Title: SEWER
1(No Transcript)
2- SEWER
- PIPING DESIGN
- Sewer piping differs from water piping, in that
sewer pipes are not under pressure. The function
that takes place inside sewer pipes is at ambient
atmospheric pressure, and the influence of
gravity. - Sewer pipes drain because they are installed on
a slope and fluids flow downhill. The slope of
sewer lines is a consideration because most
effluent floats, and slow movement of the drain
allows solids to flow unobstructed. But if the
flow is too rapid, larger solids tend to tumble,
and become a potential for clogging a drain pipe.
Ideally, a horizontal sewer drain is never more
than half full. - Drain lines that must traverse excessive height
in a short lateral distance are installed with
vertical drops rather than excessive slope.
3- Drain pipes are installed so the slope is
consistent from the location of the fixture that
is farthest from the entrance into a public
drain, or to some suitable disposal. - For this reason, the slope of drain pipes is
critical to their efficiency. If a drain from a
fixture in an intermediate area in a system is
installed lower than the consistent point in the
drain system, effluent will collect in the low
areas, and the system will not drain well.
4flow
In addition to consistent slope, it is a
requirement of the plumbing code for all turns in
direction of piping be done with 45 degree
fittings in the direction of flow, rather than
90. This facilitates the movements of slow moving
solids through a drainage system.
5- CROSS SECTION
- THROUGH SINK
- OR LAVATORY
- DRAIN AND VENT
- Without a vent for
- supply of air to
- replace fluid in
- the drain, siphon
- action would pull
- the fluid out of
- the trap
A vent provides a path to Expel toxic sewer gas
to The atmosphere
Non-integral trap
Non-integral trap
6WATER CLOSETS - Types of Discharge
Blowout Public - Loud
Siphon Jet Residential - Quiet
The seal area in the diagrams indicate the
integral trap. Because of the water that remains
in the bowl, sewer gas is blocked from coming
into the room .
7- The sizing of pipe for drainage is far less
complex than that for water piping, as there is
no pressure involved, no rate of flow of water,
and distance makes a difference only in that
enough slope must be available to accommodate the
drainage. - Three charts are pertinent to drainage.
- The first chart lists the fixture unit value
for fixtures, which are not quite the same as for
water supply fixture units.
8(No Transcript)
9- The next chart shows the size of non-integral
traps. A non-integral trap is a drain from a
fixture to a building drain line, such as the
drain mechanism beneath the lavatory in the bath
room or beneath the sink in the kitchen.
Non-integral means that the drain is not part of
the fixture. - An example of an integral trap is a water
closet or a urinal, which have their own traps,
because of the way they are made.
10(No Transcript)
11- The third chart is the one related to
determining the collective size of drain pipes in
a system. The fixture unit values of each unit
determines the size of each segment of pipe in
the system that serves the fixtures. - The logical sequence for determining pipe size
is first to draw a plan of the building, showing
all the fixtures that are to be installed. A
line that represents the drain pipe is drawn to
connect the fixtures, which extends out of the
building to an available drain deposit, such as a
municipal sewer system. - Beginning at the high end of the system, the
fixture unit value for each segment of pipe is
shown. Then from the following chart, the size of
drain pipe is found. - The far left column indicates drain pipe
diameter. Notice the top of the chart shows
various degrees of slope for drain pipe. For
this course, use the column that allows for a
slope of ¼ per foot. The numbers in the body of
the chart are total fixture units allowed by the
pipe sizes for the slope given.
12scratch
13- Remember that a Water Closet requires a 3
drain, and you cannot install more than two Water
Closets on a 3 drain. A drain line that has
more than two water closets must be a minimum of
4 diameter, regardless of how many fixture units
it supports. - The next slide shows the drainage plan for the
residence that was used to calculate water
supply. Realize that the drainage plan is to
determine pipe sizes for what is called rough
plumbing, which is that part of drainage that is
installed below the floor and in walls. The
smallest pipe generally used in rough plumbing is
2 diameter. - Finish plumbing, or trim is the parts of the
plumbing system one can see, beneath cabinets,
under fixtures, etc., and is made of materials of
a better finish for appearance and ease of
cleaning. -
14(No Transcript)
15- The next sessions will include plumbing waste
for fixtures that are stacked more than two
story, and the method for determining vents and
size of vents.
16(No Transcript)