excitation - PowerPoint PPT Presentation

About This Presentation
Title:

excitation

Description:

its about excitation – PowerPoint PPT presentation

Number of Views:485
Slides: 32
Provided by: gauravrai
Tags:

less

Transcript and Presenter's Notes

Title: excitation


1
EXCITATION SYSTEMS
Copyright P. KundurThis material should not
be used without the author's consent
2
Excitation Systems
Outline
  1. Functions and Performance Requirements
  2. Elements of an Excitation System
  3. Types of Excitation Systems
  4. Control and Protection Functions
  5. Modeling of Excitation Systems

3
Functions and Performance Requirements of
Excitation Systems
  • The functions of an excitation system are
  • to provide direct current to the synchronous
    generator field winding, and
  • to perform control and protective functions
    essential to the satisfactory operation of the
    power system
  • The performance requirements of the excitation
    system are determined by
  • Generator considerations
  • supply and adjust field current as the generator
    output varies within its continuous capability
  • respond to transient disturbances with field
    forcing consistent with the generator short term
    capabilities
  • rotor insulation failure due to high field
    voltage
  • rotor heating due to high field current
  • stator heating due to high VAR loading
  • heating due to excess flux (volts/Hz)
  • Power system considerations
  • contribute to effective control of system voltage
    and improvement of system stability

4
Elements of an Excitation System
  • Exciter provides dc power to the generator field
    winding
  • Regulator processes and amplifies input control
    signals to a level and form appropriate for
    control of the exciter
  • Terminal voltage transducer and load compensator
    senses generator terminal voltage, rectifies and
    filters it to dc quantity and compares with a
    reference load comp may be provided if desired
    to hold voltage at a remote point
  • Power system stabilizer provides additional
    input signal to the regulator to damp power
    system oscillations
  • Limiters and protective circuits ensure that the
    capability limits of exciter and generator are
    not exceeded

5
Types of Excitation Systems
  • Classified into three broad categories based on
    the excitation power source
  • DC excitation systems
  • AC excitation systems
  • Static excitation systems
  • DC Excitation Systems
  • utilize dc generators as source of power driven
    by a motor or the shaft of main generator self
    or separately excited
  • represent early systems (1920s to 1960s) lost
    favor in the mid-1960s because of large size
    superseded by ac exciters
  • voltage regulators range from the early
    non-continuous rheostatic type to the later
    system using magnetic rotating amplifiers

6
  • Figure 8-2 shows a simplified schematic of a
    typical dc excitation system with an amplidyne
    voltage regulator
  • self-excited dc exciter supplies current to the
    main generator field through slip rings
  • exciter field controlled by an amplidyne which
    provides incremental changes to the field in a
    buck-boost scheme
  • the exciter output provides rest of its own field
    by self-excitation
  • AC Excitation Systems
  • use ac machines (alternators) as source of power
  • usually, the exciter is on the same shaft as the
    turbine-generator
  • the ac output of exciter is rectified by either
    controlled or non-controlled rectifiers
  • rectifiers may be stationary or rotating
  • early systems used a combination of magnetic and
    rotating amplifiers as regulators most new
    systems use electronic amplifier regulators

7
Figure 8.2 DC excitation system with amplidyne
voltage regulators
8
  • 2.1 Stationary rectifier systems
  • dc output to the main generator field supplied
    through slip rings
  • when non-controlled rectifiers are used, the
    regulator controls the field of the ac exciter
    Fig. 8.3 shows such a system which is
    representative of GE-ALTERREX system
  • When controlled rectifiers are used, the
    regulator directly controls the dc output voltage
    of the exciter Fig. 8.4 shows such a system
    which is representative of GE-ALTHYREX system
  • 2.2 Rotating rectifier systems
  • the need for slip rings and brushes is
    eliminated such systems are called brushless
    excitation systems
  • they were developed to avoid problems with the
    use of brushes perceived to exist when supplying
    the high field currents of large generators
  • they do not allow direct measurement of generator
    field current or voltage

