Kenyas experience in switchgear and controlgear - PowerPoint PPT Presentation

1 / 36
About This Presentation
Title:

Kenyas experience in switchgear and controlgear

Description:

The creepage of switchgear bushings is 31mm/KV. according to IEC 60815 [1]. For the less polluted environment (inland) the creepage is. 25mm/KV. ... – PowerPoint PPT presentation

Number of Views:104
Avg rating:3.0/5.0
Slides: 37
Provided by: kpl5
Category:

less

Transcript and Presenter's Notes

Title: Kenyas experience in switchgear and controlgear


1
Kenyas experience in switchgear and controlgear
  • A Presentation at IEC Affiliate members workshop
    in Cape Town on 2005-10-20

2
  • Presenter Joel M. Kiilu
  • Paper prepared by
  • Joel M. Kiilu
  • Dr. Humphrey Ndwiga
  • Francis Ouma
  • Cyrus Khalusi

3
CONTENT
  • 1. INTRODUCTION
  • 2. CHALLENGES OF SWITCHGEAR AND CONTROLGEAR
  • SERVICE CONDITIONS
  • 3. PROCUREMENT OF SWITCHGEAR AND
  • CONTROLGEAR THROUGH OPEN TENDERS.

4
1.0 INTRODUCTION
  • Kenya became an associate member of IEC in April
    this year.
  • The Kenya National Committee of IEC launched in
    August, 2005.
  • Presentation to share Kenyas experience in
    switchgear and controlgear operations and
    specifications made in an attempt to meet the
    challenging service conditions.

5
1.1 Usage and manufacture of switchgear
  • Firms in Kenya that use high and medium voltage
  • switchgear and controlgear
  • Those that generate electricity ( KenGen and
    IPPs)
  • Electricity Transmission and Distribution
    company(KPLC)
  • Industries
  • No high or medium voltage switchgear and
  • controlgear is manufactured in Kenya.

6
1.2 Existing grid voltages
  • Existing power systems in Kenya
  • - transmission system 220KV and 132KV.
  • - immediate future plans, a 330kv system inter
  • connecting Kenya and Tanzania.   
  • - distribution grid - 66KV, 33KV and 11KV.
  • - Customer own systems - 6.6KV, 3.3KV
  • systems. 
  • - low voltage system comprises 415volts
  • 3phase and 240volts -single phase.

7
1.3 Type of switchgear and controlgear installed
  • This grouping is in terms of insulation and arc
  • quenching medium employed
  • High voltage switchgear - SF6 and mineral oil
  • Medium voltage - SF6 Vacuum and mineral oil
  • Low voltage - Air 
  • The load-break switches air
  • High voltage bulk oil and minimum volume oil
  • outdoor circuit breakers are being phased out.
  • Use of SF6 indoor breakers is being discontinued
    in
  • preference to vacuum breakers.(SF6 gas is
    environmentally
  • unfriendly)

8
Composition of the different types of switchgear
in Nairobi City and its Environs
9
1.4 Experience on the performance based on
arc-quenching medium. 
10
(No Transcript)
11
2. CHALLENGES OF SWITCHGEAR AND CONTROLGEAR
SERVICE CONDITIONS
  • Kenya has unique conditions which present
    varying challenges while drafting switchgear and
    controlgear specifications.
  • Service conditions
  • Salinity, humidity and pollution
  • Service altitude 0 - 3000 metres above sea
    level. 
  • Climatic conditions desert-savannah- tropical
  • forests.
  • Environmental conditions
  • limited resources for system reinforcement.
  • high electricty demand
  • Stringent procurement rules

12
 2.1 Salinity, humidity and pollution
  • Saline conditions in the coastal region of Kenya
    form deposits of
  • salt on equipment bushings/insulators.
  • Dust from cement factories settle on switchgear
    insulators.
  • -leading to tracking currents on the
  • surface of insulators.
  • Humidity and salinity cause corrosion of exposed
  • metal parts resulting to
  • -mal-operation of air break switches
  • -shortening of equipment life.
  • -equipment failure
  • Geothermal plants ( in the Rift Valley) too emit
    hydrogen sulphide
  • that is corrosive.
  •  

