Title: Energy Management System
1Energy Management System
2System Level Functions
- Energy / Power Managment System
- To keep power system running at optimal
conditions under constraints for the actual
operation - The Power Management system comprises the
following basic functions - Generator control (for diesel, turbine and shaft
driven generators) - Switchboard control
- Circuit Breaker control
3Low Level Control and Protection
- Engine Protection and Governing
- Protect diesel engine from damage, monitoring and
shut-down - Speed control and load sharing
- Automatic Voltage Regulators (AVR)
- Voltage control and reactive load sharing
- Protection Relays
- Protect el. System from overloads etc.
4Power Plant
Vessel Loads
Propulsion Auxilliaries
5Synkronisere generatorer
- Spenningsløs tavle
- Generator har riktig frekvens (Riktig turtall)
- Generator gir nominell spenning (Magnetisering)
- Neste generatorer
- Generator gir samme spenning som tavle
- Riktig frekvens
- Er i fase med tavle
- Avvik fører til
- Spenning Skjevfordeling av reaktiv effekt
(motordrift) - Frekvens Mekanisk belastning på generator
6Parallelldift av generatorer
- Frekvensstatikk lik
- Hastighetsfall ved lastforandring mest mulig lik
- Den minst fallende vil ellers ta all last.
- Regulering Turtallsregulering
- Spenningsstatikk
- Spenningssfall ved lastforandring
- Den minst fallende vil ta all reaktiv effekt og
prøve å drive de med lavere spenning. - Regulering Magnetisering
7SVC- Hovedfunksjoner
- The SVC Power Management comprises the following
basic functions - Diesel Generator Control
- Turbine Driven Generator Control
- Shaft Generator Control
- Switchboard Control
- Load and Consumer Control
8Tilleggsfunsjoner
- Automatic opening of bus-ties in a total blackout
situation - Automatic routing of power from the high voltage
to the low voltage switchboard after a blackout
situation has been removed - Automatic opening of the transformer high voltage
circuit breakers when a blackout occurs to
suppress transformer surge current - Automatic restarting of thruster motors from a
different switchboard after a partial blackout
9Diesel Generator Control
- Diesel Generator Control covers the following
- Manual Control Functions
- Automatic Control Functions
- Safety Functions
- Exhaust Gas Monitoring
- Alarm Inhibiting
10Manual Control Functions
- The following control functions are available
when the Diesel Generator Control function is in
the manual mode - Diesel Start/Stop
- Generator Connect/Disconnect
- Manual Load Sharing
- Fuel Selection
- Pre-lubrication
11Diesel Start/Stop
- Manual start and stop of the diesel engine of
each Diesel Driven Generator (DDG) is available
at all SVC operator stations. - A manual start will initiate a DDG start sequence
if no external start block signals are active. - Normally three engine start attempts can be
performed, and if a start is not successful after
the third attempt a start failure alarm will be
given. - A manual stop will initiate a stop sequence
provided that the DDG is not connected to a
switchboard. - When the DDG has come to a complete stop,
auxiliary systems are stopped, and preheater and
prelubrication are started.
12(No Transcript)
13Generator Connect/Disconnect
- Connect command activates the synchronising unit
which - checks if frequency and voltage deviations
between the generator and the net are within
system limits and, when the phases are equal,
closes the appropriate generator circuitbreaker. - Disconnect
- If the automatic load sharing function is
activated the engine will be loaded off to a
specified limit (typical 10) before the circuit
breaker opens. - The system will however prevent disconnection if
theresult will be overload on the remaining
diesel engines.
14- Manual frequency/load sharing control is
accomplished by - giving a DDG engine speed "increase" or
"decrease" command. - Fuel Selection
- Some diesel engines can be run on both light and
heavy fuel oil. This can be manually controlled. - Pre-lubrication
- With the automatic Pre-lubrication function
implemented, the pre-lubrication pump of a DDG
will be started and run for a setperiod of time
when the DDG is started or stopped.
15Power Management
Schematic overview of power production and
distribution
Generator symbol text instrument panel
Main Switch Board load - and consumer control
Bus tie
Emergency generator, not operational
Heavy consumers, not operational
.
16Automatic Control Functions
- The following Control Functions are available
when the Diesel Generator Control function is in
the Automatic mode - Automatic Frequency Control
- Fixed Load
- Symmetric Load Sharing
- Asymmetric Load Sharing
- Load Dependent Start/Stop
- Load Limitation
- Blackout Restart
17Automatic Frequency Control
- Speed control of a DDG
- is primarily performed by the DDG's governor
- with secondary adjustments being performed by the
Automatic Frequency Control function. - Based on measurements of the net frequency, the
Automatic Frequency Control function will
regulate the speed setpoint of the running DDGs.
18Fixed Load
- When fixed load is selected for a DDG, the load
will be kept steady for this engine. - The load variations will then be shared by the
other engines. - This selection can be overridden by the Load
Sharing system to prevent overload or reverse
power on the other connected engines. - The operator can change the fixed setpoint by
means of the "increase" and "decrease" commands.
19Load sharing
- Symmetric Load Sharing
- Engines, which are selected for symmetric load
sharing, will automatically share the same
percentage load. - Asymmetric Load Sharing
- Can be made separately for each DDG and
independent of each of the other DDGs. - The purpose of using the asymmetric load sharing
function is to burn off accumulated carbon inside
Diesel Engines by running each of them as a main
DDG with an optimum constant load for a
pre-defined period of time.
