Title: International Residential
1 International Residential Code for One- and
Two- Family Dwellings 2006
2Scope of the IRC
- Detached One Two Family Dwellings and
Townhouses - Separate Means of Egress
- Not more than 3 stories above grade
- Includes accessory structures
- Everything outside this scope is IBC
- IRC is a scaled down IBC listing only
requirements for items with its scope
3IBC or IRC?
4 IRC 2006 Chapter 3 Building Planning
5Purpose of Chapter 3
- The provisions of this chapter address a wide
variety of issues important to designing a
building that is both safe and usable. The
limitations placed on the materials and methods
of construction can lead to structural integrity.
Snow, wind, and seismic loading are regulated, as
are the expected live and dead loads
6Design Criteria and limitations(R301)
- Dead Load
- Live Load
- Environmental Load
- Deflection of structural members
7Live Load (Table R301.5 )
Exterior Balconies 60 psf Decks
40 psf Passenger Vehicle Garages 50
psf Attics without storage 10
psf Attics with storage
20 psf Rooms (other than bedrooms) 40
psf Sleeping Rooms
30 psf Stairs
40 psf Guardrails and
Handrails 200 psf
8Wind Load
- Somerset, Wicomico, Worcester -120 mph
- Caroline, Dorchester, Talbot 100 mph
- All other counties 90mph
- Equivalent basic wind speeds have been adjusted
to properly reflect the conversion between 3-sec
gust and fasted mile measurement. - Basic wind speed exceed 100 mph in
hurricane-prone regions or 110 mph elsewhere
shall be designed per WFCM, SSTD10, ASCE-7 etc.
9Wind Speed Conversions(Table R301.2.1.3)
10Snow Load
11Exterior Wall LocationR302
12Exterior Wall Location
Wall and openings perpendicular to lot lines
require no fire rating
Mini. 1 hr FR and openings are prohibited
lt3 feet
Mini. 1 hr FR with unprotected openings of max.
25 of wall area
gt3 feet and lt5 feet
Wall and openings require no fire rating.
Openings are not limited in area
gt5 feet
13Proj are limited
1-hr rated wall
Openings _at_ 90 º are ok
1-hr rim board
vents are ok
lt 5 clearance to lot line requires a 1-hr fire
rating
14Light, Ventilation, and Heating(R303)
- Glazing area vs. floor area of each habitable
room ( 8, 4 openable). - Bathroom ( 3 SF glazing 50 openable or 50 CFM
intermittent ventilation or 20 CFM continuous
ventilation, must vent directly to outside) - Stairway illumination (1 foot-candle)
- Required Heating ( 68 F at 3 above floor and 2
from ext. wall at the design temperature)
15 Minimum Room Area (R304)
- Minimum Floor Area
- Every house must have at least one Habitable
space at least 120 sf - All other Habitable Spaces must be at least 70
sf - Except - Kitchen
- Every Habitable Space must be at least 7 wide
in one direction
16Minimum Ceiling Heights (R305)
Habitable room shall be min. 7 feet AFF.
OR In habitable basement, Beams and girders
spaced 4 O.C. may be within 6-6 AFF
Unhabitable basement ceiling may be 6-8 AFF.
Beams, ducts may project min. 6-4 AFF.
6-6
17Ceiling Height Floor Area
18Sanitation (R306)
- Bathrooms
- Every House shall have
- Water Closet
- Lavatory
- Bathtub or Shower
- Minimum fixture spacing per IRC
19Bathroom Fixtures (R307.1)
20Minimum Fixture Clearances
15
21 MIN
4
21Glazing (R308)
- Required in all Hazardous Door and Wall Locations
11 Locations and 10 Exceptions - Exception Glazing perpendicular to plane of door
except for a wall which the door swings towards - Must have a permanent label specifying
- Glazing Type
- Applicable Testing Standard
22 24
60
60
24
24 Rule Requires Tempered Glazing only on right
side
23CLOSET IS lt 36 DEEP
Tempered Glazing is NOT required in this window
24CLOSET IS gt 36 DEEP
Tempered Glass is required in this window
25Intervening Wall
REQUIRED
NOT REQUIRED
26 60
Safety Glazing Required
2736
60
BUT NOT HERE
Window adjacent to the stairway requires safety
glazing.
2860
36
Tempered Glass is required in this window
2960
Tempered glazing required in windows surrounding
a tub
30Pools, Saunas and Hot Tubs
TEMPERED GLASS AROUND WALKWAY
29
3160
60
Tempered glazing required in the windows, doors
and porch wall
32Garages (R309)
- Opening Protection
- Separation between garage and habitable space
- Garage located less than 3 feet from the dwelling
unit on the same lot.
33Fire Separation Requirements
- Direct entry from a garage to a bedroom is not
permitted. - ½ Gypsum between garage and all habitable spaces
- Floor/ceiling assembly provide 5/8 Type X, all
supporting structural members protected with ½
Gypsum - Less than 3 from a dwelling unit on the same lot
protected with ½ gypsum applied to interior side
garage wall
342ND FLOOR JOISTS
BUT NOT HERE
Wood beam, column studs and wall carrying joists
must be protected for 20 minutes.
