Schedule - PowerPoint PPT Presentation

1 / 64
About This Presentation
Title:

Schedule

Description:

A 20-Storey residential building with total 160 no. of ... Cubicle Switchboard. By obstacles. Open type Switchboard. By placing out of reach. Overhead Line ... – PowerPoint PPT presentation

Number of Views:78
Avg rating:3.0/5.0
Slides: 65
Provided by: Aqu55
Category:
Tags: cubicle | schedule

less

Transcript and Presenter's Notes

Title: Schedule


1
Schedule
2
Introduction
Load Estimation
Terminology
Basic Equipment
Codes and Standards
Power Distribution Final Circuit
Standby Generator and Power Supplies
Protection Cable Wiring
Earthing
Design of Electricity Distribution
3
Protection and Cable Wiring
  • Date 13 November 2008

4
Example
  • A 20-Storey residential building with total 160
    no. of flats (ADMD 6.5 kVA/ flat)
  • Lift 4 Lifts _at_ 25kVA (one is a fireman lift)
  • Water Pump Potable _at_ 10kVA
  • Flushing _at_ 10kVA
  • F.S. Pump _at_ 30kVA
  • Public Lighting _at_ 5kVA
  • Emergency Lighting 10
  • Draw a schematic diagram

5
Protection for Safety
  • Scope
  • Protection From Fire Burns (To property/
    Installation
  • Protection against Thermal Effect
  • Protection against Overcurrent
  • Protection Against Electric Shock (To persons)
  • Protection against Direct Contract
  • Protection against Indirect Contract.

6
Protection Against Thermal Effect
  • When fixed equipment is installed having a
    surface temperature sufficient to cause a risk of
    fire or harmful effects to adjacent materials
    suitable measures such as screening by proper
    material or mounting so as to allow safe
    dissipation of heat and at a sufficient distance
    from adjacent material.

7
Protection Against Thermal Effect
  • Any part of fixed installation likely to attain a
    temperature exceeding the temperature limit
    specified in IEE standard should be guarded to
    prevent accidental contact.

8
Protection Against Thermal Effect
  • IEE Regulations 422-01-05 specify that adequate
    precautions shall be provided to prevent spread
    of burning liquids or flame for equipment
    containing flammable liquid in excess of 25
    litres.

9
Protection Against Overcurrent
  • Definition
  • Overcurrent is a current exceeding the rated
    value for a current carrying part. It may be
    either an overload current or a short-circuit
    current.
  • Overload Current is an overcurrent occurring in a
    circuit which is electrically sound, due to
    loading in excess of the design current of the
    circuit.
  • Short-Circuit Current is an overcurrent resulting
    from a fault of negligible impedance between live
    conductors having a difference in potential under
    normal operating conditions.

10

11
Protection Against Overcurrent
  • Overcurrent Protective Devices
  • Every installation and circuit shall be protected
    against overcurrent by devices which will operate
    automatically at values of current which are
    suitably related to the safe current ratings of
    the circuit. (9A1)
  • The overcurrent devices shall be suitably located
    and constructed so as to prevent danger from
    overheating or arcing and to permit ready
    restoration of supply without danger.

12
Protection Against Overcurrent
  • Overcurrent Protective Devices
  • The means of protection against overcurrent shall
    be a device capable of breaking any overcurrent
    up to and including the prospective short circuit
    current at the point where the device is
    installed. Such device may be circuit breaker
    incorporating overload release, or fuses, or
    circuit breaker in conjunction with fuses. (9A2)
  • The overcurrent devices shall be of adequate
    breaking capacity and, where appropriate, making
    capacity for protection against fault current.
    (432-04-01)

