Title: Schedule
1Schedule
2Introduction
Load Estimation
Terminology
Basic Equipment
Codes and Standards
Power Distribution Final Circuit
Standby Generator and Power Supplies
Protection Cable Wiring
Earthing
Design of Electricity Distribution
3Power Distribution Final Circuit
4Question
- What kind of factors affecting the choice of
wiring system?
5 Power Distribution and Wiring System - 1
- Installation Cost
- Purpose and planned duration of the installation
- Environment factors and installation conditions
- Type of building construction
- Flexibility of the system and circuit arrangement
- Appearance of the finished installation
- Safety aspect
- Nature of power supply and type of earthing
system
6Installation at High Humidity Environment - 2
- The wiring system should be selected and erected
so that no damage is caused by high humidity or
ingress of water during installation, use and
maintenance. - All joint should be suitably insulated and
protected against the effects of moisture or
water. Copperclad aluminum conductors should not
be used. - Every entry to finished ducts or trunking should
be placed so as to prevent the ingress of water
or be protected against such ingress. Where water
may collect or condensation may form in a wiring
system, provisions should be made to drain it
away.
7Installation at Adverse Ambient Temperature - 1
- The wiring system including cables and wiring
accessories, should be suitable for the highest
and lowest ambient temperature that likely to
encountered. - The electrical insulation shall withstand the
maximum permissible operating temperature of the
class of insulation to BS 2757.
8Installation at Adverse Ambient Temperature - 2
- For general-purpose PVC cable, the maximum
permissible conductor of operating temperature is
70oC and the maximum permissible ambient
temperature is 65oC. - In every vertical trunking or duct wiring
installations, suitable internal barriers sould
be provided between floors or at intervals of 5m
whichever is the less.
9Installation at Adverse Ambient Temperature - 3
- Suitable measures shall be provided to avoid the
effects of heat from external source including
solar gain such as shielding or placing
sufficiently far from the source of heat or
selecting insulation suitable for those
temperature.
10Index of Protection
- The code that specifies the protection of
encloses that can be used within certain
environment. The first numeral indicate the
protection against ingress of solid bodies. The
second number indicate the protection against the
ingress of liquids.
IP XX
11(No Transcript)
12(No Transcript)
13(No Transcript)
14Index of Protection
- General Use
- Indoor Use IP2X
- Outdoor Use IP54 (Weather-proof)
15Application of Wiring System
16Typical Schematic Wiring Diagram for Internal
Power Distribution System
17General Requirement of Internal Power
Distribution System
- a) Basic Requirements
- b) High Voltage Distribution
- c) Mains
- d) Sub - Main
- e) Lateral Main
- f) Installation Methods of Cables
18General Requirement of Internal Power
Distribution System
- a) Basic Requirements 1
- Every installation shall be divided into circuits
as necessary to avoid danger in the event of a
fault, and to facilitate safe operation,
inspection, testing and maintenance. Each circuit
should be separately protected by an overcurrent
protective device. Separate circuits shall be
provided for parts of the installation which need
to be separately controlled in such a way that
these circuits are not affected by failure of
other circuits.
19General Requirement of Internal Power
Distribution System
- a) Basic Requirements 2
- Protective devices of each circuit should be
clearly labelled or identified so that the rating
of the devices and circuits they protect can be
easily recognized.
20General Requirement of Internal Power
Distribution System
- B) High Voltage Distribution-1
- Although residential and the majority of
commercial installations are adequately served
from LV-intake or HV-intake-LV distribution,
there are many industrial and some large
commercial development projects require HV intake
with extensive HV distribution system through the
sites or buildings. - For example, a hospital or an university with a
large campus, a cross harbor tunnel with
high-tension motors for ventilation fans, a very
large commercial block and a large factory with
several electrode boilers. - For these, the power company provides the main
supply point through its own switchgear complete
with bulk metering, and the customer is then
responsible for the installation of suitable high
voltage switchgear, all cabling and the required
number of on-site substations.