35Garage door header, jack studs, LVL beam and wall
carrying the floor/ceiling joists must be
protected for 20 minutes
36Min. 1-3/8 solid wood doors, Min.1-3/8 solid or
honeycomb core steel doors, 20 min fire-rated
doors.
37Detached garage/dwelling separation
Windows and other openings except complying doors
not permitted
lt3 feet
Mini. ½ G.B.
Doors permitted if Min 1-3/8 solid wood or Min.
1-3/8 steel or 20 F.R.
Not applicable to walls or openings perpendicular
to dwelling unit walls
38Emergency Escape/ Rescue Openings (R 310)
- Basement (habitable or non-habitable) and every
sleeping room - Minimum opening area (5.7 SF)
- Minimum opening height (24)
- Minimum opening width (20)
- Window wells
- Emergency escape windows under decks
39Emergency Escape/ Rescue Openings (R 310)
- Delete Section R310.1 and replace
- R310.1. Emergency escape required.
- Every sleeping room shall have at least one.
- The sill height not more than 44 above interior
standing surface - Bulkhead enclosure shall comply with R310.3
- The net clear opening shall be obtained by the
normal operation of the window or door from
inside - Escape door or window with sill below adjacent
ground shall be provided with window well per
R310.2
40THIS WINDOW MUST BE A MINIMUM OF 5.7 SQFT
- (UNLESS IT IS WITHIN 44 OF EXTERIOR GRADE IN
WHICH CASE IT MUST BE AT LEAST 5 SQFT)
MINIMUM 20 WIDE AND MINIMUM 24 TALL
LESS THAN 44 TO THE FLOOR
Windows must be at least 20 wide and 24 tall
41Window Wells (R310.2)Ladder and steps (R310.2.1)
If over 44 deep
36
36
42 Means of Egress (R311)
- At least one Exit Door required
- At least 3-0 x 6-8
-
- Side Hinged
- Operable from inside without a key
- Discharge directly from habitable area to the
outside (can not discharge through garage) - Landing same width as door and 36 in direction
of travel
43Landing not required if a guardrail is provided
at a door no longer considered an egress door
44No more than two risers for non-exit door swing
away from the stairway (R311.4.3)
45Threshold may not be more than 1-1/2 to finished
floor (R311.4.3)
46AN EXIT DOOR MUST BE SIDE-HINGED 36 WIDE
DISCHARGE TO THE OUTSIDE
A LANDING IS REQUIRED ON BOTH SIDES OF ANY EXIT
DOOR, AND THE DISTANCE BETWEEN THE THRESHOLD TO
SURFACE OUTSIDE CANNOT EXCEED 7 3/4
47Ramps (R311.6)
- Ramps
- Max. Slope 1/12 or 8.3.
- Exception Where it is technically infeasible to
comply use 1/8 or 12.5 slope. - 3x3 Landing
- Top and Bottom
- Doors open onto ramps
- Change in direction
48- Check the slope of the ramps
49Stairways (R311.5)
Enclosed, accessible space under the stairs shall
be protected by ½ GB applied to ceiling and
wall. (R311.2.2) Minimum headroom in all parts of
stairway shall not be less than 6 feet 8 inches.
Handrails shall be provided on at least one side
of each continuous run of treads or flight with
four or more risers. Circular Stairs are removed
from the Section regarding special stairways.
50Minimum Headroom (R311.5.2)
51Minimum Width for Stairways (R311.5.1)
52Riser Dimensions (R311.5.3)
- Delete Section R311.5.3. and replace
- R311.5.3 Stair treads and risers
- R311.5.3.1 Riser height - Max. 8-1/4 3/8
variance within a flight. - R311.5.3.2 Tread depth Min. 9 3/8 variance
within a flight Min. 9 wide at a point 12 from
the side where treads are narrower
53Riser Dimensions (R311.5.3)
- Delete Exception 1 of R311.5.3.3. Profile and
replace - 1. A nosing is not required if the tread depth is
10 min.
54Riser Dimensions (R311.5.3)
8-1/4
9
RISER VARIATIONS (- 3/8)
55Winder (R311.5.3.2)
56Typical Winder
10
6
57Winder with Landing
5836
36
This winder can be considered a Landing
5936
36
This winder cannot be treated as a landing
60Spiral Stair (R311.5.8.1)
Riser height 9-1/2 / Minimum headroom 6-6
6134-38
Handrail must continue to the bottom of the
stairway (R311.5.6.2)
6234-38
Handrail dimensions for a stairway
63Type I handrail
64Type II handrail
65This handrail does not provide equivalent
gripping area
66Handrail is too wide gt 2-5/8
67gt36
gt30
Porches more than 30 above grade require
guardrails with pickets
68Decks and Porches more than 30 above grade
require guardrails with pickets
69Smoke Alarms (R313)
- Smoke alarms are required
- In each bedroom
- Outside each separate sleeping area in the
immediate vicinity of the bedrooms - On each floor, including finished or unfinished
basements
70Smoke Alarms (R313)
- Smoke alarms shall be
- Inter-connected
- Permanently-wired
- Installed without a disconnecting switch
- Connected to commercial power
- Provided with Battery Backup
- This clause is removed The alarm shall be
clearly audible in all bedrooms over background
noise levels with all intervening doors closed.