13
Protection Against Overcurrent
  • Overcurrent Protective Devices
  • Overcurrent protective devices should be placed
    in non-flammable enclosures. The breakers should
    be designed or installed in a way that it is not
    possible to modify the overcurrent setting
    without the use of a key or tool. 9E(a) 9E(e)
  • Protective devices are required to be labelled,
    marked and arranged so that related circuits can
    be readily identified. E.g. name plate, warning
    notice, intended nominal current, circuit chart,
    etc. 9E(b)

14
Protection Against Overcurrent
  • Overcurrent Protective Devices
  • The overcurrent device protecting socket outlet
    circuits must be operate on an earth fault within
    0.4 seconds and device protecting fixed equipment
    circuits within 5 seconds, except for bathroom
    where this value for fixed equipment circuits is
    also 0.4 seconds. To meet this requirement, the
    measured earth fault loop impedance of circuit
    must not greater than the values givens in CoP
    Table 8,10,11.

15
Protection Against Overcurrent
  • Overcurrent Protective Devices
  • In TT system, the use of residual current devices
    is preferred to overcurrent protective devices
    because the value of earth fault loop impedance
    of such system is variable depending upon
    moisture levels at each earth electrode.

16
Overload Protection
  • Protective device shall be provided to break any
    overload current flowing in the circuit
    conductors before such a current could cause a
    temperature rise detrimental to insulation,
    joints, terminations, or surroundings of the
    conductors. 9B (1)a

17
Overload Protection
  • IEE Reg. 433-02 states the condition of
    co-ordination between conductors and protective
    devices.
  • I) Ib In Iz
  • II) I2 1.45 Iz
  • Ib Design current of the circuit
  • In Nominal current rating or setting of
    overload protective device
  • Iz Current carrying capacity of the circuit
    conductor
  • I2 The current ensuring effective operation of
    the protective device
  • The factor of 1.45 is the fusing factor of the
    protective device. (Fusing factor I2 / In)

18
Example
  • For a single phase 220V circuit , the protective
    device is a MCB (BSEN 60898 Type B). The current
    carrying capacity of the cable Iz 19A and the
    electric load is a 2.6kW electric heater.
  • Estimate the MCB rating (In).

19
Overload Protection
  • If the overload protective device is a fuse to BS
    88 Part 2 or MCB to BS 3871 and compliance with
    condition (I), then condition (II) will deem to
    be complied with.

20
Overload Protection
  • One overload protective device dose not comply
    with the requirement of condition (II) is
    semi-enclosed fuse to BS 3036. Such kind of fuse
    has a fusing factor of 2, then
  • I2 2In
  • I2 1.45 Iz
  • Therefore, 2In 1.45 Iz
  • In 0.725 Iz

21
Overload Protection
  • Position of overload protective device
  • A device for protection against overload shall be
    placed at the point where a reduction occurs in
    the value of current carrying capacity of the
    conductors of the installation. 9D(2a)
  • The device protecting conductors against overload
    may be placed along the run of those conductors,
    provided that no branches or outlets are
    introduced between the point of reduction and the
    device. 9D(2b)

22
Short Circuit Protection
  • IEE section 434 deals only with the case of short
    circuit anticipated between conductors belonging
    to the same circuit.
  • Protective devices shall be provided to break any
    short circuit current in the conductors of each
    circuit before such current could cause danger
    due to thermal and mechanical effects produced in
    conductors and connections.

23
Short Circuit Protection
  • Reg. 434-03-01 states that the breaking capacity
    rating shall be not less than the prospective
    short circuit current at the point at which the
    device is installed. Where supply is taken direct
    from the local power companys transformer, the
    main switch or circuit breaker shall have a
    short-circuit breaking capacity of 24MVA (at
    three-phase low voltage of 346V)
  • Isc 24 000 000 36.5KA
  • v 3 x 380