9
Figure 8.3 Field controlled alternator
rectifier excitation system
Figure 8.4 Alternator supplied
controlled-rectifier excitation system
10
Figure 8.5 Brushless excitation system
11
  • Static Excitation Systems
  • all components are static or stationary
  • supply dc directly to the field of the main
    generator through slip rings
  • the power supply to the rectifiers is from the
    main generator or the station auxiliary bus
  • 3.1 Potential-source controlled rectifier
    system
  • excitation power is supplied through a
    transformer from the main generator terminals
  • regulated by a controlled rectifier
  • commonly known as bus-fed or transformer-fed
    static excitation system
  • very small inherent time constant
  • maximum exciter output voltage is dependent on
    input ac voltage during system faults the
    available ceiling voltage is reduced

Figure 8.6 Potential-source controlled-rectifier
excitation system
12
  • 3.2 Compound-source rectifier system
  • power to the exciter is formed by utilizing
    current as well as voltage of the main generator
  • achieved through a power potential transformer
    (PPT) and a saturable current transformer (SCT)
  • the regulator controls the exciter output through
    controlled saturation of excitation transformer
  • during a system fault, with depressed generator
    voltage, the current input enables the exciter to
    provide high field forcing capability
  • An example is the GE SCT-PPT.
  • 3.3 Compound-controlled rectifier system
  • utilizes controlled rectifiers in the exciter
    output circuits and the compounding of voltage
    and current within the generator stator
  • result is a high initial response static system
    with full "fault-on" forcing capability
  • An example is the GE GENERREX system.

13
Fig. 8.7 Compound-source rectifier excitation
system
Figure 8.8 GENERREX compound-controlled
rectifier excitation system IEEE1976 16
14
Control and Protective Functions
  • A modern excitation control system is much more
    than a simple voltage regulator
  • It includes a number of control, limiting and
    protective functions which assist in fulfilling
    the performance requirements identified earlier
  • Figure 8.14 illustrates the nature of these
    functions and the manner in which they interface
    with each other
  • any given system may include only some or all of
    these functions depending on the specific
    application and the type of exciter
  • control functions regulate specific quantities at
    the desired level
  • limiting functions prevent certain quantities
    from exceeding set limits
  • if any of the limiters fail, then protective
    functions remove appropriate components or the
    unit from service

15
Figure 8.14 Excitation system control and
protective circuits
16
  • AC Regulator
  • basic function is to maintain generator stator
    voltage
  • in addition, other auxiliaries act through the ac
    regulator
  • DC Regulator
  • holds constant generator field voltage (manual
    control)
  • used for testing and startup, and when ac
    regulator is faulty
  • Excitation System Stabilizing Circuits
  • excitation systems with significant time delays
    have poor inherent dynamic performance
  • unless very low steady-state regulator gain is
    used, the control action is unstable when
    generator is on open-circuit
  • series or feedback compensation is used to
    improve the dynamic response
  • most commonly used form of compensation is a
    derivative feedback (Figure 8.15)

Figure 8.15 Derivative feedback excitation
control system stabilization
17
  • Power System Stabilizer (PSS)
  • uses auxiliary stabilizing signals (such as shaft
    speed, frequency, power) to modulate the
    generator field voltage so as to damp system
    oscillations
  • Load Compensator
  • used to regulate a voltage at a point either
    within or external to the generator
  • achieved by building additional circuitry into
    the AVR loop (see Fig. 8.16)
  • with RC and XC positive, the compensator
    regulates a voltage at a point within the
    generator
  • used to ensure proper sharing VARs between
    generators bussed together at their terminals
  • commonly used with hydro units and cross-compound
    thermal units
  • with RC and XC negative, the compensator
    regulates voltage at a point beyond the generator
    terminals
  • commonly used to compensate for voltage drop
    across step-up transformer when generators are
    connected through individual transformers