but with the new reference to NPFA 72 the
requirement has not be changed
71Insulation (R316) Moisture Vapor Retarders (R318)
- Vapor Barriers are required on the warm-in-winter
side of perimeter walls, floors, and roof
assemblies - Insulation including facing materials must have a
- Flame spread index lt 25
- Smoke development index lt 450
-
72This situation required the vapor barrier to be
in substantial contact with the floor sheathing
73FSK
Vapor barrier is required behind the fireplace
74Dwelling Unit Separation (R317)
- Two Family Dwellings
- Separated (horiz. and vert.) by at least a
one-hour rated assembly - Exception Only a half-hour rated assembly is
required if units are sprinklered. - Fire-rated walls and floors tight against
exterior walls and extend to underside of roof
sheathing - Structural supports require equal or greater
rating
75Dwelling Unit Separation (R317)
- Townhouses
- Considered a separate building
- Separate one-hour rated wall assemblies
- Common two-hour rated assembly
- Common foundations permitted
- Structural roof and wall sheathing may fasten to
common wall framing - Separation wall(s) tight against exterior wall
sheathing and extend to the underside of the roof
sheathing.
764
4
Protection is provided to 4 each side of the
separation wall.
77(No Transcript)
781-HR RATED
Protective sheathing must be applied to at least
4 on each side of the separation wall.
79Protection Against Decay (R319)
- Joists are lt 18 above ground
- Girders lt 12 above ground or in beam pockets
with clearances lt ½ around sides, top and ends - Sills or Plates
- Foundations lt 8 from above ground
- Slabs in direct contact with ground (unless
separated from slab with moisture barrier) - Wood sheathing, siding or framing lt 6 above
ground
804
4
Girder Beam gt 12 above grade can be untreated
81Protection Against Decay (R319)
- Sill Plates and Rim Boards at attached decks
- Exterior posts embedded in concrete
- Exterior posts supported by concrete, brick or
wood in direct contact with ground - Exception Posts or Columns supported by 1
pedestals - Exposed Glulam timbers
- Field Treatment per AWPA M4
824
4
Wood Columns need to be treated as they are in
contact with brick in contact with the ground
834
4
Column supported by pedestal does not need to be
treated
84- Rim/Ledger needs to be treated
85Protection Against Termites (R320)
- Methods
- Soil Treatment
- Baiting System
- Pressure Treated Wood
- Natural Termite Resistant Wood
- Physical Barriers
- Protection required for
- New Houses
- Additions
862006 IRC Changes
- Hurricane prone regions with wind speed equal to
or exceeding 100 mph. - Table 302.1. Exterior walls
- Ramps Max slope 1/12
- Elevators and Platform lifts This new section
provides safety standards for the equipment.
87 88 IRC2006 Chapter 4 Foundations
89Purpose of Chapter 4
- The provisions of this chapter regulate
foundations designed and constructed under IRC
code. In addition to foundations ability to
support applied load, This chapter addresses
other factors that can affect foundation
performance. These include surface and subsurface
water control, moisture control in basement and
crawl space, minimum footing depth, etc.
90Soil and Foundation
- Types of soils (USCS)
- Soil bearing capacity / Lateral soil pressure
- Footing/Soil interactions
- Minimum concrete footing width
- Foundation types Basements, crawl space, and
slab on grade.
91Presumptive load bearing values of foundation
materials (Table R401.4.1)
92Minimum width of concrete or masonry footings
(Table R403.1)
93Minimum Footing Depth
- At least 12 below grade
- Extend below frost line
94Check footing width, reinforcement, frost depth,
and sub-grade is level ( Max 1/10 slope). Footing
shall be on and undisturbed natural soils or
engineered fill
95Monolithic slab with integral footing
96Drainage(R401.3)
- Lots shall be graded to drain surface water away
from foundation walls - Min. 6 within first 10 feet
- Min. 5 slope where physical restrictions exists
- Min. 2 for swales with 10 feet
- Min. 2 for impervious surfaces within 10 feet
97Onsite runoff shall be directed away from the
foundation walls
98Well Graded Site
99Foundation Anchors (R403.1.6)
- ½ anchor bolts with min. 7 embedment
- Spaced 6 feet on center
- Min. two bolts per sill plate section with one
bolt located not more than 12 or less than seven
bolt diameter from each end of plate section.
100This bolt is too close to the end of sill plate
101(No Transcript)
102Prescriptive Foundation Wall Designs(R404)
- Masonry Foundation Walls
- Concrete Foundation Walls
- ICF Foundation Walls
- 10 high foundation walls are included
103Laterally Supported Foundation Walls (R404.1)
- Full basement floor - 3 ½ thick
- Floor joist and blocking connected to sill plate
per Table R404.1(1) - Bolt spacing for sill plate shall be per Table
R404.1(2) - Floor blocked perpendicular to the floor joists.