21General Requirement of Internal Power
Distribution System
- B) HV Ring Main Distribution system
- Just similar to the ring main system which used
by power company in their 11kV network
22General Requirement of Internal Power
Distribution System
Standard method of ring main connection mixed
with radial feeding
23General Requirement of Internal Power
Distribution System
- B) Advantage of HV Ring Main Distribution system
- Even in the event of a cable fault on the ring,
it is still possible to maintain or restore
supply to all points by opening the switches on
both sides of the fault. - Additional outlets to the ring may be easily
installed without shut downs. - Greater maintenance facilities are available both
on the ring feeder circuit breakers and the RMUs. - In additional, if the main HV switchboard is
sectionalized and fed from more than one
suppliers substations, a ring main may be
supplied from two different sections, thus
improving security. - Apart from fault conditions, it is also possible
to operate a ring main in open mode as the
preferred arrangement but, for whatever purpose
it must be ensured that neither of the section is
overload.
24General Requirement of Internal Power
Distribution System
- c) Mains - 1
- Consumer main switch shall be installed and
connected immediately before the supply co.s
meter. - A common main switch shall be installed to
control all the communal installation of the same
consumer. - The consumer main switch should incorporate
- Means of isolation and switching
- Means of protection against overcurrent, and
- Means of protection against earth leakage.
25General Requirement of Internal Power
Distribution System
- c) Mains - 2
- The main switch or circuit breaker shall have a
short-circuit breaking capacity of 40kA at low
voltage. - The characteristic of the main switch shall
disconnect within 5 seconds during an earth
fault. - The switchboard shall incorporate Castell key
interlock or other means to prevent the supply
transformers operated in parallel. All
interconnecting devices including the bus-section
switch shall be of 4-pole type with electrical
and mechanical interlock.
26General Requirement of Internal Power
Distribution System
- c) Mains - 3
- Where standby generator is installed,
mechanically interlocked 4-pole changeover device
shall be used for interconnection between the
normal and standby source. A local switch shall
be installed after a changeover device. - Single phase consumer main switch shall be of
double pole type. - A schematic wiring diagram showing the main
distribution system should be displayed near the
main switch with rating 100A or above.
27General Requirement of Internal Power
Distribution System
- c) Mains - 4
- Each consumer installation shall provided his own
earthing system - For 3 phase installation with main switch rating
of 160A and above, C.T. operated meter shall be
installed. - Warning Notice DANGER-ELECTRICITY, UNAUTHORISED
ENTRY PROHIBITED with Chinese translation shall
be painted or engraved on plastic boards
permanently fixed outside the door of
switchrooms. Each character shall not less than
50mm high.
28General Requirement of Internal Power
Distribution System
- c) Mains - 5
- The mina earthing terminal of the installation
should be bonded by a conductor of not less than
150mm2 copper to the electricity suppliers
transformer earth or metallic sheaths of service
cable.
29General Requirement of Internal Power
Distribution System
- c) LV Distribution-1
- LV distribution exist in nearly all electrical
installations. - Nearly all LV distribution are in radial from.
- The greater the impedance of the cable from the
secondary of the transformer to the LV
switchboard, the less be the potential
short-circuit current, and therefore these cables
should not be larger than necessary. - If two 1500kVA transformer were connected in
parallel, then the potential fault current could
be as much as 60MVA. As this exceeds the breaking
capacity of most standard LV switchboards ( which
is usually only 31 MVA, it would entail the
installation of much more expensive switchboard
or special high-reactance transformers, or split
the LV main switchboards into two or more
separate sections, each section being fed from a
transformer not exceeding 1500kVA.
30General Requirement of Internal Power
Distribution System
- c) LV Distribution-2
- The greater the impedance of the cable from the
secondary of the transformer to the LV
switchboard, the less be the potential
short-circuit current, and therefore these cables
should not be larger than necessary. - If two 1500kVA transformer were connected in
parallel, then the potential fault current could
be as much as 60MVA. As this exceeds the breaking
capacity of most standard LV switchboards ( which
is usually only 31 MVA, it would entail the
installation of much more expensive switchboard
or special high-reactance transformers, or split
the LV main switchboards into two or more
separate sections, each section being fed from a
transformer not exceeding 1500kVA.
31General Requirement of Internal Power
Distribution System
- c) LV Distribution-3
- If sectionised is used in switchboard interlocked
bus-section switches should be provided
32Typical ring main feeding six distribution boards
33Radial distribution diagram for typical small
commercial building meters on each floor if
required
34General Requirement of Internal Power
Distribution System
- C) Rising Mains-1
-
- 1) Cable, including prefabricated tee-off cable.