18
Figure 8.16 Schematic diagram of a load
compensator
The magnitude of the resulting compensated
voltage (Vc), which is fed to the AVR, is given by
19
  • Underexcitation Limiter (UEL)
  • intended to prevent reduction of generator
    excitation to a level where steady-state
    (small-signal) stability limit or stator core
    end-region heating limit is exceeded
  • control signal derived from a combination of
    either voltage and current or active and reactive
    power of the generator
  • a wide variety of forms used for implementation
  • should be coordinated with the loss-of-excitation
    protection (see Figure 8.17)
  • Overexcitation Limiter (OXL)
  • purpose is to protect the generator from
    overheating due to prolonged field overcurrent
  • Fig. 8.18 shows thermal overload capability of
    the field winding
  • OXL detects the high field current condition and,
    after a time delay, acts through the ac regulator
    to ramp down the excitation to about 110 of
    rated field current if unsuccessful, trips the
    ac regulator, transfers to dc regulator, and
    repositions the set point corresponding to rated
    value
  • two types of time delays used (a) fixed time,
    and (b) inverse time
  • with inverse time, the delay matches the thermal
    capability as shown in Figure 8.18

20
Figure 8.17 Coordination between UEL, LOE relay
and stability limit
Figure 8.18 Coordination of over-excitation
limiting with field thermal capability
21
  • Volts per Hertz Limiter and Protection
  • used to protect generator and step-up transformer
    from damage due to excessive magnetic flux
    resulting from low frequency and/or overvoltage
  • excessive magnetic flux, if sustained, can cause
    overheating and damage the unit transformer and
    the generator core
  • Typical V/Hz limitations
  • V/Hz limiter (or regulator) controls the field
    voltage so as to limit the generator voltage when
    V/Hz exceeds a preset value
  • V/Hz protection trips the generator when V/Hz
    exceeds the preset value for a specified
    timeNote The unit step-up transformer low
    voltage rating is frequently 5 below the
    generator voltage rating

V/Hz (p.u.) V/Hz (p.u.) 1.25 1.2 1.15 1.10 1.05
Damage Time in Minutes GEN 0.2 1.0 6.0 20.0 ?
Damage Time in Minutes XFMR 1.0 5.0 20.0 ? ?
22
Modeling of Excitation Systems
  • Detail of the model required depends on the
    purpose of study
  • the control and protective features that impact
    on transient and small-signal stability studies
    are the voltage regulator, PSS and excitation
    control stabilization
  • the limiter and protective circuits normally need
    to be considered only for long-term and voltage
    stability studies
  • Per Unit SystemSeveral choices available
  • per unit system used for the main generator field
    circuit
  • chosen to simplify machine equations but not
    considered suitable for exciter quantities under
    normal operating conditions field voltage in the
    order of 0.001 (too small)
  • per unit system used for excitation system
    specifications
  • rated load filed voltage as one per unit
  • not convenient for system studies

23
  • 8.6.2 Modeling of Excitation System Components
  • The basic elements which form different types of
    excitation systems are the dc exciters (self or
    separately excited) ac exciters rectifiers
    (controlled or non-controlled) magnetic,
    rotating, or electronic amplifiers excitation
    system stabilizing feedback circuits signal
    sensing and processing circuitsSeparately
    excited dc exciter Figure 8.26 Block
    diagram of a dc exciter
  • Self-excited dc exciter
  • The block diagram of Fig. 8.26 also applies to
    the self-excited dc exciter. The value of KE,
    however, is now equal to Ref/Rg-1 as compared to
    Ref/Rg for the separately excited case.
  • The station operators usually track the voltage
    regulator by periodically adjusting the rheostat
    setpoint so as to make the voltage regulator
    output zero. This is accounted for by selecting
    the value of KE so that the initial value of VR
    is equal to zero. The parameter KE is therefore
    not fixed, but varies with the operating
    condition.