- Where supporting unbalanced load on opposite
sides of the building, the building aspect ratio
L/W shall not exceed the value specified in Table
R404.1(3)
104Table R404.1(1)Top Reactions and Prescriptive
Support for Foundation Walls (Partial)
105Table R404.1(2)Maximum Plate Anchor-Bolt Spacing
for Supported Foundation Wall (Partial)
106(No Transcript)
107Table R404.1(5)Concrete Foundation Walls
(Partial)
108Concrete Foundation Walls -Example
- Soil Type ML-CL
- Wall Height 8 feet
- Unbalanced Fill 7 Feet - 4 Inches
- Wall Thickness 6 inches
- Required Reinforcement 6 _at_ 27 o.c.
109(No Transcript)
110(No Transcript)
111Retaining Walls(R404.5)
- Max. 24 unbalanced backfill
- Not laterally supported at the top
- Retaining wall shall be designed for a safety
factor of 1.5 against lateral sliding and
overturning.
112Foundation Drains (R405)
- Where they are needed
- Foundation drain materials
- Construction details
113- Drains shall be provided around all concrete or
- masonry foundations that retain earth and enclose
- habitable or usable spaces located below grade.
- ( except on well drained ground or Group I soils)
114- Drainage tiles, gravel or crushed stone drains,
- perforated pipe or other approved system.
115Foundation Waterproofing and Dampproofing (R406)
- Dampproofing
- Bituminous Coating
- 3lb/sq.yd. Acrylic Cement
- 1/8 coat Surface Bonding Cement
- Waterproofing Material
- Other Approved Methods
- Waterproofing
- 2-ply Hot Mopped Felt
- 55 lb Roll Roofing
- 6-mil PVC
- 6-mil Polyethylene
- 40-mil Polymer-Modified Asphalt
- 60-mil Flexible Polymer Cement
- 1/8 Cement-Based, Fiber-Reinforced, Waterproof
Coating - 60-mil Solvent-Free Liquid Applied Synthetic
Rubber
116Waterproofing/Dampproofing
117Typical Details
118Under Floor Space Ventilations(R408)
- Vented crawl space
- Unvented crawl space
-
119Vented Crawl Space
- The minimum net area of ventilation openings
(1150) - Five exceptions in 2003 Code are removed. (i.e.
11500 where ground surface is treated with vapor
retarder materials) - One ventilating opening shall be within 3 feet of
each corner of the building
120Unvented Crawl Space(R408.3)
- Exposed earth is covered with a continuous vapor
retarder. (Overlap 6 sealed and taped / Extend
edges 6 up the stem wall attached and sealed to
the wall) - Provide one of the following
- Continuous mechanical exhaust ventilation at
1CFM/50 SF and perimeter walls insulated - Conditioned air supply sized to deliver at rate
of 1CFM/50 SF and perimeter wall insulated. - Plenum complying with Section M1601.4 if
under-floor space is used as a plenum. -
1212006 IRC Changes
- Added requirements for foundation drainage when
6 in 10 feet can not be obtained - Added requirements for support of foundation
walls including anchor spacing - New section for retaining walls
- New section for unvented crawl space
122 123 IRC 2006 Chapter 5 Floors
124Purpose of Chapter 5
- The provisions of this chapter address the
general performance requirements for floor
system. Four types floor systems are covered in
this chapter. They are wood floor framing, wood
floors on the ground, steel floor framing and
concrete slab on the ground.
125Wood Floor Framing (R502)
- Solid sawn dimension lumbers
- End jointed lumbers
- Prefabricated wood I joists
- Engineered floor trusses
- Structural log members
126Allowable Spans
Given 2X10 floor joists SPF 2 _at_ 12 O.C./ 10
PSF DL/30 PSF LL. What is the Max. span?
127Floor Framing Details (R502.6-7)
- The end of each joist, beam or girder shall have
Min. 1-1/2 of bearing on wood or metal. 3 on
masonry and concrete - Joists framing from opposite sides over a bearing
support shall lap a minimum of 3 inches and be
nailed with mini. 3-10d face nails. - Joists shall be supported laterally at the ends
by full depth solid blocking not less than 2
nominal in thickness or full depth header, band
or rim joist.
128Drilling and Notching (R502.8)
- Notches in solid lumber (1/6 of depth, not longer
than 1/3 depth, not be located in middle 1/3
span) - The diameter of holes (not exceed 1/3 depth. Not
closer than 2 to top or bottom of the member) - The engineered wood products (as permitted by
manufacturer)
129Proper Notching
130Proper Drilling
131(No Transcript)
132(No Transcript)
133Wood Trusses(R502.11)
- Design and manufacture of MPC wood trusses
(ANSI-TPI 1 ) - Bracing
- Alterations to trusses
- Truss design drawings
134Pre-manufactured Floor Truss System
135Truss Drawing RequirementsR502.12.4
- Slope or depth, span and spacing
- Location of joints
- Bearing widths
- Design Loads
- Live and Dead for Top Bottom Chord
- Concentrated
- Wind Seismic
- Reactions
- Connections for
- Truss to Girder
- Ply to Ply
- Field Splices
- Axial forces in members
- Deflection ratio
- Permanent truss member bracing locations
136(No Transcript)
137(No Transcript)
138Care of Trusses
139(No Transcript)
140Pre-manufactured I-joist system
141Drilling and Notching
142Allowable span for structural panel (Table
R503.2.1.1(1))
143Concrete Floors on Ground(R506)
- Concrete slab shall be min. 3-1/2 thick
- Area within the foundation walls shall have all
vegetation and top soil removed. - 4 inch thick base of clean sand or gravel or
crushed stone or crushed blast-furnace slag.
