Title: AUTOMATIC TRANSFER SWITCHES
1(No Transcript)
2Transfer/Bypass Isolation Switch - General Review
3Introduction
This presentation will provide you with an
overview of Russelectric Transfer/Bypass
Isolation Switches.
r
4Definition
- A manually operated device used in conjunction
with a transfer switch to provide a means of
directly connecting load conductors to a power
source and of disconnecting the transfer switch.
r
5Applications
- No Break/Overlapping Design Where a bypass
isolation switch is required but where
maintenance or testing without disturbing the
load is a priority - Load Break Design Where a bypass isolation
switch is required and simplicity of operation is
critical during an emergency condition
6Views of the Bypass Switch
Conduit Entry
Bypass/Isolation Handles
Load Connection
Normal Connection
Emergency Connection
Transfer Switch
r
Conduit Entry
7Views of the Bypass Switch
Eyebolts for lifting
Shifter Handle Plate
Bypass/Isolation Portion
Microprocessor and Accessory Plate
Transfer Switch Portion
r
8Views of the Bypass Switch
r
9Views of the Bypass Switch
r
10Views of the Bypass Switch
r
11No Break Bypass
There is no interruption in power to a critical
load during bypass operations. During the
bypass operation, the automatic switch and the
non-automatic switch are paralleled on the same
source.
r
12No Break - Normal
With the Isolating Handle in the Normal Position,
the Automatic Transfer Switch is feeding the Load
with the available source. In this case, it is
the Normal Source. If Normal is lost, the
Transfer Switch will
13No Break - Emergency
transfer to the Emergency Source.
14No Break - Normal
In this position, the Load is being fed by the
Normal Source through the Transfer Switch.
15No Break Bypass Normal
When the Bypass Handle is moved to Bypass to
Normal, the Normal Bypass Contact closes
(Makes). At this point, the Load is being fed by
the Normal source through both the Bypass Switch
and the Transfer Switch.
16No Break Bypass Normal
The Load Break Contact opens (breaks) and the
Load is being fed by the Normal Source through
the Bypass Switch. Power is still on the
Transfer Switch, however, the open Load Break
Contact is preventing the Transfer Switch from
feeding the Load.
17No Break Bypassed Normal (Isolated)
Moving the Isolating Handle to the the Isolate
Position disconnects the Transfer Switch from the
circuit. There is no power on the Transfer
Switch. The Load is being fed by the Normal
Source.
18No Break Bypassed Emergency (Isolated)
If the Emergency Source is available, it is
possible to transfer the Bypass Switch to the
Emergency Source while the Transfer Switch is
isolated.
19No Break Bypassed Emergency
Moving the Bypass Handle to Bypass to Emergency
opens the Normal Bypass Switch Contacts
20No Break Bypassed Emergency (Isolated)
and closes the Emergency Bypass Switch Contacts.
21No Break Bypassed Emergency
Moving the Isolating Handle back to the Normal
Position racks the Transfer Switch back into the
circuit. At this point, the Load is still fed by
the Emergency Source through the Bypass Switch.
Notice that the transfer switch is in a different
position than the Bypass Switch. This is not a
problem because of the Load Break Contact.
22No Break Bypassed Emergency
Moving the Isolating Handle back to the Normal
Position racks the Transfer Switch back into the
circuit. At this point, the Load is still fed by
the Emergency Source through the Bypass Switch.
Notice that the Transfer Switch is in the same
position as the Bypass Switch. Our No Break
design will not allow you to rack the Transfer
Switch back in unless it is in the same position
as the Bypass Switch. The Load is still fed
through the Bypass Switch because the Load Break
Contact is still open.
23No Break - Emergency
When the Bypass Handle is moved to Auto, the Load
Break Contact closes (makes). The Load is now
fed by the Emergency Source through the Automatic
Transfer Switch and the Bypass Switch.
24No Break - Emergency
The Bypass Switch Contacts open (break) and the
Load is being fed through only the Transfer
Switch.
25Benefits of the RTB(D)NB - No Break Design
- Power can be maintained to load during ATS
failure - Provides for a means of bypassing the ATS without
interrupting power to the load for maintenance
and ATS testing - The speed of the contacts is independent of the
speed of the bypass handle movement
r
26Features of the RTB(D)NB - No Break Design
- The load break contact (see one-line)
- Contacts and Over-Center Mechanism is identical
to the ATS - The contact speed is independent of the speed of
the bypass handle movement - A simple electro-mechanical interlock system
activated by a single push-button
r
27Operation - RTB(D)NB - No Break Design
- 1. Observe - the ATS position
- 2. Slide - the handle to the ATS source
position - 3. Push - the solenoid interlock push-
button - 4. Pull - the bypass handle down
- 5. Pull - isolating handle to isolate ATS
r
28Load Break Bypass
A load break contact opens during the bypass
operation to allow bypass to either source. The
load is interrupted during the bypass operation.
r
29Load Break - Normal
With the Isolating Handle in the Normal Position,
the Automatic Transfer Switch is feeding the Load
with the available source. In this case, it is
the Normal Source. If Normal is lost, the
Transfer Switch will
30Load Break - Emergency
transfer to the Emergency Source.