- The selection of cable as rising mains is usually
limited by its current carrying capacity (CCC) - The cable may be single-core insulted cable, or
multi-core armoured cable. - For single-core, p.v.c.-insulated. Non-armoured
cable, the largest cross sectional area is
1000mm2 giving a CCC of 1200A. - As a rule of thumb, when the demand exceeds 800A,
busduct is preferred.
35General Requirement of Internal Power
Distribution System
- c) Rising Mains-2
-
- 2) Insulated busduct (or busbar) system,
including feeder type and plug-in type busduct. - The rating of busduct could be up to 5000A or
even higher. The provision of plug-in unit
provide flexibility for tee-off at any location/
floor at anytime when demand required. - The bus may be insulated conductor or bare
conductors totally enclosed in continuous steel
trunking.
36General Requirement of Internal Power
Distribution System
- c) Rising Mains-3
- The following factors affect the selection of the
type of rising main - Load assessment
- Load distribution
- Environmental conditions such as ambient
temperature and humidity - Heights of riser
- Maximum allowable voltage drop
- Fault level
- Likelihood of alternation and future extension/
expansion being frequently required - form, types and usage of the building
- whether the wiring is to be installed during the
construction of a building, in a completed
building, or as and extension system. - Capital outlay required
- Planned duration of installation
37General Requirement of Internal Power
Distribution System
- d) Sub-main - 1
- Any building of more than four floors including
the ground floor and designed for occupation of
more than one consumer shall be provided with 3
phase electrical rising mains with 3 phase and
neutral tee-off at each floor - Type of rising mains could be one of the
followings - Insulated conductors in trunking/ conduit
- Armoured cables suitably supported
- Bare conductors in trunking
38General Requirement of Internal Power
Distribution System
- d) Sub-main - 2
- Each riding mains installation shall be protected
against overcurrent and earth leakage and shall
be equipped with suitable means of isolation. - For busbar installation having a rated capacity
not exceeding 400A in each phase of a 3 phase 4
wire system, the associated neutral busbar should
have a cross-sectional area not less than the
cross-sectional area of the phase busbar.
39General Requirement of Internal Power
Distribution System
- d) Sub-main - 3
- Riser earthing conductor for multi-tenant
installations shall be installed and the minimum
size of riser earthing conductor is 70mm2 copper. - The loadings on 3 phase rising mains should be
properly balanced. The neutral conductor should
have a suitable current carrying capacity to
cater for any imbalance or harmonic current.
40General Requirement of Internal Power
Distribution System
- d) Sub-main - 4
- The design of rising mains installation should be
agreed by the electricity supplier. - No part of the communal installation should pass
through any individual consumers unit within the
multi-consumer building. - No cable, other than that for lift installation
governed by BS5655, shall be run in lift shaft.
41General Requirement of Internal Power
Distribution System
- e) Lateral Mains - 1
- Adequate space for lateral mains and meter board
wiring shall be provided in meter room. - The loading on 3 phase lateral mains should be
balanced as far as practicable. - An installation requiring more than 60A is
required to be arranged to service a 3-phase
supply. - Appropriate correction factors shall be applied
for determining the current carrying capacity of
cables.
42General Requirement of Internal Power
Distribution System
- e) Lateral Mains - 2
- Distribution board, switchgear and busbar chamber
should have phase identification. - Where cables, conducts, ducts pass through
structural element such as floors and walls, the
openings shall be sealed by appropriate fire
resistant materials. In addition, internal
fire-resistant barriers shall be provided to
prevent the spread of fire. - Segregation of low-voltage circuits, fire alarm
circuits and telephone/ telecommunication
circuits shall be made when they run together.
43General Requirement of Internal Power
Distribution System
- e) Lateral Mains - 3
- Connection between the electricity suppliers
meter and the consumers main switch should be
not less than 4mm2 stranded copper conductor. - The insulation and/ or sheath of the cables shall
be removed for a distance of 150mm from the
connection, and replaced if necessary by suitable
heat-resisting insulation when connecting the
cable to bare conductors/ busbar.
44General Requirement of Internal Power
Distribution System
- e) Lateral Mains - 4
- Warning notice DANGER in red legible letter
with Chinese translation shall be displayed near
each distribution board, Each character shall not
less than 10mm high. - Where an installation is connected to rising
mains, agreement should be obtained from the
owner of rising mains if new current demand
exceed that before. Moreover, prior approval from
the power company should be obtained before any
alteration work is carried out.