24
Short Circuit Protection
  • Three-phase and Single-phase Symmetrical Short
    Circuit Currents
  • If we are dealing with three-phase symmetrical
    short-circuit, then we need only to know the
    impedance of one-phase conductor.
  • Three-phase symmetrical short-circuit current
  • Isc(3Ø) Vp / Z1
  • Vp phase to neutral voltage
  • Z1 impedance of phase conductor
  • If we are concerned with single-phase symmetrical
    short circuit current between phase and neutral
    we have to take into consideration the impedance
    of the phase and neutral conductors.
  • Single-phase symmetrical short-circuit current
  • Isc(1Ø) Vp / (Z1Zn)
  • Zn impedance of neutral conductor

25
Example
26
Short Circuit Protection
  • Position of Devices for Short Circuit Protection
  • The short-circuit protective device shall be
    placed at the point where a reduction occurs in
    value of current carrying capacity of the
    conductors or placed on the conductor that
  • Not exceed 3m in length after the reduction of
    cross-section area and
  • To reduce the risk of fault current to a minimum
    and
  • To reduce the risk of fire or danger to persons
    to minimum.
  • For MCB to be used as short circuit protective
    device, both maximum and minimum short circuit
    current should be checked. The fault current in
    the circuit must lie between Imax and Imin that
    the conductor shall be protected by the
    overcurrent device.

27
Short Circuit Protection
  • The breaking capacity of the protective device
    shall capable to withstand the prospective
    short-circuit current flow through during earth
    fault. Engineers are required to check/ calculate
    the prospective short-circuit current at the
    point where the device is installed, and to
    compare the breaking capacity of the device.
    Typical breaking capacity of protective devices
    and the minimum breaking capacity of protective
    devices to be installed in respect of different
    types of supply, with or without back-up fuse.

28
Typical Breaking Capacity of Protective Devices
29
Typical Protective Short Circuit Current
30
Typical Protective Short Circuit Current
31
Protection Against Both Direct and Indirect
Contact
  • A) Separate Extra Low Voltage (SELV)
  • The nominal voltage should not exceed 50Vrms
  • Safety sources such as Class II safety isolating
    transformer to BS 3535 with secondary winding
    isolating from earth or battery
  • Live parts of the circuit shall be isolated from
    Earth, circuit of other system or extraneous
    conductive parts

32
Protection Against Both Direct and Indirect
Contact
  • A) Safety Extra Low Voltage (SELV)
  • If the supply voltage used dose not exceed 25
    Vrms, no precautions to prevent direct contact is
    required under normal body resistance. If the
    supply voltage used is lied between 25 Vrms and
    50 Vrms , direct contact protection shall be
    either by barrier or enclosure having IP2X, or by
    insulation which capable to withstand a test
    voltage of 500V a.c. for one minute.

33
Protection Against Both Direct and Indirect
Contact
  • B) Functional Extra Low Voltage (FELV)
  • If the system complies with the requirements of
    safety extra-low voltage system, except that it
    fails to isolate from earth or protective
    conductors of other circuit, the system shall be
    protection against direct contact by
  • Enclosures to IP2X, and/or
  • Insulation of live parts capable to withstand
    500V a.c. for one minute.

34
Protection Against Both Direct and Indirect
Contact
  • B) Functional Extra Low Voltage (FELV)
  • If the system generally fails to comply with the
    requirements of safety extra-low voltage system,
    then the system shall be
  • Protection against Direct contact by barriers or
    enclosures and/ or insulation subjected to test
    voltage for primary circuit.
  • Protection against indirect Contact by connecting
    exposed conductive parts to protective conductor
    of the primary circuit.

35
Protection Against Both Direct and Indirect
Contact
  • C) Limitation of Discharge Energy
  • Equipment shall comply with appropriate British
    Standards, and shall limit current lower than the
    shock current, and shall be isolated from other
    circuit.

36
Protection Against Direct Contact
1) Methods
37
Protection Against Direct Contact
  • 2) Insulation should withstand the mechanical,
    electrical, thermal and chemical stresses to
    which it serves and only to be removed by
    destruction. If applied on site, the quality of
    the insulation shall be tested to that of similar
    factory-built equipment.

