Title: SF6 contamination by air in the Pelletron
1SF6 contamination by air in the Pelletron
- Recycler Departmental Meeting
- November 5, 2008
- A. Shemyakin
2Results of the gas analyses performed in MI-31
assembly
July 17- repair of the storage tank leaks was
finished
Oct 8- repair of the Pelletron tank leaks was
finished
Jun 10, Jul 28, Aug 21 29- five bottles of SF6
were added
- Three consecutive tests of the gas in the
Pelletron tank gave similar results SF6 is
heavily contaminated by air - The same company
- 2007 test was good
3What might have contributed
- There were leaks in the Pelletron tank
- Between Jan and Oct 2008, the SF6 loss was 1.5
2 psi/month (out of equivalent of 100 psia in
both tanks) - The leak added air in the time of gas transfers
with a negative pressure in the Pelletron tank - Decrease of the total SF6 amount forced to leave
the very minimum relative pressure in the storage
tank - There was a large leak in the storage tank
- The most probable candidate because of scale of
the leak - The storage tank pressure gauge was found reading
3 psig at atmospheric pressure instead of zero - Temperature variations provided a good
opportunity for sucking the air into the leaking
storage tank - Before transfers, the gauge was reading from 0
(on 11-Apr-08) to 5 psig - With a large amount of manually operated valves
to set during transfers, its difficult to rule
out completely a human error - Until Jun-08, there were no readings storage tank
P and T, so it is impossible to trace changes of
PV/T during transfers
4Effect of the Pelletron tank leak
- One of possibilities is an air contamination in
the time when SF6 is pumped out of the Pelletron
tank, and the tank is already at a negative (vs
atmosphere) pressure - Estimation from the following data
- min achievable pressure, 0.3 Torr in summer
months - Pipe between the gauge and the pump with 100 l/s
conductivity in the molecular regime - Pumping in this mode for 1 hour
- This effect adds only a small amount of air,
equivalent of 0.5 psi per one transfer (out of
85 psia)
5Air intake through the storage tank
- Until 10-Jun-08, the storage tank pressure and
temperature were not read by ACNET. Immediately
after connection, a large leak was found in the
pressure relief valve. The leak could have been
there for a long time. - It means a large loss of SF6 in the time of
transfers and possibility to suck in air both in
the pumping the gas into the Pelletron and in
the time of temperature variations
Storage tank temperature and pressure after
connecting the gauges to ACNET. SF6 was added to
the storage tank two days before the connection.
Adding SF6 after repairing the storage tank leak.
The mass stayed constant after that.
6Calculated mass during the transfers
Data (P, T) for transfers storage tank - from
technicians manual records in the log books,
Pelletron tank from data logger D44
- The table shows the sums of PV/T in both tanks
before the transfer, with all gas in the storage
tank, and after transferring gas back to the
Pelletron - Except the transfer on 11-Apr-08, numbers before
the transfer and after the transfer back to the
Pelletron are consistent within 1, and amount
calculated for the gas in the storage tank is by
7 lower (error in calibration of gauges). - On 11-Apr-08, 6 was added in the time of
pumping into the storage tank. - Unclear how it might happen
- Storage tank pressure gauge read zero before the
transfer (that corresponds to -3 psi)
7Consequences
- Stability of HV and recirculation has not changed
- Most likely, due to the fact that we are running
a nominally 6 MV machine at 4.3 MV - Humidity is kept low by the alumina-filled
dehumidifier - Burst of the lost current are frequent only after
tank openings - Large absolute pressure of oxygen may result in a
fire inside the tank - On the other hand, amount of oil-like material is
small, and recently there were no sparks - Oxygen is said to deteriorate reliability
- Grease burning and contact oxidation
- Purification of so heavily contaminated SF6 is
difficult - According to companies Karl Williams have
contacted, it can be only fully replaced, 100 k
value - A possibility to remove only oxygen are being
looked at - We may have to live with this gas and with a
likely increased frequency of failures
8Summary
- Tests showing a large air contamination in the
system are most likely correct - We are discussing sending a sample for testing in
a different company - Significant portion of air might have come
through a large leak in the storage tank - Only one instance, the transfer on April 11,
2008, reliably shows a increase of PV/T (apart
of adding SF6 from bottles) - Still there is no complete explanation for almost
40 of air in the gas - Presently, there are no detectable leaks in the
system - There is no direct impact of the contamination on
the cooler operation - However, oxygen may deteriorate reliability of
the Pelletron - No cheap way to have the gas with no oxygen has
been found yet