Title: Schedule
1Schedule
2Introduction
Load Estimation
Terminology
Basic Equipment
Codes and Standards
Power Distribution Final Circuit
Standby Generator and Power Supplies
Protection Cable Wiring
Earthing
Design of Electricity Distribution
3Protection and Cable Wiring
4Example
- A 20-Storey residential building with total 160
no. of flats (ADMD 6.5 kVA/ flat) - Lift 4 Lifts _at_ 25kVA (one is a fireman lift)
- Water Pump Potable _at_ 10kVA
- Flushing _at_ 10kVA
- F.S. Pump _at_ 30kVA
- Public Lighting _at_ 5kVA
- Emergency Lighting 10
- Draw a schematic diagram
5Protection for Safety
- Scope
- Protection From Fire Burns (To property/
Installation - Protection against Thermal Effect
- Protection against Overcurrent
- Protection Against Electric Shock (To persons)
- Protection against Direct Contract
- Protection against Indirect Contract.
6Protection Against Thermal Effect
- When fixed equipment is installed having a
surface temperature sufficient to cause a risk of
fire or harmful effects to adjacent materials
suitable measures such as screening by proper
material or mounting so as to allow safe
dissipation of heat and at a sufficient distance
from adjacent material.
7Protection Against Thermal Effect
- Any part of fixed installation likely to attain a
temperature exceeding the temperature limit
specified in IEE standard should be guarded to
prevent accidental contact.
8Protection Against Thermal Effect
- IEE Regulations 422-01-05 specify that adequate
precautions shall be provided to prevent spread
of burning liquids or flame for equipment
containing flammable liquid in excess of 25
litres.
9Protection Against Overcurrent
- Definition
- Overcurrent is a current exceeding the rated
value for a current carrying part. It may be
either an overload current or a short-circuit
current. - Overload Current is an overcurrent occurring in a
circuit which is electrically sound, due to
loading in excess of the design current of the
circuit. - Short-Circuit Current is an overcurrent resulting
from a fault of negligible impedance between live
conductors having a difference in potential under
normal operating conditions.
10 11Protection Against Overcurrent
- Overcurrent Protective Devices
- Every installation and circuit shall be protected
against overcurrent by devices which will operate
automatically at values of current which are
suitably related to the safe current ratings of
the circuit. (9A1) - The overcurrent devices shall be suitably located
and constructed so as to prevent danger from
overheating or arcing and to permit ready
restoration of supply without danger.
12Protection Against Overcurrent
- Overcurrent Protective Devices
- The means of protection against overcurrent shall
be a device capable of breaking any overcurrent
up to and including the prospective short circuit
current at the point where the device is
installed. Such device may be circuit breaker
incorporating overload release, or fuses, or
circuit breaker in conjunction with fuses. (9A2) - The overcurrent devices shall be of adequate
breaking capacity and, where appropriate, making
capacity for protection against fault current.
(432-04-01)
13Protection Against Overcurrent
- Overcurrent Protective Devices
- Overcurrent protective devices should be placed
in non-flammable enclosures. The breakers should
be designed or installed in a way that it is not
possible to modify the overcurrent setting
without the use of a key or tool. 9E(a) 9E(e) - Protective devices are required to be labelled,
marked and arranged so that related circuits can
be readily identified. E.g. name plate, warning
notice, intended nominal current, circuit chart,
etc. 9E(b)
14Protection Against Overcurrent
- Overcurrent Protective Devices
- The overcurrent device protecting socket outlet
circuits must be operate on an earth fault within
0.4 seconds and device protecting fixed equipment
circuits within 5 seconds, except for bathroom
where this value for fixed equipment circuits is
also 0.4 seconds. To meet this requirement, the
measured earth fault loop impedance of circuit
must not greater than the values givens in CoP
Table 8,10,11.
15Protection Against Overcurrent
- Overcurrent Protective Devices
- In TT system, the use of residual current devices
is preferred to overcurrent protective devices
because the value of earth fault loop impedance
of such system is variable depending upon
moisture levels at each earth electrode.
