Transcript and Presenter's Notes

Title: Via Christi Regional Medical Center Wichita, KS


1
Via Christi Regional Medical CenterWichita, KS
Electricity Reduction
  • Lindy Pope
  • September 14, 2007

2
Presentation Overview
  • Via Christi Overview
  • Energy Consumption Audit
  • Light Audit
  • Delamping and Timers
  • New Lamp Purchases
  • Occupancy Sensors
  • Dimming Controls
  • Air Audit
  • Employee Awareness
  • Energy Star Products
  • Monitor Power Management
  • Energy Awareness Program
  • Total Savings
  • Questions

3
Via Christi Overview
Via Christi Regional Medical Center is a
non-profit Catholic health organization based in
Wichita, Kansas.
I worked at their St. Francis campus. St.
Francis is a 1,450,000 square feet Level-1 Trauma
Center.
4
Energy Consumption Audit
12 months of energy data was collected for St.
Francis, St. Joseph, Our Lady of Lourdes, Good
Shepherd, and 30 other locations owned by Via
Christi. The 4 main buildings were placed into
Energy Stars Portfolio Manager to get a
benchmark reading.
5
Energy Consumption Audit
  • St. Francis meters were broken down into the
    location they served, what events happen in those
    locations, and per square foot.
  • All this information was collected to allow the
    hospital to focus their energy conservation on
    the locations where they use the most energy.
  • An example of the final spreadsheet can be seen
    below.

6
Light Audit
  • Overall higher lighting levels than needed.
  • Recommendations
  • ¼ Delamping- 25 locations
  • In locations that are over lit constantly
    and/or low traffic hallways
  • Turn off certain lights during the day- 21
    locations
  • Achieve through timers or connecting the
    lighting to a Building Automation System
  • 21 timers are needed a purchase price of 630
  • Benefits
  • 5,793.27 and 125,068 kWh savings in electricity
    per year
  • Removal of 336 lamps

7
New Lamp Purchases
  • A list of the current lamp purchases for St.
    Francis and St. Joseph was reviewed to determine
    if there are better options.
  • 11 lamp types were identified that should be
    changed.
  • The new lamps reduce electricity, lamp disposal,
    mercury, and/or maintenance costs
  • T-8 38,350 to 45,950 T- 8s in the 4 main
    buildings
  • Savings
  • 81,920 to 97,302 in electricity per year
  • 1,638,387 to 1,946,005 kWh per year
  • 69,030 to 82,710 mg of mercury

  Bulb Lamp Watts Rated Life Mean Lum CRI Temp Mercury Price
Current GE F32T8/SP41/ECO T-8 32 30,000 2660 78 4100K N/A 1.37
Replacement Philips F32T8/ADV841/XEW/ALTO T-8 25 36,000 2400 85 4100K 1.7 mg 3.34
8
Occupancy Sensors
  • Location Average Savings Amount Annual Savings
    (per room)
  • Private Offices 35 600 7.59 - 12.56
  • Classrooms 40 35 18.40 - 49.06
  • Conference Rooms 47 62 10.29 -
    20.58
  • Restrooms 54 121 35.50 - 59.13
  • Storage Areas 60 264 7.88 - 15.77
  • Lounge/Kitchen 35 90 13.80 - 27.60
  • Waiting Room 30 50 26.28 - 52.56
  • Exam Room 50 121 6.57 - 13.14
  • Total Savings
  • 15,497 to 28,591 in electricity per year
  • 310,119 to 571,747 kWh per year

9
Dimming Controls
  • Dimming controls offer occupants more control
    over their environment.
  • They can be used in patient rooms, offices, and
    exam rooms.
  • Occupancy sensors save more in offices then
    dimmers do.
  • Dimming controls, in exam rooms, have no
    research on potential savings.
  • Patient rooms
  • Implement dimmers during renovations or new
    construction.
  • There are 730 patient rooms.
  • The chart below shows the estimated savings per
    year if dimmers were placed in patient rooms.

Lamps Payback (years) Annual Savings per Room in kWh Total per Year in kWh
6 6 9.20 183.96 6,716 134,291
10 3.6 15.33 306.6 11,191 223,818
10
Air Audit
Equipment used UE Systems 9000 Ultrasonic Leak
Detector Compressed Air 20 leaks for a total
loss of 74.8 CFM Total loss of 7,862.98 and
157,260 kWh per year Medical Air 11 leaks for a
total loss of 22.9 CFM Total loss of 3,009.06
60,181 kWh per year Steam 5 leaks for a total
loss of 35.12 lb/hr Total loss of 3,999 and
331 Mbtu per year Total 14,871, 217,441 kWh,
and 331 Mbtu per
year
11
Energy Star Products
  • Product Savings (1 unit per year) Total
    Savings (per Year)
  • CRT/LCD Monitor 8 10,500
  • TV 3 2,190
  • Vending Machine 140 10,500
  • Computer 6 3,600
  • LED Exit Signs 12 6,000
  • Other products
  • Copiers, printers, refrigerators, DVDs, fax,
    and food service equipment
  • Total Savings
  • 27,090 per year
  • 500,000 kWh per year

12
Monitor Power Management
  • This free software from Energy Star puts all
    monitors on the network into sleep mode after a
    pre-determined time.
  • Estimated savings per monitor 10-20
  • Total Savings (based on 1,500 monitors)
  • 15,000 to 30,000 per year
  • 300,000 to 600,000 kWh per year
  • Cisco Systems Success Story
  • 20,000 monitors
  • Total savings of 528,000 or 26 per monitor
    per year
  • Only 16 hours of IT time to implement

13
Energy Awareness Program
  • Newsletter Ad
  • Makes sure employees are an active part of
    energy savings.
  • Fact Sheets
  • Will remind people of energy conservation acts
    and benefits.
  • Posters
  • Constant reminder to turn off
  • the lights and office equipment
    at night.
  • Total Estimated Savings (from
  • Energy Star)
  • 30,000-76,000 per year
  • 600,000-1,520,000 kWh per year

14
Total Savings
Project Annual Cost Savings (in electricity) Environmental Results per year Status
Delamping 1,895 Reduce 37,906 kWh Reduction of 343 lamps Recommended
Daylight Timers 4,358 Reduce 87,162 kWh Recommended
Air Audit 14,871 Reduce 217,441 kWh Reduce 331 Mbtu Recommended
Lamp Changes 81,920 to 97,302 Reduce 1,638,387 to 1,946,004 kWh Recommended
Lamp Changes 81,920 to 97,302 Reduce 69,030 to 82,710 mg mercury Recommended
Occupancy Sensors 15,497 to 28,591 Reduce 310,119 to 571,747 kWh Recommended
Dimming Controls 2,229.2 to 3,715 (offices) Reduce 44,584 to 74,307 kWh Not Recommended
Dimming Controls 6,716 to 11,191 (patient rooms) Reduce 134,291 to 223,818 kWh Recommended
Energy Awareness Program 30,000 to 76,000 Reduce 600,000 to 1,520,000 kWh Recommended
Monitor Management 15,000 to 30,000 Reduce 300,000 to 600,000 kWh Recommended
Energy Star Products 27,090 500,000 kWh Recommended

15
Total Savings
Total Savings in Energy per Year 197,347 to
291,298 3,825,306 to 5,704,078 kWh