45General Requirement of Internal Power
Distribution System
- f) Installation methods of cables
- According to he CP for WP or IEE Wiring
Regulations, cables can be in the following ways - Open or clipped direct
- Embedded direct in building ,materials
- In conduit
- In trucking
- In free air, on cleats, brackets or ladder
- In building voids
- In trenched
46General Requirement of Internal Power
Distribution System
47General Requirement of Internal Power
Distribution System
- Definition of Final Circuit
- A circuit connected directly to current using
equipment, or to a socket outlet or other outlet
points for the connection of such equipment.
48General Requirement of Internal Power
Distribution System
- Final Circuit Typical Arrangement 1
- IEE Reg. 314-01-04 states that an installation
comprises more than one final circuit, each shall
be connected to a separate way in a distribution
board and that the wiring to each final circuit
shall be electrically separate from each other.
49General Requirement of Internal Power
Distribution System
- Final Circuit Typical Arrangement 2
- Typical Arrangement shall be
- Two lighting circuits to ensure the whole unit
will not be in darkness if a fault occurs on one
lighting circuit. - Circuit for 5A or 15A socket outlet to be fed by
an exclusive radial final circuit. The maximum
loading of each socket outlet shall be 5A or 15A
respectively.
50General Requirement of Internal Power
Distribution System
- Final Circuit Typical Arrangement 3
- Circuit for 13A socket outlets complying with
BS1363. - Separate circuit for each large current-using
appliance such as room cooler, cookre or kitchen
appliance. - Lighting circuits should be electrically separate
from power circuits except that it may be
connected to bell transformers or electric
clocks.
51Conduit Wiring SystemType of Conduit
- Steel Conduit to BS 4568 Part 1
- A) Light duty type plain and conduits
- Limited to use in dry situation
- Unsuitable for bending
- Low degree of mechanical protection
- B) Heavy duty type screwed-end conduits
- Back enamel for internal use in dry situation
- Hot-dip galvanized for external use in situation
subject to dampness or water condensation - Good mechanical strength and electrical
continuity.
52Conduit Wiring SystemType of Conduit
- Steel Conduit to BS 4568 Part 1
- C) Classification for protection
53Conduit Wiring SystemType of Conduit
- Steel Conduit to BS 4568 Part 1
- D) Heavy duty hot-dip galvanized steel conduit
system is the most common use system for surface
conduit wiring and concealed conduit wiring.
Conduit is supplied in standard lengths of 4
meters and is manufactured in accordance with
BS4568.
54Conduit Wiring SystemType of Conduit
- Plastic conduits
- To BS4607 Part 1 and 2
- Characteristics light, easily bend, less
installation time, no water condensation, lower
cost - Heavy duty PVC conduits can be concealed but CPC
are required.
55Conduit Wiring SystemType of Conduit
- Copper Conduits
- High resistance to corrosion
- Last for long time
- Higher cost
- Act as excellent circuit protective conductor
(CPC)
56Conduit Wiring SystemType of Conduit
- Aluminum Conduits
- Light weight and lower cost
- Not so good in mechanical protection
-
- Flexible Conduits
- To BS731 Part 1
- Used for final connection to machinery
- CPC are required.
57Conduit Wiring SystemSizing of Conduit - 1
- EMSDs COP for the Electricity (Wiring)
Regulations provides the following tables for
ease of conduit sizing - Table A, B for 1/C PVC cables in a straight run
3m - Table C, D for 1/C PVC cable in conduit run gt 3m.
- The conduit size is considered satisfactory if
the conduit factor is equal to or exceeds the sum
of the cable factors
58Conduit Wiring SystemSizing of Conduit - 2
Table A Cable factors for short straight runs
59Conduit Wiring SystemSizing of Conduit - 3
Table B Conduit factors for short straight runs
60Conduit Wiring SystemSizing of Conduit - 4
Table C Cable factors for long straight runs,
or runs incorporating bends
61Conduit Wiring SystemSizing of Conduit - 5
Refer to Table A and B
Table D Conduit factors for runs incorporating
bends
62Conduit Wiring SystemSizing of Conduit - 6
- Example
- In a conduit installation the length of run is
10m, assuming 2 right-angle bend. What is the
conduit size to enclose four 2.5 mm2 PVC cables? - From Table C, factor for one 2.5mm2 cable 30
- Therefore, four 2.5mm2 cables 4 x 30 120
- From Table D, suitable conduit size with a factor
of 141(gt120) is 20mm. - 10m Vs 2 bends, cable factor 141
63Trunking Wiring System - 1
- Use in conditions where a considerable no. of
cables are required in an installation or where
cables are too large for drawing into conduits. - Erection time is reduced (wiring is easier and
quicker) - Multi-compartment trunking provides circuit
segregation.
