Title: Sizing DWV


1
Sizing DWV
  • Plumbing Systems
  • CNST 305
  • Environmental Systems 1
  • Dr. Berryman

2
Design Guidelines
  • VENTS
  • Above ground venting cannot be less than 1 ¼
  • 1 ¼ vent can handle on 1 DFU
  • Underground venting cannot be less than 2 in
    diameter
  • Vents must be a certain distance from the trap
    that it serves
  • An individual vent must not be less than ½ the
    size of the drain that it connects
  • An individual vent should not be larger than the
    drain that it connects
  • Downstream piping always bigger than the upstream
    section
  • A vent line must be 6 above flood level rim of
    the fixture before turning horizontal
  • Branch vents must slope toward a drain
  • Some codes require that at least one of the
    buildings VTR be 4 in diameter or larger
  • DRAIN/WASTE
  • All traps must be vented
  • The waste stack cannot be smaller the the largest
    horizontal branch connecting to the stack
  • At least one waste stack same as building drain
  • No branch pipe smaller than the one that proceeds
    it
  • Above ground cannot be less that 1¼
  • Below ground cannot be less than 2
  • 1 ¼ drain pipe can handle on 1 DFU
  • A drain line cannot be smaller than the trap arm
    to which it is connected
  • Use 4 trap arm for floor mounted water closets

3
Sizing Drain Waste
  • Determine number of plumbing fixtures to install
  • Layout fixtures in space to codes (ie ADA)
  • Determine site utilities
  • Generate isometric
  • Determine minimum trap size for each fixture (tbl
    2-2)
  • Determine DFU
  • Add DFU values starting from the farthest end of
    system

4
Drain/Waste Iso
  • GIVEN
  • Water Closet Siphon jet w/ flushometer valve,
    pressure 15 psi
  • Wall Urinal Siphon jet with ¾ spud/flushometer
  • Lavatory
  • TDL 100

5
Determine Trap Size for Drains
  • From Table 2-2
  • Water Closet 3
  • Wall Urinal 2
  • Lavatory 1 ¼

6
Add DFU
  • Water Closet 6 DFU
  • Wall Urinal 4 DFU
  • Lavatory 1 DFU

7
Size Waste Branches
8
Sizing Waste (cont.)
9
Sizing Vents
10
Complete DWV Isometric
11
Sizing Circuit or Loop Vents
12
Next Time
  • Test Review
  • In class homework assignment
  • Review notes and reading
  • Able to use books/notes
  • Due 10 minutes before end of class
  • We will grade and review assignment
  • Next week Start HVAC

13
  • GIVEN
  • Water Closet Siphon jet w/ flushometer valve,
    pressure 15 psi
  • Wall Urinal Siphon jet with ¾ spud/flushometer
  • Lavatory
  • TDL 100