Title: ControlWave Whats new and whats next
1ControlWaveWhats new and whats next
- Shane McCoy
- Account Executive
2Retirement Party
- 33XX 3530 - Nearly 20 years of loyal service
- Network 3000/3530 announce their retirement
beginning in March 2007 after 20 years of loyal
service - Bristol Bristol has been planning for this
eventual retirement for the past five years - Mature line of ControlWave products offering
direct functional alternatives - ControlWave provides greater functionality,
offers and a more open architecture, leverages
current technology all at more attractive
pricing
333XX to ControlWave
PRODUCT MAPPING
DPC 3330/3335 ControlWave Micro RSP
3332 Redundant CW RIO 3331 CW Micro Exp
I/O RTU 3310 CW Micro Express RTU 3305 CW
Express Micro
433XX to ControlWave
PRODUCT MAPPING
SAP 3305 ControlWave ExpressPAC RTU 3340 CW
Micro ControlWave LP CW Micro Express GFC
5ControlWave Express
- ARM 9 processor
- 14 or 33 MHz
- 2 MB SRAM, 8 MB Flash
- 3 serial ports
- 1-RS232, 1-RS585
- 1 selectable RS232/485
- Optional Ethernet port
- Local display interface
- Very low power consumption
- lt 0.1 watt with 14 MHz CPU
- lt 0.3 watt with 33 MHz CPU
- Local display interface ?
Optimum price/performance for small applications
(10.25 x 5.5 x 1.25) (26 cm x 14 cm x 3.2 cm)
DIN rail or Panel mount
6ControlWave Express I/O
- Flexible Digital I/O configuration
- 4 dedicated DI
- 2 Dedicated DO
- 2 selectable DI/DO
- 2 selectable DI/HSC
- 2 selectable DI/Pulse inputs on CPU
- Add Analog I/O
- 3 AI
- 4-20 mA or 1-5 Vdc
- 1 optional AO
- 4-20 mA or 1-5Vdc
- RTD input on 14 MHz CPU ?
7ControlWave Express I/O
- Digital I/O
- Internally sourced dry contact inputs
- 60 microA for low power or 2 mA for noise
immunity selectable per card - 400 mA DO current sink capability
- Analog I/O
- 14 bit AI, .2 accuracy over temperature
- 12 bit AO, .3 accuracy over temperature
- Pulse/DI on CPU
- 1 second scan rate
- Internally sourced dry contact inputs
- 200 microA
- HSC/DI on I/O board
- 0 10 KHz
- Internally or externally sourced voltage inputs
- 200 microA or 2.2 mA ?
8ControlWave ExpressPAC
- Pre-engineered SCADA RTU
- Built on ControlWave Express RTU
- Reduces integration and maintenance costs
- 15.77 H x 7.8 W x 9 D Lexan housing (40.1cm X
19.8cm X 22.9cm) - Nema 3R (Nema 4x except with a battery vent)
- Mounting Pipe-mounted, or wall-mounted
- Solar Panel 2 pipe or mast-mounting
- C1, D2 - approved, C1, D2 submitted ?
SCADA RTU package solution
9ControlWave ExpressPAC
- Select from variety of standard options
- 2 button or 25 button Keypad/Display for local
operator interface - Lithium battery option
- Solar panel option with lead acid battery
- Wide range of FreeWave MDS radio options
- Dial-line modem option
- Solar regulator radio AUX out ?
Highly integrated package
10ControlWave Micro Dual Ethernet CPU
- Allows integrated network segmentation between
PLC/RTU and I/O network - Each Ethernet port is an independent Ethernet
network
ControlWave Micro Dual Ethernet CPU
11Control Wave Micro Distributed I/O
- Ethernet Communications
- One to Fourteen I/O Slots per drop
- One or more I/O Systems
12Thermocouple and RTD Input Cards
- Thermocouple Modules
- Available for Control Wave and Control Wave Micro
- 6 Points per module
- Accepts B,R,S,J,E,K,T,C,N Type Thermocouples
- RTD Modules
- Available for Control Wave and Control Wave Micro
- 4 Points per module
- Accepts 2,3, or 4 wire 100 ohm Platinum RTDs
13Integrated Pump Control Application
- Applications include
- Well Station
- Reservoir level Control
- Remote Tank Level Control
- Duplex Lift or Booster Station
- Triples Lift or Booster Station ?
- Pump Start / Stop and VFDSpeed Control
ControlWave Benefit Pre-programmed/programmable We
b page configuration
14Control WaveWhats new and whats next