Exception A base course is not needed over Group
I soil - 6 mil polyethylene or approved retarder
144Concrete Floor on Grade
145Reinforcement Placement
Slab upper third line
Slab thickness
Slab center line
Slab on grade
1462006 IRC Changes
- Added reference standard for structural log
member. - Added load path for lateral forces shall be
provided between floor framing and braced wall
panels located above or below a floor. - Added the requirement that cuts, notches, and
bored holes for engineered wood products are not
permitted unless allowed by Manufacturer or by a
RDP. - Added reinforcement support requirements for
slabs on grade
147 148 IRC2006 Chapter 6 Wall Construction
149Purpose of Chapter 6
- The provisions of this chapter contain
prescriptive requirements of the design and
construction of walls and partitions for the
support of the required dead, live, and snow
loads. In addition, the walls are a key component
in resisting the lateral forces attributable to
earthquakes and wind.
150Wood Wall Framing Materials(R602)
- Dimension lumbers
- End jointed lumber
- Structural glued laminated timber
- Structural log member
151End Jointed Lumber (R602.1.1)
152Wood Grade(R602.2)
- Minimum No.3 or stud grade lumber exception
Bearing studs not supporting floors and
nonbearing studs my be utility grade lumber
153Allowable height and spacing of wall studs
154(No Transcript)
155Wall Framing Details (R602.3)
156Drilling and Notching
- Notches shall not exceed 25 width of the stud in
Exterior or bearing walls ( not exceed 40 in
nonbearing walls) - Holes shall not be located in the same cross
section of the notch - The diameter of the hole shall not be more than
60 of stud width. The edge of the hole shall not
be less than 5/8 away from the edge of the stud.
157Drilling and Notching
- Studs located in exterior walls or bearing walls
drilled over 40 and up to 60 shall also be
doubled with no more than two successive double
studs bored. - When cutting, drilling or notching of the top
plate by more than 50 of its width, a galvanized
metal tie of not less than 16 GA and 1-1/2 wide
shall be fastened across the plate with not less
than 8-16d nails at each side.
158Proper Notching and Drilling
159Proper Notching and Drilling
160(No Transcript)
161Lateral load unbraced walls
wind
162Lateral load braced walls
wind
163Braced wall panel
- Unit of bracing
- Extend full height of the wall
- Measured by height and length
Height
Length
164Braced wall lines
Braced wall line 1
Braced wall line 2
Braced wall line 4
Braced wall line 3
FLOOR PLAN
165Braced wall line with offsets
4
Braced wall line
4
PARTIAL FLOOR PLAN
166Wall Bracing (R602.10)
- Intermittent braced wall Method 1 to 8 as
defined by R602.10.3 - Continuous wood structural sheathing (R602.10.5)
- Alternate braced wall (R602.10.6)
- Engineered design
167Intermittent Braced walls
Braced Wall
Braced Wall
Braced Wall
No bracing required
No bracing required
Elevation
168Intermittent Braced Wall
Braced Wall
Braced Wall
Braced Wall
lt25
lt12-6
Elevation
169Braced Wall Methods (R602.10.3)
170TABLE R602.10.1 (Seismic A and B or Wind lt 100
mph)
171Wall Bracing
172Alternate Braced Wall Panels (R602.10)
- Intermittent braced wall Method 1 to 8 as
defined by R602.10.3 - Continuous wood structural sheathing (R602.10.5)
- Alternate braced wall (R602.10.6)
- Engineered design
173Alternate Braced Wall Panels (R602.10)
1742006 IRC Changes
- Clarified the requirements for top plate splices
and notches - Added section for Alternate Bracing Wall Panel
Adjacent to a Door or Window Opening - Added requirement for manufacturers instructions
for window installation - Clarified the location of the Wind-Borne Debris
Protection areas
175 176IRC 2006 - Chapter 7 Wall Covering
177Interior Covering (R702)
178Interior Plaster (R702.2)
- Three Coats over Metal Lath
- Two Coats over other Bases
- Support for Gypsum or Metal Lath
- 16 o.c. for 3/8 thick
- 24 o.c. for ½ thick
179Interior Plaster (R702.2)
180Gypsum Board (R702.3)
- Fastening per Table R702.3.5 or screws of Type W
or S - Thickness 3/8 to 5/8
- Diaphragm Ceilings
- 1 ½1 Aspect Ratio
- Not Cantilevered or Rotational
- Capacity from framing
- 16 o.c. 90 plf
- 24 o.c. 70 plf
181Gypsum Board (R702.3)
182Backing for Tile (R702.4.2)
- Wall tile in Tub and Shower areas and wall panels
in Shower areas - Cement ASTM C1288
