1Presentation
2Allround UPS - Product portfolio
PROTECT 2. 33
PROTECT 3. 31
PROTECT 3. 33
PROTECT 4. 33
3PROTECT 2. 33 20kVA (10kVA) weight 250kg
without battery 490kg with integrated
battery PROTECT 2. 33 40kVA
(30kVA) weight 400 kg without battery
1500mm
4New UPS Protect 2.33
30 / 40kVA
10 / 20kVA
1500mm
1900mm
5Whats new ?
SBS
Mains
Loads
Pulse-Rectifier
Inverter
Safe load bus
Battery
UPS
6New UPS Protect 2.33
Normal-Mode (Mains available)
Loads
7BATTERY-Mode
8BYPASS-Mode
9New UPS Protect 2.33
DC voltage 2 x 400V 800V
3 x 400V
3 x 400V
Battery U DC nominal lt 20kVA 2 x 132V - 2 x
228V lt 40kVA 2 x 192V - 2 x 228V 2 x 11 - 2
x 19blocks DC range 210 - 550V
Booster and Charger
10New UPS Protect 2.33
- Rectifier
- IGBT technology
- sinusoidal input current
- low THD I lt 3 (low harmonics, compliant with
actual and future standards IEC 61000-3-12 / IEC
61000-3-4 / IEEE 519) - Cos-Phi / Power factor gt0.99
11New UPS Protect 2.33
Sinusoidal Input Current as build-in Feature
Input Voltage 100 V / screen t 5 ms /
screen Input Current THDi lt 3 20A / screen
12New UPS Protect 2.33
- Booster / Charger
- IGBT technology
- DC/DC converter
- charger mode 2 x 400V DC gt battery voltage
- booster mode / line fail battery voltage gt 2 x
400V DC - charger capacity 3kW (20kVA system)
- Battery Charging Management AeBM
13New UPS Protect 2.33
- Inverter
- IGBT technology
- High-Speed ST 10 Controller for fast dynamic
regulation - output voltage with low THD U lt 3 at nonlinear
load - able to handle capacitive and inductive loads
14New UPS Protect 2.33
- Static Bypass / Manual Bypass
- SCR technology (Thyristors)
- convection cooled
- fully 100 rated
- overload / short circuit capacity 1000 -
- synchronization to an alternate line voltage with
high harmonic content - THDu lt 10 IEC 61000-2-4 Class 3 for
industrial environment ! - synchronization range adjustable
- slew rate adjustable
- Manual bypass switch integrated
15New UPS Protect 2.33
- Battery for Protect 2 10 / 20kVA
- nominal battery voltage 2 x 132V - 2 x 228V
- integrated standard battery voltage 2 x 132V
- (2 x 11 blocks Panasonic LC-X 1228 AP )
- gt 10kVA - 30min
- gt 20kVA - 10min
- higher flexibility, to adjust any required
battery back-up time with various number of cells - avoids oversizing of battery
- extended back-up time available with external
battery
16New UPS Protect 2.33
- Battery for Protect 2 30 / 40kVA
- nominal battery voltage 2 x 192V - 2 x 228V
- integrated standard battery voltage 2 x 216V
- (2 x 18 blocks Panasonic LC-X 1228 AP)
- gt 30kVA - 10min
- gt 40kVA - 7.5min
- higher flexibility, to adjust any required
battery back-up time with various number of cells - avoids oversizing of battery
- extended back-up time available with external
battery
17New UPS Protect 2.33
External Battery Cabinet - 2 x 11 blocks
20kVA / 10min - 4 x 11 blocks 20kVA /
30min internal battery plus external battery
with 6 x 11 blocks 20kVA / 50min
18New UPS Protect 2.33
External Battery Cabinet - 2 x 18 blocks
40kVA / 7.5min - 4 x 18 blocks 40kVA /
22min internal battery plus external battery
with 6 x 18 blocks 40kVA / 40min