Title: Ridgewater College Willmar Campus


1
Ridgewater CollegeWillmar Campus
  • Dryer Fire in Cosmetology Lab
  • October 28, 2009

2
Ridgewater CollegeWillmar Campus
Cosmetology
X
X
3
Incident
  • Alarm Notification County Dispatch at 845 am
  • Notification to FD 847am
  • My Opinion as to cause Chemical residue left in
    towels and ignition during drying operation.
  • The fire was in the dryer that had towels placed
    in it about 20 minutes prior to the fire being
    noticed.
  • One of the maintenance employees, John Knutson,
    was driving past and saw smoke coming from the
    dryer vent on the side of the building. He
    entered and tried to extinguish the fire with a
    5lb CO2 fire extinguisher with no success. He
    then went to activate a pull station central
    alarm and returned with a second 5lb CO2
    extinguisher and had no success. He then closed
    the door to B175 and the two sprinkler heads
    controlled the fire until the Willmar Fire
    Department arrived. There was no smoke or heat
    detection in the dryer room.
  • Fire was contained to the dryer with some
    extension to the ceiling tiles. Water damage was
    to the room of origin and the adjacent classroom
    and product storage room.
  • Smoke damage to the entire compartment with
    secondary minor smoke damage to the exiting
    corridor. Class for cosmetology was canceled for
    today although the rest of the school resumed
    classes. Food services were halted until an all
    clear was received from the County Sanitarian.
    Fire crews were on scene about 2 hours assisting
    with clean up and ventilation.

4
My Opinion
  • This fire started because of a chemical residue
    issue and ignition in the dryer. This is common
    in this type of occupancy.
  • Have ABC dry chemical extinguisher instead of CO2
    in this area.
  • Additional smoke and heat detection should be
    made available in areas of high hazard for early
    detection.
  • If it werent for the alert employee John
    Knutson, and if this fire would have happened in
    this building with NO SPRINKLERS this loss would
    have been catastrophic!!

5
Consider Buying C.A.R.E. System
  • C.A.R.E. System
  • (Combustion Auto Response Equipped)
  • C.A.R.E. drying tumblers provide some peace of
    mind in the unlikely event of a laundry fire
    within the cylinder. This feature senses for an
    abnormally high temperature within the dryer
    cylinder. If a laundry fire should start within
    the cylinder, water is sprayed on the linens from
    a multi-port manifold to saturate the load. If
    the system is activated, a warning signal can be
    sent to a remote location. The externally mounted
    C.A.R.E. system features multiple sensors and two
    water valves to assure accurate performance.
  • Option available on 50 75 lb models.

6
450 Consideration
  • Water Fire Suppression Systems are available for
    the larger model dryers
  • http//www.unimac.com/tech_pdf/70292001.pdf
  • Alliance Laundry Systems LLCAttn UniMac
    SalesShepard Street
  • PO Box 990Ripon, WI 54971-0990920-748-3121

7
Fire Location Dryers- Washers - Coat and Storage
Room
8
(No Transcript)
9
Storage Room
Dryers
Washers
Student Coat Rack
10
Control Panel
When the building engineer first attached the
fire the door was partially closed and he had to
use the extinguisher to open it so he could apply
the CO2. The tumbler drum was still turning. This
model is designed to continue operation if the
doors is open less the 2 inches. Door was
partially open because the plastic internal latch
had melted off.
V Pattern would indicate that this fire may have
started below the drum but this is not the case.
Lint Trap Area
11
(No Transcript)
12
Latch
13
The green towels are the ones used with chemicals
14
The only damage to the door was in this area of
the seal.
15
If the fire would have started below in the lint
trap area the edge would have more burn
indication.
16
Control Panel
17
Control Panel Housing
18
Control Panel Housing
19
Control Panel Housing
20
Inside Control Panel Housing
21
Lint Trap Filter Area
22
Lint Filter
Lint Trap Filter Frame
23
Air Intake at the bottom of the drum
24
Lint Trap Filter Frame Clip
25
Fuse Panel was not secured. I was told that there
were NO maintenance issues with this dryer but
yet the fuse panel door was open
3 fuses in this box
26
Wiring diagram and warranty paper for this dryer
27
(No Transcript)
28
Dryer Fire on the other side of this wall
Students Jackets etc that were in the dryer room
hanging on the clothing rack. These have smoke
and water damage.
29
5lb CO2 Extinguisher used. Might have been better
to have one 10lb or a dry chemical ABC in this
area.
30
Exhaust Tube Clean Compared to others
31
Horizontal Run of the Exhaust Tube
32
Power Box For The Dryer
33
High Heat Over Limit Switch
34
(No Transcript)
35
High voltage box for wiring to the heating
elements
36
I was informed that they had not done any work on
this dryer - loose screw or it was not put back
if the cover was removed.
37
Heating elements are behind this panel fire was
showing here when staff member was attacking the
fire. He used the 2nd CO2 extinguisher here.
38
2nd Similar Dryer Not Involved
39
(No Transcript)
40
(No Transcript)
41
(No Transcript)
42
(No Transcript)
43
Lint trap on non affected dryer relatively clean
44
Washing Machine
45
(No Transcript)
46
Sprinkler head in fire room note improper fire
stopping in the ceiling
47
Maintenance Issues
48
This door opens into a storage room which next to
the dryer room. The next series of photos is from
this room. This room had water damage. This room
has heat detection and sprinklers
49
Looking back into the dryer room from the storage
area.
50
(No Transcript)
51
Code violations where there is high pile storage
to close to the ceiling and above the sprinklers
52
(No Transcript)
53
Improper storage
54
These doors are used for smoke control and fire
separation. The problem is that these and several
other doors are not closing properly
55
These doors are used for smoke control and fire
separation. The problem is that these and several
other doors are not closing properly
56
These doors are used for smoke control and fire
separation. The problem is that these and several
other doors are not closing properly.
57
These doors are used for smoke control and fire
separation. The problem is that these and several
other doors are not closing properly.
58
Fire code issue obstacles in front of alarm
devices
59
Fire Location Dryers- Washers - Coat and Product
Storage Room
Next photo of utility room
60
Improper storage for this room
This room is on the west end of the dryer room
61
Ceiling and fire spread issues in the same
storage room