38
Protection Against Direct Contact
  • 3) Live parts shall be inside enclosures or
    behind barriers on following conditions
  • In general, at least IP2X
  • At readily accessible or top surface, at least
    IP4X
  • In removing the enclosures or barrier, it shall
    be
  • By tool or key, and/or
  • Possible only after disconnection of supply and
    restoration of supply only possible after the
    replacement of the enclosure/barrier, and/or
  • Intermediate barrier to IP2X.

39
Protection Against Direct Contact
  • 4) IEE Reg. 412-04-02 states that suitable
    precautions such as using obstacles to prevent
    unintentionally touching to live part for
    equipment intended for protection against direct
    contact.
  • 5) A bare live part should not be placed within
    arms reach or 2.5m of any exposed/ extraneous
    conductive parts.

40
Protection Against Indirect Contact
  • Methods
  • Earthed equipotential bonding and automatic
    disconnection of supply
  • Use of Class II equipment or equivalent
    insulation
  • Non-conducting location
  • Earth-free local equipotential bonding
  • Electrical separation.
  • The most commonly used protective measure
    against indirect contact is that of automatic
    disconnection of supply using the overcurrent
    protective device.

41
Earthed Equipotential Bonding and Automatic
Disconnection - 1
  • A) Principle
  • To bond all the exposed and extraneous conductive
    parts to earth in order to create a zone at
    earthed potential so that the potential
    difference (touch voltage) between those parts
    are minimized in the event of an earth fault
    inside the zone (touch voltage would be reduced
    by bonding), and then to cut the supply within
    the maximum safe time duration.

42
(No Transcript)
43
What happen if electrical appliances are not
earthed?
44
Can earthing help?
45
What happen if extraneous conductive parts are
not bonded?
46
Earthed Equipotential Bonding and Automatic
Disconnection
  • B) Disconnection of Supply under Earth Fault
  • A protection device shall disconnect the supply
    during an earth fault so as not to cause danger.
  • Maximum disconnection times are shown as follows

47
Earthed Equipotential Bonding and Automatic
Disconnection
  • B) Disconnection of Supply under Earth Fault
  • Maximum value of earth loop impedance achieving
    the above disconnection time for various
    protective devices are shown in Table 41B1, Table
    41B2 and Table 41D of IEE Regulations (for 240V).
    The values shall be multiplied by 0.916 (220V/
    240V) for nominal supply voltage of 220V.

48
Earthed Equipotential Bonding and Automatic
Disconnection
49
Earthed Equipotential Bonding and Automatic
Disconnection
  • B) Disconnection of Supply under Earth Fault
  • The breaking capacity of the protective device
    shall capable to withstand the prospective earth
    fault current.
  • Local supplementary bonding shall be required
    where the disconnection time cannot be achieved

50
Earthed Equipotential Bonding and Automatic
Disconnection
  • B) Disconnection of Supply under Earth Fault
  • The principle is to limit the resistance of the
    protective conductor so that the voltage
    appearing on exposed conductor parts under fault
    conditions is limited to 50 volts or if the
    voltage is a higher value the circuit would
    disconnect faster.
  • For ring circuits the impedance of the protective
    conductor is calculated between its two ends
    before final connection is made and shall not
    exceed four times the value given in table 41C.

51
Earthed Equipotential Bonding and Automatic
Disconnectio
52
Earthed Equipotential Bonding and Automatic
Disconnection
C) Determination of Disconnection Time 1) Maximum
values of earth loop impedance for various
overcurrent protective devices are shown in table
41B1, Table 41B2 Table 41D 2) Actual earth loop
impedance can be calculated as follows Zs Ze
Z1 Z2 Ze Earth loop impedance at the
source Z1 Impedance of phase conductor Z2
Impedance of circuit protective conductor (cpc)
53
Earthed Equipotential Bonding and Automatic
Disconnection
  • C) Determination of Disconnection Time
  • 3) Compare the actual Zs with the tabulated
    Zs(max)
  • The actual Zs value measured from the
    installation should be smaller than the Zs(max)
    value from IEE Tables in order to achieve safe
    disconnection time. Attention is drawn on that
    the Zs (max) form IEE Tables shall be converted
    to nominal supply voltage system in Hong Kong
    before comparison.
  • Zs (max 220) Zs (max 240) in IEE Tables X
    220/240