13
Picture No. 1 Corroded 33kV isolator at Kipevu
Power Station in Mombasa- Coast Region
14
Picture No.2 Rusted tripping springs of a 132KV
single pole breaker at Rabai (Coastal region) 
15
Specification requirements
  • a)In order to reduce the problems of tracking  
  • The creepage of switchgear bushings is 31mm/KV
  • according to IEC 60815 1.
  • For the less polluted environment (inland) the
    creepage is
  • 25mm/KV.
  • Where possible the bushings of the switchgear is
  • silicone based (hydrophobic).
  • b)In order to reduce the problems of corrosion
  • All the external ferrous parts of the switchgear
    is
  • painted to 80 microns or heavy duty galvanized.
  • Where possible metallic parts should be replaced
    with materials
  • that do not react with salt.
  • Provision of heaters with temperature and
    hygrostat controls in control panels.
  • Switchgear should meet the specified service
    condition.
  •  
  •  

16
2.2            Altitude and lightning 
  • Electricity reticulation covers areas whose
    altitude is 3000m above sea level (Kenya
    highlands). The thin air weakens insulation
    across bushings resulting to flash overs which
    usually crack the bushings.
  • Incidentally these areas also experience high
    lightning strikes. The isokeraunic level is about
    180 thunderstorm days a year. The lightning
    strikes cause damage mostly to outdoor
    switchgear, surge diverters and transformers.
  •  

17
Picture No. 3 Flashover on poles of a 36kv
breaker installed in Eldoret .
18
Mitigations on altitude and lightning
  • To mitigate against the effects of altitude and
  • lightning the following requirements have been
  • added to the switchgear specifications 
  •  
  •   Increased use of lightning shield wires on the
    lines and
  • masts in substations. 
  • Use of arcing horns as a substitute protection
    when the
  • surge arrestors get destroyed due to high
    lightining
  • discharges.
  • For given altitude derating of insulation is
    applied as
  • per IEC 60694 3. Derating of switchgear
    voltage
  • rating according to IEC 60071 2 as
    shown in the
  • table below.

19
Switchgear for altitudes above and below 1000m
above sea level.
  •  

20
2.2     Burning of switchgear terminations
  • Usually caused by high resistance termination -
    arising from thermal cycles or galvanic
    corrosion.
  • Heat also causes the cement sealing SF6 gas in
    circuit breakers to melt - allowing the gas to
    escape
  • To reduce these occurances switchgear
    specifications require 
  • Connection terminal silver or tin-coated
    should be
  • scratch-proof.
  • Air-break switch contacts to be silver plated
    at the
  • connection points and the contacts to be
    spring loaded.

21
Picture No. 4 burnt cable terminations of an
indoor switchgear in Nairobi
22
2. 3     High solar radiation
  • Effects of high solar radiation in some
    regions 
  • Derating of load carrying capacity to avoid
    exceeding temperature rise limit.
  • In cases where ethylene-propylene diene monomer
    (EPDM rubber) has been exposed to the atmosphere
    there are incidents of cracking due to the solar
    ( Ultra violet) radiation
  • To reduce the effect of Utra violet radiation the
    following
  • requirements have been added to the switchgear
    specifications 
  •  
  • Manufacturers equipment shall comply to this
    service
  • condition
  • Exposed EPDM rubber shall not to be used.

23
2.4 System Constraints (Reinforcement) 
  • Incidents during which switchgear explode while
    clearing faults.
  • Cases where downstream faults are cleared by
    upstream switchgear instead of the associated
    breaker down stream.
  • Attempts to break light load using a disconnector
    culminating into phase to phase fault and contact
    failures.
  • mostly affected - switchgear rated at 25KA/3sec
    short circuit current and below that is installed
    where the system fault level is high.