16Overload Protection
- Protective device shall be provided to break any
overload current flowing in the circuit
conductors before such a current could cause a
temperature rise detrimental to insulation,
joints, terminations, or surroundings of the
conductors. 9B (1)a
17Overload Protection
- IEE Reg. 433-02 states the condition of
co-ordination between conductors and protective
devices. - I) Ib In Iz
- II) I2 1.45 Iz
- Ib Design current of the circuit
- In Nominal current rating or setting of
overload protective device - Iz Current carrying capacity of the circuit
conductor - I2 The current ensuring effective operation of
the protective device - The factor of 1.45 is the fusing factor of the
protective device. (Fusing factor I2 / In)
18Example
- For a single phase 220V circuit , the protective
device is a MCB (BSEN 60898 Type B). The current
carrying capacity of the cable Iz 19A and the
electric load is a 2.6kW electric heater. - Estimate the MCB rating (In).
19Overload Protection
- If the overload protective device is a fuse to BS
88 Part 2 or MCB to BS 3871 and compliance with
condition (I), then condition (II) will deem to
be complied with.
20Overload Protection
- One overload protective device dose not comply
with the requirement of condition (II) is
semi-enclosed fuse to BS 3036. Such kind of fuse
has a fusing factor of 2, then - I2 2In
- I2 1.45 Iz
- Therefore, 2In 1.45 Iz
- In 0.725 Iz
21Overload Protection
- Position of overload protective device
- A device for protection against overload shall be
placed at the point where a reduction occurs in
the value of current carrying capacity of the
conductors of the installation. 9D(2a) - The device protecting conductors against overload
may be placed along the run of those conductors,
provided that no branches or outlets are
introduced between the point of reduction and the
device. 9D(2b)
22Short Circuit Protection
- IEE section 434 deals only with the case of short
circuit anticipated between conductors belonging
to the same circuit. - Protective devices shall be provided to break any
short circuit current in the conductors of each
circuit before such current could cause danger
due to thermal and mechanical effects produced in
conductors and connections.
23Short Circuit Protection
- Reg. 434-03-01 states that the breaking capacity
rating shall be not less than the prospective
short circuit current at the point at which the
device is installed. Where supply is taken direct
from the local power companys transformer, the
main switch or circuit breaker shall have a
short-circuit breaking capacity of 24MVA (at
three-phase low voltage of 346V) -
- Isc 24 000 000 36.5KA
- v 3 x 380
24Short Circuit Protection
- Three-phase and Single-phase Symmetrical Short
Circuit Currents - If we are dealing with three-phase symmetrical
short-circuit, then we need only to know the
impedance of one-phase conductor. - Three-phase symmetrical short-circuit current
- Isc(3Ø) Vp / Z1
- Vp phase to neutral voltage
- Z1 impedance of phase conductor
- If we are concerned with single-phase symmetrical
short circuit current between phase and neutral
we have to take into consideration the impedance
of the phase and neutral conductors. - Single-phase symmetrical short-circuit current
- Isc(1Ø) Vp / (Z1Zn)
- Zn impedance of neutral conductor
25Example
26Short Circuit Protection
- Position of Devices for Short Circuit Protection
- The short-circuit protective device shall be
placed at the point where a reduction occurs in
value of current carrying capacity of the
conductors or placed on the conductor that - Not exceed 3m in length after the reduction of
cross-section area and - To reduce the risk of fault current to a minimum
and - To reduce the risk of fire or danger to persons
to minimum. - For MCB to be used as short circuit protective
device, both maximum and minimum short circuit
current should be checked. The fault current in
the circuit must lie between Imax and Imin that
the conductor shall be protected by the
overcurrent device.
27Short Circuit Protection
- The breaking capacity of the protective device
shall capable to withstand the prospective
short-circuit current flow through during earth
fault. Engineers are required to check/ calculate
the prospective short-circuit current at the
point where the device is installed, and to
compare the breaking capacity of the device.
Typical breaking capacity of protective devices
and the minimum breaking capacity of protective
devices to be installed in respect of different
types of supply, with or without back-up fuse.
28Typical Breaking Capacity of Protective Devices
29Typical Protective Short Circuit Current
30Typical Protective Short Circuit Current
31Protection Against Both Direct and Indirect
Contact
- A) Separate Extra Low Voltage (SELV)
- The nominal voltage should not exceed 50Vrms
- Safety sources such as Class II safety isolating
transformer to BS 3535 with secondary winding
isolating from earth or battery - Live parts of the circuit shall be isolated from
Earth, circuit of other system or extraneous
conductive parts
32Protection Against Both Direct and Indirect
Contact
- A) Safety Extra Low Voltage (SELV)
- If the supply voltage used dose not exceed 25
Vrms, no precautions to prevent direct contact is
required under normal body resistance. If the
supply voltage used is lied between 25 Vrms and
50 Vrms , direct contact protection shall be
either by barrier or enclosure having IP2X, or by
insulation which capable to withstand a test
voltage of 500V a.c. for one minute.