31Load Break - Normal
In this position, the Load is being fed by the
Normal Source through the Transfer Switch.
32Load Break Bypass Normal
When the Bypass Handle is moved to Bypass to
Normal, the Load Break Contact opens. At this
point, the Load is not being fed by either source.
33Load Break Bypass Normal
The Normal Bypass Switch Contacts close and the
Load is being fed by the Normal Source. Power is
still on the Transfer Switch, however, the open
Load Break Contact is preventing the Transfer
Switch from feeding the Load.
34Load Break Bypassed Normal (Isolated)
Moving the Isolating Handle to the the Isolate
Position disconnects the Transfer Switch from the
circuit. There is no power on the Transfer
Switch. The Load is being fed by the Normal
Source.
35Load Break Bypassed Emergency (Isolated)
If the Emergency Source is available, it is
possible to transfer the Bypass Switch to the
Emergency Source while the Transfer Switch is
isolated.
36Load Break Bypassed Emergency
Moving the Bypass Handle to Bypass to Emergency
opens the Normal Bypass Switch Contacts
37Load Break Bypassed Emergency (Isolated)
and closes the Emergency Bypass Switch Contacts.
38Load Break Bypassed Emergency
Moving the Isolating Handle back to the Normal
Position racks the Transfer Switch back into the
circuit. At this point, the Load is still fed by
the Emergency Source through the Bypass Switch.
Notice that the transfer switch is in a different
position than the Bypass Switch. This is not a
problem because of the Load Break Contact.
39Load Break Bypassed Emergency
The Transfer Switch automatically transfers to
the Emergency Source. The Load is still fed
through the Bypass Switch because the Load Break
Contact is still open.
40Load Break - Emergency
When the Bypass Handle is moved to Auto, the
Emergency Bypass Switch Contacts open and the
Load Break Contact closes (there is a point where
both the Emergency Bypass Switch Contacts and the
Load Break Contact is open). The Load is now fed
by the Emergency Source through the Automatic
Transfer Switch.
41Failure Scenarios
The next few slides will demonstrate the
advantages of the Load Break Bypass design in
several possible failure scenarios.
r
42Load Break Bypass Normal
The switch is bypassed to the normal source
43Load Break Bypass Normal Lose Normal
When the normal source is lost.
44Load Break Bypass Normal Engine Start
An engine start signal is sent and the emergency
source becomes available.
45Load Break Bypassed Emergency
By simply moving the bypass handle to the BYPASS
TO EMERGENCY position, the load is supplied by
the emergency source.
46Load Break - Normal
The load is being supplied by the normal source
through the transfer switch...
47Load Break Normal Lose Normal
When the normal source is lost.
48Load Break Normal Engine Start
An engine start signal is sent and the emergency
source becomes available. However, a problem
with the transfer switch prevents transfer to the
emergency source.
49Load Break Bypassed Emergency
By simply moving the bypass handle to the BYPASS
TO EMERGENCY position, the load is supplied by
the emergency source.
50Benefits of the RTB(D) - Load Break Design
- Power can be maintained to load during ATS
failure - Provides a means of bypassing the ATS for
maintenance - No elaborate system of electrical solenoids,
electrical interlocks or mechanical interlocks - Fast, Simple and Easy Operation
r
51Features of the RTB(D) - Load Break Design
- Utilizes an absolute foolproof method of
bypassing to either normal or emergency - The load break contact (see one-line)
- Contacts and Over-Center Mechanism are identical
to the ATS - The contact speed is independent of the speed of
the bypass handle movement
r
52Operation - RTB(D) - Load Break Design
- 1. Observe - that the source is available
- 2. Slide - the handle over to the
desired/available source - 3. Pull - the bypass handle down
- 4. Pull - isolating handle to isolate ATS
R
531. Observe - that the source is available
R
542. Slide - the handle over to the
desired/available source
and 3. Pull - the bypass handle down
R
554. Pull - isolating handle to isolate ATS
R
56Rack-out - Remove ATS if desired
R
57If Normal Source is lost while Isolated or Racked
out - Engine start signal will automatically be
given. When Emergency source is available,
bypass to Emergency
R
58Slide Bypass Handle over to Emergency
R
59Slide Bypass Handle over to Emergency
R
60Access - 100 through 3000 Amp
- Standard Rear or Both Sides
- Front Access Only
- Top Transition Pull Box
- Side Transition Cubicle (Left or Right)
r
61Access - 4000 Amp
- Available in Rear Access Only
r
62Power Connections
- EDS 185 - RMT/RTB Lug Data Sheet
- Compression and Provisions For
- Bus Duct Connections
r
63Construction Features
- 12-gauge steel enclosure
- Plenty of cable bending space
- No aluminum bus or components
- Bus connections - Belleville type compression
washers - 90 degree Celsius rated Lugs
- Self-aligning ATS draw-out
- Maintain Engine Start on Bypass to Emergency
R
64Ratings3-Cycle Close and Withstand
- 100 - 400 Ampere 42,000 Amps
- 600 - 800 Ampere 65,000 Amps
- 1000 - 1200 Ampere 85,000 Amps
- 1600 - 4000 Ampere 100,000 Amps
R
65r