54
Earthed Equipotential Bonding and Automatic
Disconnection
C) Determination of Disconnection Time 4) The
earth fault current can be calculated using the
following formula If Uo /Zs Uo Phase to
earth voltage If earth fault current 5) By
putting the calculated fault current against the
characteristic curves of the protective device
given in IEE, the actual disconnection time can
be found.
55
Example
  • A 220V circuit is protected by a 30A Type 2 MCB,
    the cable used is 2.5/1.5 twin with cpc PVC
    copper conductor, if the circuit length is 15m
    and Ze up to the MCB board is 0.5O, what is the
    actual disconnection time?
  • From table 17, R1R2 /m 19.51mO x 1.38
  • 0.269
    O/m

56
Time (s)
Current (A)
57
Provision of Residual Current Device (RCD)
  • If the required disconnection time cannot be
    achieved, RCD shall be provided
  • A RCD shall not be used as the sole means of
    protection against direct contact. The use of a
    RCD is recognized as reducing the risk of
    electric shock if residual operation current not
    exceeding 40ms at a residual current of 150mA in
    addition to other means of protection against
    direct contact.
  • IEE Reg. 412-02-16 states that where RCD are used
    to comply with the disconnection times, the
    residual operating current times earth fault loop
    impedance must not exceed 50.
  • e.g. I2 30mA, Zs 50/ 0.03 1667ohms.

58
Provision of Residual Current Device (RCD)
  • RCD having a rated residual operating current not
    exceeding 30mA shall be provided for every socket
    outlet circuit in a household or similar
    installation forming part of TT system.
  • For instillation supplied form overhead line
    system, the installation shall be protected
    against earth leakage by RCD.
  • The sum of normal leakage current of various
    items of equipment must not grater that half of
    the value of nominal residual operating current
    of the RCD.

59
Provision of Residual Current Device (RCD)
  • Leakage current for typical equipment are shown
    below for reference

60
Coordination/ Discrimination of Protective Devices
  • Overcurrent protective devices shall be
    coordinated so that the energy let-through by the
    fault current protective device does not exceed
    that which can be withstood without damage by the
    overload current protective device.
  • It is allowed to install a protective device with
    a breaking capacity lower than the prospective
    short-circuit current available provided that
  • There is a protective device on the supply side
    of the lower rated protective device which has
    the necessary breaking capacity and
  • Both protective devices are coordinated so that
    the energy let-through the supply side device
    will not damage the lower rated device or cables
    conductors protected by both devices.

61
Coordination/ Discrimination of Protective Devices
  • When a consumer's main switch is connected
    directly to the power companys transformer, the
    overcurrent protection of the main switch shall
    discriminate with the power companys high
    voltage protective settings.
  • Discrimination between fuse-links connected in
    cascade internal power distribution can be
    achieved if the current rating of general purpose
    fuse-links have a discrimination ratio of 1.6 1
    or based upon the pre-arcing I2t values shown
    Table VI of BS 88 Part 1 1988.
    Engineer-in-charge should check the
    characteristic curves and I2t of protective
    devices installed in series for proper
    discrimination.

62
Coordination/ Discrimination of Protective Devices
  • Protective device for motor circuit shall be
    carefully selected so as to suit the maximum
    starting current. The maximum acceptable starting
    current for induction motors are tabulated as
    follows

63
Q A
64
The End
Write a Comment
User Comments (0)
About PowerShow.com