- Fiber-Cement ASTM C1325
- Glass Mat ASTM C1178
- Green Board not permitted
183Backing for Tile (R702.4.2)
184Exterior Covering (R703)
185General Requirements (R703.1)
- Provide a weather resistant exterior wall
envelope - Prevent accumulation of water in wall
- Water resistance barrier behind veneer
- Protection from condensation per Chapter 11
186Water-Resistive Barrier (R703.2)
- Material behind an exterior wall covering to
resist liquid water - No. 15 asphalt felt, free from holes
- Approved water-resistive barrier
187(No Transcript)
188Wood, Hardboard Wood Panel(R703.3)
- Vertical Joints over framing members
- Horizontal Joints lapped 1 min, shiplapped or
flashed
189Attachments (R703.4)
- Table R703.4
- Other Approved Fasteners
- Wind Speed at least 110 mph resist component and
cladding load
190Attachments (R703.4)
191Wood Shakes and Shingles(R703.5)
- Single or Double Course over ½ sheathing or
furring strips - Attached with two hot-dipped, stainless or
aluminum nails or staples
192Exterior Plaster(R703.6)
- Lath and Lath attachments corrosion resistant
- Water-Resistive Barrier
- Vapor Permeable
- Equiv. to two layer of Grade D paper
193Stone and Masonry Veneer(R703.7)
- Limited to 1 story above grade and 5 inch
thickness - Except per Table R703.7(1)
- Supporting Construction deflection limited to
1/600 - Ties at least No. 9 gage at 24 o.c. each way
supporting 2.67 sq of veneer, max
194Table R703.7(1)
195Stone and Masonry Veneer
196(No Transcript)
197EIFS (R703.9)
- Per Manufacturers specifications
- Decorative trim not faced nailed
- Terminate at least 6 above grade
198Vinyl Siding (R703.11)
- Labeled per ASTM D3679
- Siding, Soffit and accessories installed per
manufacturer
1992006 IRC Changes
- Added Horizontal Gypsum Diaphragms
- Added Water Resistive Barrier behind coverings
- Added Protection of Wood Sheathing behind Plaster
- Removed Provisions for Self-Flashing Windows
200IRC 2006 - Chapter 8 Roof Framing
201R801.2 Requirements Check and verify load path
202Lumber Grade R802.1
203Ridge Board (R802.3) 1 nominal thickness and
same depth as joists
204Rafter connections 802.3.1 per Table R8-2.5.1(9)
205R802.3.1 Ceiling Joist and rafter Connections
206Ceiling Joist Connections R802.3
207Ceiling joists as collar ties R802.3
208Ceiling joist span R802.4 per Tables R802.4(1)
and (2)
209Rafter span R802.5
Kneewall
Exterior Wall Toplate
210Figure R802.5.1 Braced Rafter Construction
211Rafter and Ceiling Joist Bearing (R802.6) 1-1/2
on Wood or Metal or 3 on Concrete
212Notching of Rafters 802.7
213Cutting and Notching Sawn Lumber R802.7.1
214Cutting and Notching (R802.7.2) Engineered wood
products
Cut truss
215Framed openings R802.9
- Frame with Header and Trimmer
- lt4 Header Single
- gt4 Header Double Header Trimmer
- gt6 Header Approved Hangers
216R802.9 Framing of Openings
217Wood Trusses (R802.10)
218Wood truss design R802.10.2
219Wood truss drawings R802.10.1
220Truss Drawing RequirementsR802.10.1
- Slope or depth, span and spacing
- Location of joints
- Bearing widths
- Design Loads
- Live and Dead for Top Bottom Chord
- Concentrated
- Wind Seismic
- Reactions
- Connections for
- Truss to Girder
- Ply to Ply
- Field Splices
- Axial forces in truss members
- Permanent truss member bracing locations
221Truss Limits R802.10.2.1
- Trusses per ANSI/TPI 1
- 60 perpendicular to truss
- 36 parallel to truss
- Not more than 2 stories each 10 max
- Roof Slope
- 312 min
- 1212 max
- 110 mph wind max
- Exposures A, B, C
- 70 psf snow load max
222(No Transcript)
223Wood truss bracing R802.10.3
224(No Transcript)
225Roof tie downs R802.11 per Table R802.11
226(No Transcript)
227Broken Truss?
228This is the plan for the trusses.
229Are Trusses braced to plan?
230Roof Sheathing R803
231Roof VentilationR806
- Openings 1/8 to ¼
- Openings 1/150
- 1/300 with Ridge and Eave vents
- 1/300 for ceiling with vapor barrier
- 1 air space above insulation
- Unvented Conditioned Attic
- No Vapor Barrier at ceiling
- Air-impermeable insulation to roof deck
- Condensing Surface above 45 degrees
232What type of venting is specified?
233How would you vent this?
234Proper framed opening?
235Another View
236Proper Connection?
237So what is the problem?
238Girder trusses must be connected per truss plan.
Check nailing.
239Are these girder trusses working together?