33Protection Against Both Direct and Indirect
Contact
- B) Functional Extra Low Voltage (FELV)
- If the system complies with the requirements of
safety extra-low voltage system, except that it
fails to isolate from earth or protective
conductors of other circuit, the system shall be
protection against direct contact by - Enclosures to IP2X, and/or
- Insulation of live parts capable to withstand
500V a.c. for one minute.
34Protection Against Both Direct and Indirect
Contact
- B) Functional Extra Low Voltage (FELV)
- If the system generally fails to comply with the
requirements of safety extra-low voltage system,
then the system shall be - Protection against Direct contact by barriers or
enclosures and/ or insulation subjected to test
voltage for primary circuit. - Protection against indirect Contact by connecting
exposed conductive parts to protective conductor
of the primary circuit.
35Protection Against Both Direct and Indirect
Contact
- C) Limitation of Discharge Energy
- Equipment shall comply with appropriate British
Standards, and shall limit current lower than the
shock current, and shall be isolated from other
circuit.
36Protection Against Direct Contact
1) Methods
37Protection Against Direct Contact
- 2) Insulation should withstand the mechanical,
electrical, thermal and chemical stresses to
which it serves and only to be removed by
destruction. If applied on site, the quality of
the insulation shall be tested to that of similar
factory-built equipment.
38Protection Against Direct Contact
- 3) Live parts shall be inside enclosures or
behind barriers on following conditions - In general, at least IP2X
- At readily accessible or top surface, at least
IP4X - In removing the enclosures or barrier, it shall
be - By tool or key, and/or
- Possible only after disconnection of supply and
restoration of supply only possible after the
replacement of the enclosure/barrier, and/or - Intermediate barrier to IP2X.
39Protection Against Direct Contact
- 4) IEE Reg. 412-04-02 states that suitable
precautions such as using obstacles to prevent
unintentionally touching to live part for
equipment intended for protection against direct
contact. - 5) A bare live part should not be placed within
arms reach or 2.5m of any exposed/ extraneous
conductive parts.
40Protection Against Indirect Contact
- Methods
- Earthed equipotential bonding and automatic
disconnection of supply - Use of Class II equipment or equivalent
insulation - Non-conducting location
- Earth-free local equipotential bonding
- Electrical separation.
-
- The most commonly used protective measure
against indirect contact is that of automatic
disconnection of supply using the overcurrent
protective device.
41Earthed Equipotential Bonding and Automatic
Disconnection - 1
- A) Principle
- To bond all the exposed and extraneous conductive
parts to earth in order to create a zone at
earthed potential so that the potential
difference (touch voltage) between those parts
are minimized in the event of an earth fault
inside the zone (touch voltage would be reduced
by bonding), and then to cut the supply within
the maximum safe time duration.
42(No Transcript)
43What happen if electrical appliances are not
earthed?
44Can earthing help?
45What happen if extraneous conductive parts are
not bonded?
46Earthed Equipotential Bonding and Automatic
Disconnection
- B) Disconnection of Supply under Earth Fault
- A protection device shall disconnect the supply
during an earth fault so as not to cause danger. - Maximum disconnection times are shown as follows
47Earthed Equipotential Bonding and Automatic
Disconnection
- B) Disconnection of Supply under Earth Fault
- Maximum value of earth loop impedance achieving
the above disconnection time for various
protective devices are shown in Table 41B1, Table
41B2 and Table 41D of IEE Regulations (for 240V).
The values shall be multiplied by 0.916 (220V/
240V) for nominal supply voltage of 220V.
48Earthed Equipotential Bonding and Automatic
Disconnection
49Earthed Equipotential Bonding and Automatic
Disconnection
- B) Disconnection of Supply under Earth Fault
- The breaking capacity of the protective device
shall capable to withstand the prospective earth
fault current. - Local supplementary bonding shall be required
where the disconnection time cannot be achieved
50Earthed Equipotential Bonding and Automatic
Disconnection
- B) Disconnection of Supply under Earth Fault
- The principle is to limit the resistance of the
protective conductor so that the voltage
appearing on exposed conductor parts under fault
conditions is limited to 50 volts or if the
voltage is a higher value the circuit would
disconnect faster. - For ring circuits the impedance of the protective
conductor is calculated between its two ends
before final connection is made and shall not
exceed four times the value given in table 41C.