24
  • AC Exciter and Rectifier

Figure 8.28 Block diagram of an ac exciter
Figure 8.30 Rectifier regulation model
25
Windup and Non-Windup Limits
RepresentationSystem equationLimiting
action
Figure 8.34 (a) Integrator with windup limits
RepresentationSystem equationLimiting
action
Figure 8.34 (b) Integrator with non-windup
limits
26
8.6.3 Modeling of Complete Excitation
Systems Figure 8.39 depicts the general structure
of a detailed excitation system model having a
one-to-one correspondence with the physical
equipment. While this model structure has the
advantage of retaining a direct relationship
between model parameters and physical parameters,
such detail is considered too great for general
system studies. Therefore, model reduction
techniques are used to simplify and obtain a
practical model appropriate for the type of study
for which it is intended.The parameters of the
reduced model are selected such that the gain and
phase characteristics of the reduced model match
those of the detailed model over the frequency
range of 0 to 3 Hz. In addition, all significant
nonlinearities that impact on system stability
are accounted for. With a reduced model,
however, direct correspondence between the model
parameters and the actual system parameters is
generally lost.
Figure 8.39 Structure of a detailed excitation
system model
27
Standard IEEE Models
  • IEEE has standardized 12 model structures for
    representing the wide variety of excitation
    systems currently in use (see IEEE Standard
    421.5-1992)
  • these models are intended for use in transient
    and small-signal stability studies
  • Figures 8.40 to 8.43 show four examples

28
  • Type DC1A Exciter model
  • Type AC1A Exciter model

Figure 8.40 IEEE type DC1A excitation system
model. IEEE 19918
The type DC1A exciter model represents field
controlled dc communtator exciters, with
continuously acting voltage regulators. The
exciter may be separately excited or self
excited, the latter type being more common. When
self excited, KE is selected so that initially
VR0, representing operator action of tracking
the voltage regulator by periodically trimming
the shunt field rheostat set point.
Figure 8.41 IEEE type AC1A excitation system
model. IEEE 19918
The type AC1A exciter model represents a field
controlled alternator excitation system with
non-controlled rectifiers, applicable to a
brushless excitation system. The diode rectifier
characteristic imposes a lower limit of zero on
the exciter output voltage. The exciter field
supplied by a pilot exciter, and the voltage
regulator power supply is not affected by
external transients.
29
  1. Type AC4A exciter model
  2. Type ST1A exciter model

The type AC4A exciter model represents an
alternator supplied controlled rectifier
excitation system - a high initial response
excitation system utilizing full wave thyristor
bridge circuit. Excitation system stabilization
is usually provided in the form of a series
lag-lead network (transient gain reduction). The
time constant associated with the regulator and
firing of thyristors is represented by TA. The
overall gain is represented by KA. The rectifier
operation is confined to mode 1 region. Rectifier
regulation effects on exciter output limits are
accounted for by constant KC.
The type ST1A exciter model represents
potential-source controlled-rectifier systems.
The excitation power is supplied through a
transformer from generator terminals therefore,
the exciter ceiling voltage is directly
proportional to generator terminal voltage. The
effect of rectifier regulation on ceiling voltage
is represented by KC. The model provides
flexibility to represent series lag-lead or rate
feedback stabilization. Because of very high
field forcing capability of the system, a field
current limiter is sometimes employed the limit
is defined by lLR and the gain by KLR.
30
Modeling of Limiters
  • Standard models do not include limiting circuits
    these do not come into play under normal
    conditions
  • These are, however, important for long-term and
    voltage stability studies
  • Implementation of these circuits varies widely
  • models have to be established on a case by case
    basis
  • Figure 8.47 shows as an example the model of a
    field current limiter

31
(a) Block diagram representation
(b) Limiting characteristics
Figure 8.47 Field-current limiter model
Write a Comment
User Comments (0)
About PowerShow.com