64Trunking Wiring System - 2
- Typical types of trunking
- A) Steel trunking for busbar rising mains.
- B) PVC skirting 3-compartment trunking for
fitting-out wiring works where different category
circuits such as Telephone cable, CABDS cable
power supply cable are to be installed in same
run. - C) Floor trunking to BS 4678 Part 2 provides
cabling to service boxes flushed with floor level
(e.g. in open-plan office or dental room) - D) Tap-on trunking in factory for internal power
supply to machinery by plugging into the overhead
trunking. - E) Steel surface trunking for cable to BS 4678
Part 1
65Trunking Wiring System - 3
- Classification for protection against corrosion
66Sizing of Trunking - 1
Table E Cable factors for trunking
67Sizing of Trunking - 2
Table F Factors for trunking
68Sizing of Trunking - 3
- Example
- What is the maximum no. of 10mm2 PVC cables
permitted in 50mm x 50mm trunking? - From Table E, factor of 10mm2 conductor 36.3
- From Table F, factor of 50 x 50mm trunking 1037
- Maximum no. of cable 1037 36.3
- 28.56 (say 28)
69Ducting - 1
- It provided mechanical protection for cable run
in the ground or under concreted floor. - Types of ducting
- Concrete ducts
- Steel underfloor ducts
- Fibre underfloor ducts
- Maximum spacing factor is 35.
- It should be securely fixed and protected against
corrosion and mechanical damage.
70Ducting - 2
- Entries to duct must be protected against the
inflow of water. - Cables installed in underground ducts shall have
a metal sheath. - Underfloor trunking should be fabricated with
sheet steel of not less than 12mm thickness for
compartment width up to 100mm, but at least 1.6mm
thickness for compartment width over 100mm. The
minimum thickness of 1mm shall be used for the
partitions and connector material.
71Segregation of Circuits - 1
- 1) Suitable segregation between enclosed circuits
with different categories shall be provided in
wiring. For example, a low voltage circuit shall
be separated from an extra-low voltage circuit. - 2) Types of Circuit
72Segregation of Circuits - 2
- 3) Low Voltage circuit shall be segregated form
extra-low voltage circuit. Extra-low voltage
cables shall not be drawn into the same conduit
or duct, or terminated in the same box or block
as low voltage cables unless the former are
insulated for the highest voltage present in the
low voltage circuit. - 4) Cables of fire alarm and emergency lighting
circuits shall not in any circumstances be drawn
into the same conduit duct or ducting of other
cables.
73Segregation of Circuits - 3
- 5) Electrical services shall not be installed
with pipes or tubes of non-electrical services
(e.g. air, gas, oil, or water) in the same
conduit, ducting or trunking. This requirement
does not apply where the various services are
under common supervision and it is confirmed that
no mutual detrimental influence can occur. - 6) For cables of category 1,2,3 circuits that are
installed without enclosure or underground, a
minimum separation of 50mm should be provided
between different category circuits or
alternatively at least 25mm separation with slabs
of concrete inserted between the circuits and the
shortest path round the concrete should exceed
75mm.
74Segregation of Circuits - 4
- 7) Insulated bridge of at least 6mm thick should
be used for separation of surface wiring of
Category 1,2,3 circuit running across each other.
The bridge should overlap the cables by at least
25mm on either side of point of crossing. - 8) For cables of Category 4 circuit that are
installed without enclosure or underground, a
minimum separation of 300mm should be provided
between Categories or alternatively a reduced
separation with 50mm thick slabs of concrete
inserted between the circuits and the shortest
path round the concrete should exceed 180mm.
75Standard Circuit for 13A Socket Outlet
- The development of the BS1363 plug and socket
system and the associated concept of ring circuit
have made possible the provision of large numbers
of socket outlets at lower installation costs. - All ring circuits shall be run in the form of a
ring looping into the terminals of the socket
outlets and returning to same protective device.
The circuit protection conductor (cpc) should
also be run in a ring unless it is provided in
form of metallic conduit or trunking. - Typical standard circuits are tabulated as
follows
76Q A
77The End