24
Probable causes 
  • Switchgear short circuit current rating low
  • Power system Transient recovery voltage higher
    than switchgear voltage rating
  • Very many fault operations resulting to
    production of excess heat/ wear of switchgear
    arcing contact.
  •  

25
Considered solution
  • Use of switchgear of higher voltage class than
    the system voltage to withstand higher TRV.
  • Use of sectionalizers to reduce operations of
    source circuit breaker.
  • Studies to determine the system Transient
    Recovery Voltage (TRV) characteristics.
  • For example the specifications require
  • interrupting capacity of 66KV switchgear to be
    31.5KA for 3 seconds instead of 25KA.
  •  

26
Picture No. 5 breaker damaged two transformer
panels, which are mounted 4 meters in front of
the feeder panel.
27
Picture No. 6 Components of damaged circuit
breaker.
28
Picture No. 7 Damaged compartment housing  
29
  • Example of 11KV failure
  • Date of failure 13/06/2005
  • Substation Nairobi West
  • Name of the feeder South C
  • Normal Loading conditions of the feeder 320A
  • Total Number of CB operations at the
  • time of failure (Fault/Controlled) 2790
  • Load current prior to the failure 260A
  • Fault current 12000A

30
Circuit Breaker Details
  • STANDARD IEC 56 O-0.3s CO-3MIN-CO
  • (0-3MIN CO-3 MIN OCO 25KA)
  • RATED VOLTAGE 17.5(12KV)
  • INSULATION LEVEL 38/95KV
  • RATED FREQUENCY 50-60 HZ
  • RATED CURRENT 630 A
  • BREAKING CAPACITY 20(25 KA)
  • MAKING CAPACITY 50 (63) KA
  • SF6 PRESSURE AT 20 C 4 BAR (0.4 MPA)
  • SHORT TIME CURRENT 25 KA 3 SEC

31
Observations
  • The circuit breaker exploded while trying to
    clear a
  • fault.
  • Cause repeated switching on to a faulty cable.
  • Explosion completely destroyed circuit breaker
    and
  • damaged adjacent feeder compartments.
  • Panel door shot- off like a bullet- damaging
    panels
  • placed in front.  
  • Most of the circuit breaker parts were expelled
    through the panel door.

32
Way forward after this experience
  • Specifications require manufacturers to
  • state maximum number of circuit breaker
  • operations on fault and controlled operations on
  • normal load before overhaul. 
  • state level of SF6 pressure safe for tripping  
  • recommend safety measures to reduce risk to
  • injury and damage to property
  • provide evidence of the operation of arc vents.

33
3.      PROCUREMENT OF SWITCHGEAR AND CONTROLGEAR
THROUGH OPEN TENDERS.
  • Regulations apply to government owned/controlled
    corporations. These regulations require purchases
    of items of high cost to be done through open
    tenders.
  • Consequences of this include
  • involvement of all sorts of merchants, risking
    purchase of sub-standard or wrong items.
  • operating a system with unnecessarily many
    different makes of switchgear
  • extra cost incurred in conducting factory
    inspections
  •  

34
Mitigating measures
  • All switchgear tenders are accompanied by
    detailed
  • specifications.
  • Type tests reports are submitted with bids
  • Tenderers are required to respond to each
    specific
  • requirement of the tender specification.
  • High and medium switchgear tenders are invited
    from manufacturers only who should be ISO
    certified.
  • Factory inspection (new suppliers) to ascertain
    the
  • quality management system in place.
  • Factory acceptance tests of materials are
    conducted by
  • purchasers engineers according as per IEC
  • standards.
  •  

35
REFERENCES
  • 1 IEC 60815 Guide for the selection of
    insulators in respect of polluted conditions. 
  • 2 IEC 60071Insulation co-ordination 
  • 3 IEC 60694 Common specifications for high
    voltage switchgear and control gear 
  • 4 IEC 56 High voltage alternating current
    circuit breakers

36
  • THANK YOU
Write a Comment
User Comments (0)
About PowerShow.com