240Another View
241 242IRC 2006 - Chapter 9 Roof Covering
243Hail Exposure (903.5)
- Requirements based on 20 year return period
- Moderate 1.5 Hail
- Severe 2.0 Hail
- No Exposure area in Maryland
244Asphalt Shingles R905.2
Ice Damming Protection where required
245Wind Resistance of Shingles (R905.2.4.1)
- Wind Speed 110 mph or greater
- ASTM D3161, Class F
- Noted on shingle wrappers
- Special Fastening requirements apply
246(No Transcript)
247(No Transcript)
248Ice Barrier(R905.2.7.1)
- Removed temperature criteria
- Changes to history of ice forming
- Replaces eave edge with lowest edges of all
roof surfaces
249Tile and Clay Roofing R905.3
250Built-up Roofing R905.5
251Slate Shingle R905.6 412 Pitch min
252Wood Shakes R905.8 312 Pitch min
253Metal Roofing R905.10 Corrosion Resistance
254(No Transcript)
2552006 IRC Changes
- Added Hail Exposure
- Added Shingle Packaging requirements High Wind
- Modified Ice Barrier Requirements
- Clarified Recovering versus Replacement
256 257IRC 2006 - Chapter 11Energy Efficiency
258Certificate (N1101.8)
- Permanently posted on the electrical panel
- R-values
- Ceiling/Roof
- Walls
- Foundation
- Ducts
- U-factors for fenestration
- SHGC for fenestration
- HVAC efficiencies
- SWH equipment
259Climate Zones2006 IRC
260Climate Zones2006 IRC
261IRC Requirements
- Focus - building envelope
- Ceilings, walls, windows, floors, foundations
- Insulation levels, window U-factors and solar
heat gain coefficients - Air leakage
- Moisture Control
- Ducts seal and insulate
- HVAC equipment per Mechanical
- No lighting or appliance requirements
262Scope
- Residential Buildings
- IRC only for single-family, duplex, and
townhouses - Includes repairs, alterations, and additions
- e.g., window replacements
263Climate Specific Requirements
- Foundations
- Basements
- Slabs
- Crawlspaces
- Above grade walls
- Skylights, windows, and doors
- Roofs
- Solar Heat Gain Coefficient in warm climates
- Vapor retarders in cold climates
264Universal Requirements
- Duct insulation and sealing
- Infiltration control
- Including recessed cans
265Table N1102.1Insulation and Fenestration
266U-factor Alternative (N1102.1.2)
- Uses U-factors instead of R-values
267Total UA Alternative (N1102.1.3)
- Allows trade-offs across all envelope components
- Approach used in REScheck software
268Specific Insulation Requirements (N1102.2)
- Ceilings/Attics
- Mass walls
- Steel Frame walls
- Floors
- Basement walls
- Slab
- Crawl space
attic
269Ceilings
- Requirements based on
- Attic
- Assembly type
- Continuous insulation vs. Insulation between
framing
270Raised Heel Truss (N1102.2.1)
- Full height over exterior wall
- R-30 instead of R-38
- R-38 instead of R-49
271Mass Walls (N1102.2.3)
- Concrete block, concrete, insulated concrete form
(ICF), masonry cavity, brick (other than brick
veneer), earth, and solid timber/logs - Requirements
- At least 50 of the required R-value must be on
the exterior or integral to the wall - If insulation placement cannot be met, provisions
for wood frame wall insulation requirements apply
(with specific U-factor and R-value exceptions in
zones 15)
272Above Grade Walls
Insulate walls including those next to
unconditioned spaces
Dont forget to insulate rim joists
273Floors (N1102.2.5)
- Insulation must maintain permanent contact with
underside of subfloor
- Zones 12 R13
- Zones 34 R19
- Zones 4M8 R30
274Basement Walls (N1102.2.6)
- ? 50 below grade
- Zones 13 R0
- Zones 48 R10 (cont.) or R13 (cavity)
275Defining Below-Grade Walls
276Slab Edge Insulation(N1102.2.7)
- Zone 1-3 No Insulation Required
- Zone 4-8 R-10
- Downward from top of slab a minimum of 24 (Zones
4 and 5) or 48 (Zones 6, 7, and 8) - Insulation can be vertical or extend horizontally
under the slab or out from the building (must be
under 10 inches of soil)
277Slab Edge Insulation
278Crawlspace Walls (N1102.2.8)
- With insulated crawlspace walls, the space must
be mechanically vented or conditioned. (R408.3)
279Additions
- Treat as a stand-alone building
- Additions must meet the prescriptive requirements
in Table 402.1.1
280Thermally Isolated Sunrooms(N1102.2.10)
- Sunroom Attached to Structure with glazing area
gt 40 - Separation per Thermal Envelope Requirements
- Ceiling
- Zone 1-4 R-19
- Zone 5-8 R-24
- Walls R-13
- Zone 4-8
- Fenestration U lt 0.50
- Skyline U lt 0.75
281Fenestration (N1102.3)
- An area weighted average of fenestration can be
used to satisfy the U-factor SHGC requirements - Zone 6-8 Hard Limits
- Fenestration lt 0.55
- Skyline lt 0.75
- 15 sq. ft. of glazing and one opaque door may be
exempted - Fenestration replacement must meet requirements
of Table N1102.1
282Windows - SHGC (N1102.3.2)
Solar Heat Gain Coefficient
- Solar Heat Gain Coefficient
- Zone 1-3 SHGC of 0.40 or lower required
(area-weighted average) - All fenestration more than 50 glazed
283Locations with SHGC Requirements
284Mandatory Requirements Building Envelope
- Air leakage
- Thermal Envelope
- Fenestration
- Recessed lighting
- Moisture control
285Air Leakage Envelope(N1102.4.1)
- Joints, Seams, Penetrations
- Site built windows/doors
- Between jamb frame
- Utility Penetrations
- Dropped Ceiling/Chase
- Knee Walls
- Tubs Showers
- Common Walls
286Areas for Air Leakage
287Recessed Lighting (N1102.4.3)
- Type IC rated and labeled in a sealed or gasketed
enclosure - Type IC rated and labeled per ASTM E 283 with no
more than 2.0 cfm of air movement - In airtight box at least 0.5 inch from
combustible material and 3 inches from
insulation
288Moisture Control (N1102.5)
- Install on warm-in-winter side of insulation
- Use in unvented framed walls, floors, and
ceilings - Exceptions
- Moisture or its freezing will not damage
materials - Other approved means provided
- Zone 1-4
289Vapor Retarder
290Maximum U-Factors(N1102.5.1)
- Strict limits on U-factor in northern U.S.