51Earthed Equipotential Bonding and Automatic
Disconnectio
52Earthed Equipotential Bonding and Automatic
Disconnection
C) Determination of Disconnection Time 1) Maximum
values of earth loop impedance for various
overcurrent protective devices are shown in table
41B1, Table 41B2 Table 41D 2) Actual earth loop
impedance can be calculated as follows Zs Ze
Z1 Z2 Ze Earth loop impedance at the
source Z1 Impedance of phase conductor Z2
Impedance of circuit protective conductor (cpc)
53Earthed Equipotential Bonding and Automatic
Disconnection
- C) Determination of Disconnection Time
- 3) Compare the actual Zs with the tabulated
Zs(max) - The actual Zs value measured from the
installation should be smaller than the Zs(max)
value from IEE Tables in order to achieve safe
disconnection time. Attention is drawn on that
the Zs (max) form IEE Tables shall be converted
to nominal supply voltage system in Hong Kong
before comparison. - Zs (max 220) Zs (max 240) in IEE Tables X
220/240
54Earthed Equipotential Bonding and Automatic
Disconnection
C) Determination of Disconnection Time 4) The
earth fault current can be calculated using the
following formula If Uo /Zs Uo Phase to
earth voltage If earth fault current 5) By
putting the calculated fault current against the
characteristic curves of the protective device
given in IEE, the actual disconnection time can
be found.
55Example
- A 220V circuit is protected by a 30A Type 2 MCB,
the cable used is 2.5/1.5 twin with cpc PVC
copper conductor, if the circuit length is 15m
and Ze up to the MCB board is 0.5O, what is the
actual disconnection time? - From table 17, R1R2 /m 19.51mO x 1.38
- 0.269
O/m
56Time (s)
Current (A)
57Provision of Residual Current Device (RCD)
- If the required disconnection time cannot be
achieved, RCD shall be provided - A RCD shall not be used as the sole means of
protection against direct contact. The use of a
RCD is recognized as reducing the risk of
electric shock if residual operation current not
exceeding 40ms at a residual current of 150mA in
addition to other means of protection against
direct contact. - IEE Reg. 412-02-16 states that where RCD are used
to comply with the disconnection times, the
residual operating current times earth fault loop
impedance must not exceed 50. - e.g. I2 30mA, Zs 50/ 0.03 1667ohms.
58Provision of Residual Current Device (RCD)
- RCD having a rated residual operating current not
exceeding 30mA shall be provided for every socket
outlet circuit in a household or similar
installation forming part of TT system. - For instillation supplied form overhead line
system, the installation shall be protected
against earth leakage by RCD. - The sum of normal leakage current of various
items of equipment must not grater that half of
the value of nominal residual operating current
of the RCD.
59Provision of Residual Current Device (RCD)
- Leakage current for typical equipment are shown
below for reference
60Coordination/ Discrimination of Protective Devices
- Overcurrent protective devices shall be
coordinated so that the energy let-through by the
fault current protective device does not exceed
that which can be withstood without damage by the
overload current protective device. - It is allowed to install a protective device with
a breaking capacity lower than the prospective
short-circuit current available provided that - There is a protective device on the supply side
of the lower rated protective device which has
the necessary breaking capacity and - Both protective devices are coordinated so that
the energy let-through the supply side device
will not damage the lower rated device or cables
conductors protected by both devices.
61Coordination/ Discrimination of Protective Devices
- When a consumer's main switch is connected
directly to the power companys transformer, the
overcurrent protection of the main switch shall
discriminate with the power companys high
voltage protective settings. - Discrimination between fuse-links connected in
cascade internal power distribution can be
achieved if the current rating of general purpose
fuse-links have a discrimination ratio of 1.6 1
or based upon the pre-arcing I2t values shown
Table VI of BS 88 Part 1 1988.
Engineer-in-charge should check the
characteristic curves and I2t of protective
devices installed in series for proper
discrimination.
62Coordination/ Discrimination of Protective Devices
- Protective device for motor circuit shall be
carefully selected so as to suit the maximum
starting current. The maximum acceptable starting
current for induction motors are tabulated as
follows
63Q A
64The End