20Assymetric load sharing
- The other running DDGs are used as "topping up"
DDGs. - If the load on the "topping up" DDGs drops to a
pre-defined minimum level, the load of the "main"
DDG will be reduced. - The function can be selected when the total power
demand (load) is less than approximately 50 of
the maximum available power.
21(No Transcript)
22Load Dependent Start/Stop 1
- A load dependent start can be initiated by one of
the following configurable conditions - The consumed power exceeds the available power by
a pre-set percentage. - The difference between the available power and
the consumed power is less than a pre-set value
(in kW). - The electric current level, delivered from one
generator, exceeds a predefined limit.
23Load Dependent Start/Stop 2
- A load dependent start is delayed by a time
filter in order not to be activated by short load
peaks. - It has its triggering point defined by a set of
start limits (1 and 2) whose values depend on the
number of connected DDGs. - Each limit in the set of limits can be given a
different delay time to make it possible to have
a load dependent start with a short time delay
for large loads.
24Load Dependent Start/Stop 3
25Load dependent stop 1
- A load dependent stop can be initiated by one of
the following configurable conditions - The consumed power, represented as a percentage
of the available power from the remaining
connected DDGs, is less than a pre-defined value. - The difference between the available power from
the remaining connected DDGs and the consumed
power exceeds a pre-set value (in kW). - A load dependent stop is delayed by a time filter
in order to prevent a stop based on short load
variations.
26Load dependent stop 2
- The operator can select which DDG should be the
standby for a load dependent start/stop. - As an option, a value for the potential extra
load, based on the running status of the heavy
consumers (thrusters, large pumps etc.), can be
calculated and added to the measured generator
load within the Load Dependent Start/Stop
function.
27Load dependent stop 3
28Load control limitation
- A DDG will take up the load in a manner that is
defined by a pre-programmed load control
limitation curve. - The load limitation program will be bypassed for
conditions thatrequire a full load for reasons of
operational safety.
29Blackout Restart
- The Diesel Generator Control function detects a
blackout by monitoring - DDG circuit breakers,
- bus-ties
- shore connections
- When a blackout is detected, the DDGs with
asymmetric load sharing will be set to symmetric
load sharing. - After a blackout situation has occurred, power is
restored by reconnection of either the first
standby DDG or all standby DDGs in numerical
sequence.
30Shut Down
- If any of the following signals from a DDG enters
an alarm state, an immediate stop of the DDG will
be initiated together with a request for the
start of the next standby DDG - Low lubrication oil pressure
- High cooling water temperature
- Over speed
- Customer specified
- After a Shut Down, the DDG concerned is
automaticallyblocked by the Diesel Generator
Control function.
31Alarm Start
- Alarm Start can cause one of the following to
occur - DDG change-over with stopping of the faulty DDG
- DDG change-over with a cooling stop of the faulty
DDG - Standby DDG start without stopping the faulty DDG
- The DDG which initiated the alarm is unloaded,
disconnected and stopped with or without a
cooling down period.
32Alarm Inhibiting
- When a DDG is detected as "stopped" alarms
related to that DDG and its associated
auxiliaries will be inhibited except for those
given by pumps - Engine running (digital)
- Engine speed (analogue)
- Generator voltage
- Generator circuit breaker
33Shaft Generator Control
- Shaft Generator Control can be implemented with
and without main engine speed control. - Main engine speed control is normally not used
when the size of the SG is small compared with
that of the main engine. - For both alternatives, the main engine must be
set to "fixed speed" (not "combinatory") before
the SG can be connected to the net. - The synchronising unit controls the main engine
pilot motor.
34Switchboard Control
- The Switchboard Control functions cover the
following - Bus-tie Control
- Circuit Breaker Control
- Transformer Monitoring
35Bus-tie Control
- Bus-tie Connect
- The Automatic Frequency Control function will
adjust the frequency of the two switchboards to
be slightly different from each other (in order
to have phase rotation). - When the voltage, frequency and phase deviations
between the two switchboards are acceptable it
will Connect - Bus-tie Disconnect
- The load on the generators will be distributed to
minimise theelectric current flow in the bus-tie.
36Circuit Breaker Control
- Control and monitoring
- Circuit breakers to emergency switchboards
- Synchronisation and connection of shore and
harbour generators - Automatic reconnection of high and low voltage
bus bars and transformer circuit breakers can be
implemented (after a blackout). - An interlock system for the circuit breakers can
be implemented to avoid dangerous combinations.
37Load and Consumer Control
- Non-essential Consumers
- To protect the power generating system from
overload and to prevent blackouts - Generates a signal to trip the consumers
- This signal will be given after the load
percentage has been at a customer-defined level
for a configurable period of time.
38Heavy Consumers
- Connected by request/block signals to prevent a
blackout at start up. - All heavy consumers that are not running are
automatically blocked. - Start If sufficient power is available, the
state of the "start block" signal changes to
"non-block". - If sufficient power is not available, the standby
generator will automatically be started up. - To prevent blackout in case of a generator trip
it can calculate which thruster is to be
tripped. - This information will be continuously update to
the fast tripping logic in the switchboard(s).