(cannot be traded off) - Based on weighted building average individual
windows or skylights can be worse - Zone 6-8
- Windows U-0.55
- Skylights U-0.75
291Systems (N1103)
- Controls
- Heat pump supplementary heat
- Ducts
- Sealing
- Insulation
- HVAC piping insulation
- Circulating hot water systems
- Ventilation
- Equipment Sizing
292Ducts (N1103.2)
- Insulation
- R-8 outside the building envelope
- R-6 in floor trusses
- Sealing
- Per M1601.3.1
- Building Cavities
- Not be used as supply ducts
293(No Transcript)
294Piping Insulation (N1103.3 and N1103.4)
- R-2 Insulation
- HVAC systems
- Exception Piping that conveys fluids between 55
and 105F - Circulating domestic hot water systems
295Ventilation Equipment Sizing (N1103.5 and
N1103.6)
- Ventilation
- Outdoor air intakes and exhausts shall have
automatic or gravity dampers that close when the
ventilation system is not operating - Equipment Sizing
- Per IRC M1401.3
296Mechanical Systems Equipment
- Equipment efficiency set by Federal law, not the
building code
2972006 IRC Changes
- Format - New climate basis
- Envelope requirements independent of window-wall
ratio - Duct R-value (8) cannot be traded off
- Compliance Certificate
298 299IRC 2006 Appendix J Existing Buildings and
Structures
300Classification of Work
- Repair
- Renovation
- Alteration
- Reconstruction
301Repairs
- The patching, restoration and/or minor
replacement of materials, elements, components,
equipment and/or fixtures for the purpose of
maintaining those materials, elements and/or
fixtures in good and sound condition.
302Requirements for Repairs
- Materials Work shall be done using like
materials - Except 1. Hazardous materials such as asbestos
and lead based paint - 2. Plumbing materials and supplies
outlined in AJ301.1.2 - Replacement Water closet Per P2903.2
- Replacement Safety Glazing per R308.1
- Repair and replacement of existing electrical
wiring and equipment per Chapters 33 through 42 -
303Renovation
- The change, strengthening or addition of
load-bearing elements and/or the refinishing,
replacement, bracing, strengthening, upgrading or
extensive repair of existing materials, elements,
components, equipment and/or fixtures. Renovation
involves no reconfiguration of spaces.
304Requirement for Renovations
- Materials and Method the materials and method
per requirement of this code - Door and window dimensions Minor reduction that
result from the use of different materials shall
be allowed whether or not they are permitted by
this code - Interior finish Wood paneling and textile wall
covering per R315 -
305Alterations
- The reconfiguration of any space, the addition
or elimination of any door or window, the
reconfiguration or extension of any system, or
the installation of any additional equipment. -
306Requirement for Alterations
- Newly constructed elements shall comply with this
code - The work shall not increase the extent of
noncompliance - Work area shall be less than 50 of dwelling unit
- Structural loads shall be the loads applicable at
the time the building was constructed. - Unsound or dangerous structural elements
uncovered during the alteration shall be made to
comply with this code - Electrical equipment and wiring per AJ501.5
-
307Reconstruction
- The reconfiguration of a space that affects an
exit, a renovation and /or alteration when the
work area is not permitted to be occupied because
existing means of egress and fire protection
systems. or their equivalent, are not in place or
continuously maintained and/or there are
extensive alterations per AJ501.3 -
308Requirement for Reconstruction
- Stairway, handrails, and guards per AJ601.1
- Wall and ceiling finish per R315
- Separation walls use construction materials
consistent with the existing wall or complying
with requirements for new structures. - Ceiling height 6-8 ceiling in habitable spaces
created in existing basement shall be permitted.
Obstructions may project to 6-4 above basement
floor. Existing finished ceiling height in
non-habitable spaces in basements shall not be
reduced. -
3092006 IRC Changes
- Added requirements under Alternation for Ceiling
Height and Stairs - Added Requirement under Reconstruction for
Ceiling Height