base
    of building by changing the yield load of Damper
  • Yield Load varied by changing electric current
    supplied to damper

24
Semi-Active Control Strategy
  • Yield Load a x Mass x Absolute Acceleration
  • Performed Optimal Alpha Analysis to Decide which
    alpha would best reduce both Acceleration and
    Deflection
  • Used Scaled Hachinohe, Taft, and El Centro
    Earthquakes
  • Max Acceleration 500 cm/sec2

25
Semi-Active Control Strategy
  • Yield Load a x Mass x Absolute Acceleration

26
Optimal Alpha Analysis Acceleration
0.3
27
Optimal Alpha Analysis Deflection
0.3
28
Semi-Active Control Results Top Story
Acceleration
  • Max Acceleration .59 m/sec2
  • Roughly equivalent to passive damping

29
Semi-Active Control Results Base Deflection
  • Max Deflection 7.5 cm
  • Increase of 2.4 cm from Passive Control

30
Semi-Active Control Results by Story
Deflection
Acceleration
31
Semi-Active Control Results Base Shear
  • Max Shear 405 kN
  • Increase from passive case

32
Base Shear - Active vs. Passive
33
Semi-Active Control Results Damper Forces
34
How does Semi-Active Control Perform in
Larger Earthquakes?
Percentage of Uncontrolled Deflection
35
Conclusions
  • Base Isolation would reduce forces in Okuma Hall
    during EQ, however displacement is increased
    considerably.
  • Passive control reduces displacement for small
    EQ, but does not perform well under larger EQ.
  • Semi-Active Control should be used to control
    deflection in event of large EQ.